Short answer: BS EN 12845+A2:2026 Clause 6.3.2 (TS p.36 / EN p.33) defines six configurations: ST1 is free standing goods or block stacks; ST2 is single rows of post pallets with aisles at least 2.4 m wide; ST3 is post pallets in multiple rows, double rows included; ST4 is palletized (beam pallet) racking; ST5 is solid or slatted shelving no wider than 1 m; ST6 is solid or slatted shelving wider than 1 m but no wider than 6 m.

In BS EN 12845+A2:2026 the sprinkler design for a warehouse comes out of the intersection of three inputs: the category of the goods (Category I to IV), the storage height and the storage configuration (ST1 to ST6). This article gives the configuration definitions (Clause 6.3.2), their limits (Table 2), the height/density matching for ceiling-only protection (Table 4), the in-rack sprinkler assumptions (Clause 7.2.3.3) and the positioning of intermediate sprinklers (Clause 12.5), each with its source. Source: BS EN 12845+A2:2026, Clauses 6.3, 7.2 and 12.5.

Clause 6.3.2: Definitions of ST1 to ST6

The standard classifies the storage configuration as follows (TS p.36 / EN p.33):

Code Definition
ST1 Free standing goods or block stacks
ST2 Single rows of post pallets, with aisles at least 2.4 m wide
ST3 Post pallets in multiple rows (double rows included)
ST4 Beam pallet racking (palletized rack)
ST5 Shelving, solid or slatted, no wider than 1 m
ST6 Shelving, solid or slatted, wider than 1 m but no wider than 6 m

The same clause adds a note: every storage method has its own storage height limits, which depend on the type and design of the sprinkler system (see 7.2); Figure 3 (TS p.38 / EN p.35) shows typical examples.

Clause 6.3.1 (TS p.36 / EN p.33) sets the general frame: the overall fire hazard of stored goods is a function of the combustibility of the stored materials, including their packaging, and of the storage configuration. To determine the required design criteria, the procedure shown in Figure 2 shall be followed.

The three conditions for storage in an OH class

Storage does not always have to be HHS. Clause 6.2.3 (TS p.34 / EN p.31) permits storage in occupancies classified as OH, but under three conditions:

  • a) The whole room must be protected to a design of at least OH3;
  • b) Storage must stay within the maximum storage heights given in Table 1;
  • c) No single block may cover more than 50 m², and each block must have at least 2.4 m of clear space around it.

Where the area is classified as OH4, or where conditions b) or c) cannot be met, the storage in the area shall be treated as HHS (see 6.2.4.2).

Table 1: Maximum storage heights for OH3 protection (TS p.35 / EN p.32)

Storage category Free standing or block storage (ST1) Storage configurations (ST2 to ST6)
Category I 4.0 m 3.5 m
Category II 3.0 m 2.6 m
Category III 2.1 m 1.7 m
Category IV 1.2 m 1.2 m

The table has two footnotes:

  • a) Where the storage heights exceed the values in the table, HHS protection is used (see 6.2.4.2 and 7.2).
  • b) ST6 is allowed here only as gondola shelving with a total width of 1.2 m and a solid central barrier running from the base to the top of the gondola. Any other ST6 storage needs HHS protection (see 7.2).

The gondola exception is therefore not in the text of Clause 6.2.3 but in footnote b to Table 1.

Table 2: Limits per configuration

Clause 6.3.2 (TS p.36 / EN p.33): for the sprinkler protection to be effective, the limits and protection requirements set out in Table 2 must be met.

Table 2 (TS p.37 / EN p.34):

Config. Hazard Applicable conditions Max. storage block area (m²) Width of aisles separating rows of storage (m) Min. separation clearance around the storage block area (m)
ST1 OH 50 not applicable 2.4
ST1 HH 150 not applicable 2.4
ST2 OH 50 2.4 or greater 2.4
ST2 HH unlimited 2.4 or greater not applicable
ST3 OH 50 not applicable 2.4
ST3 HH 150 not applicable 2.4
ST4 OH 50 1.2 or greater 2.4
ST4 HH without intermediate level in-rack sprinkler protection (b, c) unlimited 1.2 or greater not applicable
ST4 HH with intermediate level in-rack sprinkler protection (d) unlimited less than 1.2 not applicable
ST4 HH with intermediate level in-rack sprinkler protection (e) unlimited greater than 1.2 but less than 2.4 not applicable
ST4 HH with intermediate level in-rack sprinkler protection (f) unlimited 2.4 or greater not applicable
ST5 OH 50 1.2 or greater 2.4
ST5 HH without intermediate level in-rack sprinkler protection (b, c) 150 less than 1.2 2.4
ST5 HH with intermediate level in-rack sprinkler protection (d) 150 less than 1.2 2.4
ST5 HH with intermediate level in-rack sprinkler protection (g) unlimited 1.2 or greater not applicable
ST6 OH use HH protection
ST6 HH with intermediate level in-rack sprinkler protection (c, h) 150 1.2 2.4

Footnotes to Table 2 (TS p.37 / EN p.34):

  • a Not applicable.
  • b Intermediate level in-rack sprinkler protection is recommended.
  • c The method of protection is limited to risks where the ceiling sprinklers are less than 4 m above the top level of the stored goods. Where the ceiling sprinklers are more than 4 m above the top level of the goods, intermediate level in-rack sprinklers shall be used.
  • d Intermediate level in-rack sprinkler protection is assumed to be hydraulically in operation in three racks (see 7.2.3.3).
  • e Assumed to be in operation in two racks.
  • f Assumed to be in operation in one rack.
  • g Assumed to be in operation in one or two racks.
  • h Where it is not possible to install intermediate sprinklers in ST6 storage, longitudinal and transverse full height barriers shall be fitted longitudinally within each shelf. Full height barriers shall be constructed to EN 13501-1 Euroclass A1, A2 or a national equivalent.

Ceiling protection: Table 4

Clause 7.2.2.2 (TS p.39 / EN p.36): Table 4 specifies, by category, the appropriate design density and area of operation and the maximum permitted storage height for various storage types with roof or ceiling protection only. Where the storage heights exceed the limit, intermediate level in-rack sprinklers shall be provided in accordance with 7.2.3.

Table 4 (TS p.41 / EN p.38), maximum permitted storage height (m):

ST1 free standing or block stacking

Cat. I Cat. II Cat. III Cat. IV Design density (mm/min) Area of operation (wet/pre-action)
5.3 4.1 2.9 1.6 7.5 260 m²
6.5 5.0 3.5 2.0 10.0 260 m²
7.6 5.9 4.1 2.3 12.5 260 m²
- 6.7 4.7 2.7 15.0 260 m²
- 7.5 5.2 3.0 17.5 260 m²
- - 5.7 3.3 20.0 300 m²
- - 6.3 3.6 22.5 300 m²
- - 6.7 3.8 25.0 300 m²
- - 7.2 4.1 27.5 300 m²
- - - 4.4 30.0 300 m²

ST2 post pallets in single rows and ST4 palletized racks

Cat. I Cat. II Cat. III Cat. IV Design density (mm/min) Area of operation
4.7 3.4 2.2 1.6 7.5 260 m²
5.7 4.2 2.6 2.0 10.0 260 m²
6.8 5.0 3.2 2.3 12.5 260 m²
- 5.6 3.7 2.7 15.0 260 m²
- 6.0 4.1 3.0 17.5 260 m²
- - 4.4 3.3 20.0 300 m²
- - 4.8 3.6 22.5 300 m²
- - 5.3 3.8 25.0 300 m²
- - 5.6 4.1 27.5 300 m²
- - 6.0 4.4 30.0 300 m²

ST3 post pallets in multiple rows and ST5/ST6 solid or slatted shelves

Cat. I Cat. II Cat. III Cat. IV Design density (mm/min) Area of operation
4.7 3.4 2.2 1.6 7.5 260 m²
5.7 4.2 2.6 2.0 10.0 260 m²
- 5.0 3.2 2.3 12.5 260 m²
- - - 2.7 15.0 260 m²
- - - 3.0 17.5 260 m²

The note to Table 4: dry and alternate systems should be avoided in High Hazard storage, particularly with the more combustible products (higher categories) and with high storage. Where it is nevertheless necessary to install a dry or alternate system, the area of operation shall be increased by 25 %.

Clause 7.2.2.1 (TS p.39 / EN p.36): for buildings exceeding 12 m, the authorities shall be consulted.

Excessive clearance

Clause 7.2.2.3 (TS p.39-40 / EN p.36-37): the values in Table 4 shall be used to determine the clearance. Where the clearance, that is the distance between the storage height and the ceiling sprinkler deflector, exceeds 4 m, one of the following options shall be applied:

  • Option 1: the density is increased by 2.5 mm/min for the first excess metre. For each further excess metre the water density is increased by 1 mm/min. A K-factor of at least K115 (K8.0) shall be used.
  • Option 2: intermediate level in-rack sprinklers shall be provided in accordance with 7.2.3.

Intermediate level in-rack sprinklers

Clause 7.2.3.1 (TS p.40 / EN p.37): where more than 50 intermediate level sprinklers are installed in racks, they shall not be supplied from the same control valve set as the roof or ceiling sprinklers.

Clause 7.2.3.2 (TS p.40 / EN p.37): the roof or ceiling sprinklers must have a design density of at least 7.5 mm/min over an area of operation of 260 m². If goods are stored higher than the top level of intermediate protection, the roof or ceiling sprinklers must be designed to the criteria of Table 5 (TS p.42 / EN p.39).

Clause 7.2.3.3 (TS p.40 / EN p.37): for the purpose of hydraulic calculation, 3 sprinklers shall be assumed to operate simultaneously at the hydraulically most remote position at each in-rack sprinkler level, up to a maximum of three levels. According to the width of the rack aisles:

Aisle width Number of racks assumed in operation
2.4 m or greater 1 rack
1.2 m ≤ width < 2.4 m 2 racks
less than 1.2 m 3 racks

NOTE: it is not necessary to assume that more than three rows of sprinklers in the vertical plane and more than three in the horizontal plane operate simultaneously.

Clause 7.2.3.4 (TS p.40 / EN p.37): both the in-rack sprinklers and the ceiling sprinklers associated with them must always be fully hydraulically calculated (see 13.1). A NOTE gives the minimum pressure at any operating sprinkler as 2.0 bar (see 13.4.4); Clause 13.4.4 itself lists 0.50 bar for HHP and HHS (except in-rack sprinklers), 1.00 bar for K115 (K8.0) in-rack sprinklers and 2.00 bar for K80 (K5.6) in-rack sprinklers.

This is consistent with the list of mandatory full calculations in Clause 13.1 (TS p.85 / EN p.82): full calculations shall always be used for layouts with intermediate level HHS sprinklers and for gridded or looped layouts.

Positioning of intermediate sprinklers: Clause 12.5

Clause 12.5.1 General (TS p.81 / EN p.78): in double row racks the sprinklers must sit in the longitudinal flue spaces, preferably where these cross a transverse flue, and the arrangement must let water from operating intermediate-level sprinklers penetrate the stored goods. Goods stored back to back in a rack must leave a longitudinal flue of at least 0.15 m, with pallet stops where necessary, and goods stored side by side a transverse flue of at least 0.1 m. Between the sprinkler deflectors and the top of the storage there must be a clearance of at least 0.10 m for flat spray sprinklers and 0.15 m for other sprinklers.

Clause 12.5.2 (TS p.81 / EN p.78): neither the height from the floor to the lowest intermediate level nor the vertical spacing between levels may exceed 3.50 m or two tiers, whichever is the less. Unless all roof or ceiling sprinklers are less than 4 m above the top of the storage, an intermediate level shall be installed above the highest level of the storage. In no case shall the highest intermediate sprinkler level be installed more than one tier below the top of the storage.

Clause 12.5.3 (TS p.81 / EN p.78):

  • For Category I or II goods: where possible, sprinklers shall be installed in the longitudinal flue at the intersection with every second transverse flue, staggered relative to the row above. The horizontal distance between sprinklers shall not exceed 3.75 m and the product of the horizontal and vertical distances shall not exceed 9.8 m².
  • For Category III or IV goods: sprinklers shall be installed in the longitudinal flue at the intersection with every transverse flue. The horizontal distance shall not exceed 1.9 m and the product of the horizontal and vertical distances shall not exceed 4.9 m².

Clause 12.5.4 (TS p.83 / EN p.80): the number of rows of sprinklers per level is determined by the total rack width. For racks placed back to back, the total width is the sum of the individual rack widths plus the gap between them. Each level needs one row of sprinklers for every 3.2 m of rack width; wherever possible they must be placed in the flue spaces.

Clause 12.5.5 HHS intermediate sprinklers in racks without shelves (TS p.83 / EN p.80): for palletized rack storage and multiple row drive-through storage (type ST4 in Figure 3 and Table 4), intermediate sprinklers shall be installed as follows:

  • a) single row racks no wider than 3.2 m shall be protected by single rows of sprinklers fitted at the tier levels shown in Figures 13 and 14;
  • b) double row racks no wider than 3.2 m shall be protected by sprinklers centrally in the longitudinal flue space, at the ends of the stack and at the tier levels in Figures 13 and 14;
  • c) double or multiple row racks wider than 3.2 m but no wider than 6.4 m shall be protected by two rows of sprinklers installed at no more than 3.2 m spacing. Each row shall be the same distance from the nearest rack edge. At each level the sprinklers in each line shall be located in the same set of transverse flues.

The same clause adds: where any shelf or structural steel can significantly obstruct the water distribution of a sprinkler, an additional sprinkler shall be provided to give water distribution to the area screened from water.

Intermediate sprinklers in ST5 and ST6: above the shelf

Clause 12.5.6 (TS p.84 / EN p.81): where intermediate sprinklers are needed, a row must be installed above every shelf, the top shelf included if the roof or ceiling sprinklers are more than 4 m above the goods or if water access to the goods is restricted, positioned as shown in Table 21 and Figure 15. Rows must be no more than 3.5 m apart vertically.

A single row of sprinklers must be centred over the shelves; with double rows, each row must be equally distant from the nearest shelf edge. From the shelf end parallel to the range pipes to the nearest sprinkler, the distance must be the lesser of half the sprinkler spacing along the range lines and 1.4 m (TS p.85 / EN p.82).

Table 21 (TS p.85 / EN p.82)

Shelf width s Sprinkler rows Max. spacing along a row (m) Max. spacing between rows (m)
ST5: s ≤ 1.0 m 1 2.8 -
ST6: 1.0 m < s ≤ 3.0 m 1 2.8 -
ST6: 3.0 m < s ≤ 6.0 m 2 2.8 2.8

Configurations the standard does not cover

The term "mobile rack" does not appear in the text of BS EN 12845+A2:2026; there is no separate class, limit or "special consideration" note for that configuration. In the same way there is no provision giving a typical height range for drive-in storage. The configurations the standard classifies are the six types in Clause 6.3.2; Clause 12.5.5 mentions "multiple row drive-through storage" only in the context of ST4.

Field note

Footnotes d, e, f and g to Table 2 and Clause 7.2.3.3 give the same information from two places: as the aisle narrows, the number of racks entering the hydraulic calculation rises. This shows that aisle width is not only a layout decision but a direct water demand parameter; when the rack arrangement changes, the hydraulic calculation has to be redone. Clause 20.3.2.2 requires that change to be caught in the quarterly routine. (This paragraph is engineering commentary.)

Frequently Asked Questions

What are ST1 to ST6 and how are they defined?

BS EN 12845+A2:2026 Clause 6.3.2 (TS p.36 / EN p.33) defines six configurations: ST1 is free standing goods or block stacks; ST2 is single rows of post pallets with aisles at least 2.4 m wide; ST3 is post pallets in multiple rows, double rows included; ST4 is palletized (beam pallet) racking; ST5 is solid or slatted shelving no wider than 1 m; ST6 is solid or slatted shelving wider than 1 m but no wider than 6 m.

What block area and perimeter clearance apply to storage in an OH class?

Clause 6.2.3 (TS p.34 / EN p.31) permits storage in OH areas under three conditions: the whole room must be protected to at least OH3; storage must stay within the Table 1 maximum heights; and no single block may exceed 50 m², with at least 2.4 m of clear space around each block. Where the area is classified as OH4, or where b) or c) cannot be met, the storage is treated as HHS.

What are the HH block area limits in Table 2?

BS EN 12845+A2:2026 Table 2 (TS p.37 / EN p.34): ST1 HH 150 m² with 2.4 m perimeter clearance; ST2 HH unlimited, aisles 2.4 m or greater; ST3 HH 150 m² and 2.4 m; ST4 HH unlimited (the in-rack assumptions vary with aisle width); ST5 HH 150 m² with aisles less than 1.2 m where there is no in-rack protection, and unlimited with in-rack protection and aisles 1.2 m or greater; ST6 HH only with in-rack protection, 150 m², aisle 1.2 m and perimeter clearance 2.4 m.

How many racks are assumed to be hydraulically in operation for in-rack sprinklers?

Clause 7.2.3.3 (TS p.40 / EN p.37): for the purpose of hydraulic calculation, 3 sprinklers shall be assumed to operate simultaneously at the most unfavourable position at each in-rack sprinkler level, up to a maximum of three levels. Where the rack aisles are 2.4 m or wider, only one rack is assumed to be in operation; where they are less than 2.4 m but 1.2 m or more, two racks; and where they are less than 1.2 m, three racks.

Are intermediate sprinklers placed below or above the shelf?

Above. Clause 12.5.6 (TS p.84 / EN p.81): where ST5 and ST6 solid or slatted shelving needs intermediate sprinklers, a row must be fitted above every shelf, the top shelf included if the roof or ceiling sprinklers are more than 4 m above the goods or if water access to the goods is restricted, positioned as in Table 21 and Figure 15, with rows no more than 3.5 m apart vertically.

References

  • BS EN 12845+A2:2026 Clause 6.2.3 Ordinary Hazard (TS p.34 / EN p.31)
  • BS EN 12845+A2:2026 Table 1 and its footnotes, Clause 6.2.4 (TS p.35 / EN p.32)
  • BS EN 12845+A2:2026 Clauses 6.3.1 and 6.3.2 Storage configuration (TS p.36 / EN p.33)
  • BS EN 12845+A2:2026 Table 2 and footnotes a to h (TS p.37 / EN p.34)
  • BS EN 12845+A2:2026 Figure 3, Clause 7.1 (TS p.38 / EN p.35)
  • BS EN 12845+A2:2026 Table 3, Clauses 7.2.1, 7.2.2.1, 7.2.2.2, 7.2.2.3 (TS p.39 / EN p.36)
  • BS EN 12845+A2:2026 Clause 7.2.2.3 Options 1 and 2, 7.2.3.1 to 7.2.3.4 (TS p.40 / EN p.37)
  • BS EN 12845+A2:2026 Table 4 (TS p.41 / EN p.38)
  • BS EN 12845+A2:2026 Table 5 (TS p.42 / EN p.39)
  • BS EN 12845+A2:2026 Clauses 12.5.1, 12.5.2, 12.5.3 (TS p.81 / EN p.78)
  • BS EN 12845+A2:2026 Clauses 12.5.4, 12.5.5 (TS p.83 / EN p.80)
  • BS EN 12845+A2:2026 Clause 12.5.6 (TS p.84 / EN p.81)
  • BS EN 12845+A2:2026 Table 21, Clause 13.1 (TS p.85 / EN p.82)
  • BS EN 12845+A2:2026 Clause 13.4.4 (TS p.105 / EN p.102)
  • BS EN 12845+A2:2026 Clause 20.3.2.2 Review of the hazard (TS p.123 / EN p.120)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.