Short answer: BS EN 12845+A2:2026 Clause 9.3.2.1 (TS p.50 / EN p.47): a tank's effective capacity must be calculated as the volume lying between its normal water level and its lowest effective water level. Where the tank is not frost proof, its normal water level must be raised by at least 1.0 m and ice venting is required. Enclosed tanks need easy access, and every tank other than an open reservoir needs a water level indicator that can be read from outside.

The sprinkler storage tank is governed by Clause 9.3 of BS EN 12845+A2:2026 (TS p.49-54 / EN p.46-51). This article gives the tank types, the definition of effective capacity, Tables 9 and 10 for pre-calculated systems, the volume formula for fully calculated systems, the refill times, the conditions for reduced capacity tanks, the suction pipe clearances (Table 12) and the strainer rules, each with its source.

9.3.1: Types of tank

The standard lists three types (TS p.49 / EN p.46). Storage tanks shall be one or more of the following:

  • a pump suction tank;
  • a gravity tank;
  • a reservoir.

9.3.2.1: Effective capacity and general rules

Clause 9.3.2.1 General (TS p.50 / EN p.47): every system has a specified minimum water volume, and that volume must come from one of two arrangements:

  • a full capacity tank, whose effective capacity is not less than the specified volume;
  • a reduced capacity tank (see 9.3.4), in which the tank's effective capacity and the automatic infill together provide the required volume.

Effective capacity, by definition: it must be calculated as the difference between the tank's normal water level and its lowest effective water level.

Three further rules:

  • A tank that is not frost proof must have its normal water level raised by at least 1.0 m and must be given ice venting.
  • Enclosed tanks must offer easy access.
  • Every tank other than an open reservoir must have a water level indicator that can be read from outside.

Pre-calculated systems: Table 9 and Table 10

Clause 9.3.2.2 (TS p.50 / EN p.47): for pre-calculated LH and OH systems, the minimum effective water volume must be taken from Table 9. Those volumes must be kept exclusively for the sprinkler system.

Table 9: Minimum water volume for pre-calculated LH and OH systems (TS p.50 / EN p.47)

Group Height h of the highest sprinkler above the lowest sprinkler (m) Minimum water volume (m³)
LH (wet or pre-action) h ≤ 15 9
LH (wet or pre-action) 15 < h ≤ 30 10
LH (wet or pre-action) 30 < h ≤ 45 11
OH1 wet or pre-action h ≤ 15 55
OH1 wet or pre-action 15 < h ≤ 30 70
OH1 wet or pre-action 30 < h ≤ 45 80
OH1 dry or alternate / OH2 wet or pre-action h ≤ 15 105
OH1 dry or alternate / OH2 wet or pre-action 15 < h ≤ 30 125
OH1 dry or alternate / OH2 wet or pre-action 30 < h ≤ 45 140
OH2 dry or alternate / OH3 wet or pre-action h ≤ 15 135
OH2 dry or alternate / OH3 wet or pre-action 15 < h ≤ 30 160
OH2 dry or alternate / OH3 wet or pre-action 30 < h ≤ 45 185
OH3 dry or alternate / OH4 wet or pre-action h ≤ 15 160
OH3 dry or alternate / OH4 wet or pre-action 15 < h ≤ 30 185
OH3 dry or alternate / OH4 wet or pre-action 30 < h ≤ 45 200
OH4 dry or alternate Use HH protection

NOTE: Excluding sprinklers in the sprinkler valve room.

Table 10: Minimum water volume for pre-calculated HHP and HHS systems (TS p.51 / EN p.48)

Design density not exceeding (mm/min) Wet systems (m³) Dry systems (m³)
7.5 225 280
10 275 345
12.5 350 440
15 425 530
17.5 450 560
20 575 720
22.5 650 815
25 725 905
27.5 800 1 000
30 875 1 090

The dry system column is about 25 % higher than the wet column (for example 225 → 280 at 7.5 mm/min and 875 → 1 090 at 30 mm/min). These volumes too are reserved solely for the sprinkler system.

Fully calculated systems

Clause 9.3.2.3 (TS p.51 / EN p.48): The minimum effective volume of water shall be calculated by multiplying the maximum flow demand (Qmax) by the duration specified in 8.1.1.

Clause 8.1.1 Duration (TS p.45 / EN p.42) gives the durations:

Hazard class Minimum duration
LH 30 min
OH 60 min
HHP 90 min
HHS 90 min

NOTE: town mains, inexhaustible sources and all pre-calculated systems have no separate duration figure; for them, the duration is already built into the requirements of the standard.

Worked example (using the 9.3.2.3 formula only): if the hydraulic calculation for an HHS facility gives Qmax = 1 750 l/min, the minimum effective volume required is 1 750 l/min × 90 min = 157 500 l = 157.5 m³. (The Qmax value is an example input; on a real project it comes from the hydraulic calculation.)

Refill rates

Clause 9.3.3 Refill rates for full capacity tanks (TS p.51 / EN p.48):

  • The water source must be able to refill the tank within 36 h at most.
  • Each feed pipe outlet must sit at least 2.0 m horizontally away from the suction pipe inlet.

Worked example: for a 200 m³ full capacity tank the average refill rate required is 200 / 36 ≈ 5.56 m³/h, that is about 93 l/min. (The tank volume is an example input.)

For comparison, the time is much shorter for pressure tanks. Clause 9.5.5 (TS p.58 / EN p.55) requires the pressure tank to be fully charged and pressurized by the air and water supplies in no more than 8 h, and requires the water supply to be able to make up at a rate of at least 6 m³/h at the gauge pressure of the tank.

Reduced capacity tanks

Clause 9.3.4 (TS p.51 / EN p.48) requires five conditions together:

  • a) The inflow must come from a town main, work automatically and pass through at least two mechanical float valves. It must not have an adverse effect on the pump set suction, and if one float valve fails, the required infill rate must still be achieved.
  • b) The tank's effective capacity must be at least the value given in Table 11.
  • c) Tank capacity and inflow together must be enough to supply the system at the full capacity required by 9.3.2.
  • d) There must be a means to check the inflow capacity.
  • e) The inflow arrangement must be accessible so that it can be inspected.

Table 11: Minimum effective capacity of reduced capacity tanks (TS p.52 / EN p.49)

Hazard class Minimum effective capacity (m³)
LH (wet or pre-action) 5
OH1 wet or pre-action 10
OH1 dry or alternate / OH2 wet or pre-action 20
OH2 dry or alternate / OH3 wet or pre-action 30
OH3 dry or alternate / OH4 wet or pre-action 50
HHP and HHS 70 (footnote a)

Footnote a: But in no case less than 10 % of the full capacity.

Reduced capacity tanks are governed by Clause 9.3.4; Clause 9.5.5 concerns charging a pressure tank with air and water and has nothing to do with reduced capacity tanks.

Effective capacity and suction chamber dimensions

Clause 9.3.5 (TS p.53 / EN p.50): the effective capacity of a storage tank must be calculated in the way Figure 4 shows. In that figure N marks the normal water level, X the low water level and d the nominal suction pipe diameter. Table 12 sets two minimum dimensions:

  • A: between the suction pipe and the low water level (Figure 4);
  • B: between the suction pipe and the sump bottom (Figure 4).

Further provisions (TS p.54 / EN p.51): where a vortex inhibitor of at least the Table 12 size is fitted, dimension A may be reduced to 0.10 m. A sump may also be provided to get the most effective capacity out of the tank.

Table 12: Suction pipe inlet clearances (TS p.54 / EN p.51)

Nominal diameter of suction pipe d (mm) A minimum without vortex inhibitor (m) A minimum with vortex inhibitor (m) Minimum dimension of vortex inhibitor (m) B minimum (m)
65 0.25 0.10 0.20 0.08
80 0.31 0.10 0.20 0.08
100 0.37 0.10 0.40 0.10
150 0.50 0.10 0.60 0.10
200 0.62 0.10 0.80 0.15
250 0.75 0.10 1.00 0.20
300 0.90 0.10 1.20 0.20
400 1.05 0.10 1.20 0.30
500 1.20 0.10 1.20 0.35

Worked example (using table values only): for a DN200 suction pipe, A = 0.62 m without a vortex inhibitor and A = 0.10 m with one. The 0.52 m difference corresponds to 0.52 × 100 = 52 m³ of effective capacity in a tank with a base area of 100 m². (The 100 m² base area is an example input.)

9.3.6: Strainers

Clause 9.3.6 (TS p.54 / EN p.51):

  • Where pump sets work under suction lift, a strainer must be fitted on the pump suction pipe upstream of the foot valve, positioned so that it can be cleaned without draining the tank.
  • Where an open tank feeds pumps under positive head, the strainer must go on the suction pipe outside the tank, and a stop valve must be fitted between the tank and the strainer.
  • Each strainer needs a cross-sectional area of at least 1.5 times the pipe's nominal area and must stop any object larger than 5 mm in diameter.

Maintenance periods

Storage tanks are covered in two separate periods:

  • Clause 20.3.5.2 (TS p.125 / EN p.122): except for tanks designed so as not to need maintenance within 10 years in accordance with 9.6.2 b), all tanks shall be inspected internally at intervals of no more than 3 years, drained and cleaned if necessary, examined for corrosion and, where necessary, repainted or the corrosion protection renewed.
  • Clause 20.3.6 (TS p.125 / EN p.122): at intervals of no more than 10 years, all storage tanks shall be cleaned, inspected internally and their shells dealt with as necessary. NOTE: cleaning tanks generally requires them to be drained, but alternative solutions might be acceptable in order to save water.

In addition, Clause 20.3.4.4 (TS p.125 / EN p.122) requires the float valves in water storage tanks to be checked in the yearly routine to make sure that they operate correctly, and Clause 20.3.4.5 requires the pump suction strainers and the settling chamber and its screens to be inspected and cleaned as necessary at least once a year. In the weekly routine, Clause 20.2.2.2 b) (TS p.122 / EN p.119) requires all water levels in elevated private reservoirs, rivers, canals, lakes and water storage tanks, including pump priming water tanks and pressure tanks, to be checked and recorded.

On the monitoring side, Annex H, H.2.4 (TS p.156 / EN p.153) requires an indication before the water storage level falls by more than 10 % of the nominal fill level.

What the standard does not specify

BS EN 12845+A2:2026 does not prescribe the material of the storage tank (galvanized panel steel, reinforced concrete, GRP and so on). What the standard does say about materials concerns water quality and corrosion protection rather than the tank shell itself: Clause 8.1.2 (TS p.45 / EN p.42) requires the water to be free from fibrous or other matter in suspension that could build up deposits in the system pipework, and requires salt or brackish water not to be retained in the sprinkler installation pipework; Clause 9.6.2 b) (TS p.59 / EN p.56) requires the tank, in order to count as a superior single water supply, to be painted or given other corrosion protection that extends the need for draining for maintenance to at least 10 years.

Field note

The vortex inhibitor column of Table 12 and the sump provision in Clause 9.3.5 serve the same purpose: reducing the difference between the physical volume of the tank and its effective capacity. What enters the calculation is not "how many m³ the tank holds" but "how many m³ lie between the normal level and the lowest effective level"; on projects that difference is lost not at the top of the tank but at the bottom. (This paragraph is engineering commentary.)

Frequently Asked Questions

How is the effective capacity of a tank calculated?

BS EN 12845+A2:2026 Clause 9.3.2.1 (TS p.50 / EN p.47): a tank's effective capacity must be calculated as the volume lying between its normal water level and its lowest effective water level. Where the tank is not frost proof, its normal water level must be raised by at least 1.0 m and ice venting is required. Enclosed tanks need easy access, and every tank other than an open reservoir needs a water level indicator that can be read from outside.

What is the minimum water volume for pre-calculated LH and OH systems?

Table 9 (TS p.50 / EN p.47) gives it according to the height of the highest sprinkler above the lowest sprinkler. Examples: LH (wet or pre-action) 9 m³ for h ≤ 15 m, 10 m³ for 15 < h ≤ 30 and 11 m³ for 30 < h ≤ 45. OH1 wet/pre-action: 55, 70, 80 m³. OH2 wet/pre-action (and OH1 dry/alternate): 105, 125, 140 m³. OH3 wet/pre-action (and OH2 dry/alternate): 135, 160, 185 m³. OH4 wet/pre-action (and OH3 dry/alternate): 160, 185, 200 m³. For OH4 dry or alternate, HH protection is used.

How quickly must a full capacity tank refill?

Clause 9.3.3 (TS p.51 / EN p.48): the water source must be able to refill the tank within 36 h at most. Each feed pipe outlet must also sit at least 2.0 m horizontally away from the suction pipe inlet.

What conditions apply to a reduced capacity tank?

Clause 9.3.4 (TS p.51 / EN p.48) sets five conditions, all mandatory: a) the inflow must come from a town main, work automatically through at least two mechanical float valves and not adversely affect the pump set suction, and a single failed float valve must not reduce the required infill rate; b) the tank's effective capacity must be at least the Table 11 value; c) tank capacity and inflow together must be able to supply the system at the full capacity required by 9.3.2; d) a means of checking the inflow capacity must exist; e) the inflow arrangement must be accessible for inspection.

What clearance is required between the suction pipe and the low water level?

Table 12 (TS p.54 / EN p.51) gives it by nominal suction pipe diameter. For DN100, for example: B minimum 0.10 m to the bottom of the sump; A minimum 0.37 m without a vortex inhibitor; A minimum 0.10 m with a vortex inhibitor (minimum dimension of the vortex inhibitor 0.40 m). For DN200 the values are 0.15 m, 0.62 m and 0.10 m respectively (vortex inhibitor 0.80 m). According to the standard, fitting a vortex inhibitor of at least the Table 12 minimum size allows dimension A to be reduced to 0.10 m.

References

  • BS EN 12845+A2:2026 Clause 9.3.1 General (TS p.49 / EN p.46)
  • BS EN 12845+A2:2026 Clauses 9.3.2.1, 9.3.2.2, Table 9 (TS p.50 / EN p.47)
  • BS EN 12845+A2:2026 Table 10, Clauses 9.3.2.3, 9.3.3, 9.3.4 (TS p.51 / EN p.48)
  • BS EN 12845+A2:2026 Table 11 and its footnote (TS p.52 / EN p.49)
  • BS EN 12845+A2:2026 Clause 9.3.5, Figure 4 (TS p.53 / EN p.50)
  • BS EN 12845+A2:2026 Table 12, the vortex inhibitor and sump provisions, Clause 9.3.6 Strainers (TS p.54 / EN p.51)
  • BS EN 12845+A2:2026 Clause 9.5.5 Charging a pressure tank with air and water (TS p.58 / EN p.55)
  • BS EN 12845+A2:2026 Clause 9.6.2 b) (TS p.59 / EN p.56)
  • BS EN 12845+A2:2026 Clause 8.1.1 Duration, 8.1.2 Continuity (TS p.45 / EN p.42)
  • BS EN 12845+A2:2026 Clause 20.2.2.2 b) (TS p.122 / EN p.119)
  • BS EN 12845+A2:2026 Clauses 20.3.4.4, 20.3.4.5 (TS p.125 / EN p.122)
  • BS EN 12845+A2:2026 Clauses 20.3.5.2, 20.3.6 (TS p.125 / EN p.122)
  • BS EN 12845+A2:2026 Annex H, H.2.4 Liquid levels (TS p.156 / EN p.153)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.