The circulation pump is the heart of any heating or chilled water system: when it stops, or runs incorrectly, the whole installation is affected. This guide works through the faults we meet most often in the field — from purely mechanical failures to performance and diagnostic problems such as flow/return ΔT and differential pressure (Δp). Each problem is followed immediately by its practical fix, so find the heading that matches your symptom.
The pump runs but nothing heats or cools (no circulation)
If the motor is turning but no temperature difference develops across the system, the most likely causes are air in the system or an impeller spinning free on the shaft. Start by venting through the automatic and manual air vents; on wet rotor pumps, loosen the central vent plug and let the rotor clear itself. If there is still no circulation, check that the isolation valves at the manifold are open, that the check valve is fitted the right way round, and that the strainer is not blocked. On a variable speed pump, the minimum speed or pressure setpoint may simply be set too low.
The pump is noisy or rumbling (cavitation)
A gravel-like rattle or a continuous rumble is usually cavitation: the pressure at the pump suction falls below the vapour pressure of the water, and the bubbles that form collapse violently in the impeller. The fix is to raise the system fill (static) pressure — check the expansion vessel pre-charge and the fill pressure, remembering that a closed system should retain positive pressure at its highest point. High water temperature increases the required NPSH, so clean the suction-side strainer and confirm the suction valve is fully open. If the pump is simply oversized and running at excessive flow, drop it to a lower speed setting.
The pump does not run at all (motor does not turn)
Confirm the supply first: fuse or contactor, terminal voltage and the thermal overload. On a pump that has stood idle for months, the rotor may be seized with scale and sludge, which is typical at the start of the season. On wet rotor pumps, open the centre plug and turn the shaft by hand with a screwdriver. A single-phase motor with a failed capacitor will hum but not turn, and needs a new capacitor. On an inverter-driven pump, read the fault code — dry-running or low-pressure protection may have locked the pump out.
The pump keeps starting and stopping (short cycling / hunting)
On a differential pressure controlled or pressure switch controlled system, a pump that cycles within seconds usually has too narrow a deadband, or an expansion vessel that has lost its cushion. Check the expansion vessel pre-charge pressure — a ruptured diaphragm produces exactly this symptom. Widen the start-stop differential in the controller. If thermostatic valves closing suddenly are causing pressure spikes, add a differential pressure bypass valve. Rapid cycling consumes motor and bearing life very quickly.
The pump is leaking
Where the leak comes from matters. If it is weeping from a flange or union face, renew the gasket and torque the bolts in a diagonal sequence. On a dry rotor pump, dripping between the shaft and the housing means the mechanical seal has worn; dry running and abrasive water accelerate this, and the seal kit must be replaced. Wet rotor pumps generally have no mechanical seal, so a leak points to the housing gasket or a cracked body. If the leak is running toward the terminal box, isolate the electrical supply immediately.
The pump overheats or the thermal overload trips
Excess current and heating come from a blocked impeller, bearing failure, incorrect voltage or phase, or excessive flow. Compare the actual current with the nameplate rating using a clamp meter. Dry running will burn the windings within seconds, so confirm the system is full and properly vented. On a variable speed pump, incorrect motor parameters will trip the protection early. Bearing noise or heavy vibration means the bearings need replacing; on wet rotor pumps the whole pump is normally changed.
Air in the system / air lock
Gurgling at the terminals, upper floors that will not heat or cool, and a pump that seems to spin without load are the classic signs of an air lock. Vent systematically from the highest points downward, and fill the system slowly — rapid filling traps air. Check that automatic air vents are not blocked. If air keeps returning, either the expansion vessel pressure is too low (so the system draws air in under vacuum) or there is a micro-leak somewhere. A microbubble deaerator provides the permanent fix.
Vibration and mechanical noise
Structural vibration comes from an unbalanced impeller, worn bearings, loose mounting or pipe stress. Mount the pump without imposing pipe strain, using flexible connectors and anti-vibration mounts. A rumble that rises with speed is usually cavitation, whereas a steady mechanical knock points to bearings or the impeller. On inline pumps the mounting orientation must match what the manufacturer permits — the wrong shaft axis kills bearings early.
Zones or terminals heat and cool unevenly
This is usually a balancing problem rather than a pump problem: the distant circuits are not receiving enough flow. Set the flow distribution using the balancing valves at the manifold, throttling the nearest circuits so flow reaches the far ones. In single-pipe systems the last terminals are inherently weaker. If the pump was undersized, its head will not reach the far circuit — compare the pump curve against the actual system resistance. On variable speed pumps, proportional pressure control usually performs better than constant pressure on unbalanced systems.
The pump is seized at the first start of the season
On wet rotor pumps that have stood for months, scale and sludge glue the rotor in place: the motor hums but will not turn. Open the large centre plug and free the shaft by turning it a few times with a flat screwdriver. To prevent recurrence, run the pump for a few minutes once a month out of season, or use a pump with an automatic anti-blocking function, which most modern units provide.
The pump is running backwards or installed incorrectly
On a three-phase dry rotor pump, swapping two phases reverses rotation: flow and head drop sharply and efficiency collapses, yet the pump still appears to be running. Check the flow direction arrow on the body, and if rotation is reversed, swap two phases. Single-phase wet rotor pumps have fixed rotation, so the problem there is a body installed against the flow arrow. Always install the pump in the direction of flow and in a shaft position the manufacturer permits.
High electricity consumption or poor pump efficiency
Old fixed-speed pumps run at full speed even when the system load falls, wasting energy continuously. The single biggest saving is moving to a high-efficiency variable speed circulator, which slows automatically at part load. Beyond that: if the pump is oversized, drop the speed setting; close unnecessary open bypass lines; and clean fouled strainers and heat exchangers, because a dirty system forces the pump to work permanently against high resistance.
Flow/return temperature difference much larger than design
An unusually high ΔT — for example reading 30 °C on a heating system designed for 15–20 °C — tells you the flow through the system is insufficient: to carry the same heat, as flow falls the temperature difference must rise. Typical causes are an undersized pump or one set too slow, a blocked strainer or heat exchanger, a valve throttled too far, air in the system, or reverse rotation. Clean the strainer, review valve positions, and raise the pump speed or Δp setpoint. If it persists, recompare the pump curve against the real system curve.
Flow/return temperature difference much smaller than design (low delta-T syndrome)
A low ΔT — only a few degrees on heating, or below about 3 °C on chilled water — generally means excessive flow, or water returning without having picked up any load. The classic causes are a bypass or shunt line left permanently open, a three-way mixing valve leaking or wrongly set, fouled or undersized terminal coils, and an oversized pump. On chiller plant in particular, low delta-T syndrome reduces efficiency and wastes pump energy. Throttle the bypass flow, consider converting three-way valves to two-way, clean the coils, and slow the pump to match the real load.
Pump differential pressure too low
If the pressure difference between flow and return is below expectation, the pump is not developing its head. Causes include an undersized pump, reverse rotation, a worn or eroded impeller, a bypass left fully open, internal recirculation past worn wear rings, or backflow through an idle pump in a twin-pump set. Check rotation and impeller condition, close open bypasses, move a fixed-speed pump to a higher setting, or raise the Δp setpoint on a variable speed unit. A badly worn impeller means renewing the impeller or the pump.
Pump differential pressure too high
Excessively high Δp indicates that the system is presenting too much resistance to flow — a closed or throttled valve, a blocked strainer, a fouled heat exchanger — or simply that the pump is oversized. High Δp causes noise, valve erosion and wasted energy. Check for closed isolation valves and clean the strainer. On a variable speed pump, reduce an unnecessarily high Δp setpoint and switch to proportional pressure mode. If Δp spikes when all thermostatic valves close, a differential pressure bypass valve is essential.
Flow higher than design (excessive flow)
Excessive flow results from an oversized pump or a system that was never balanced. The symptoms are low ΔT, flow noise in the pipework, erosion at valves and bends, and high electricity consumption. Set each circuit to its design flow using the balancing valves, reduce the pump speed setting, or bring the setpoint on a variable speed pump down to the real requirement. Design flow should be verified against the heat output and the intended temperature difference rather than assumed.
Flow insufficient (not reaching distant zones)
Insufficient flow comes from a pump whose head does not match the system resistance, undersized pipework, a blocked strainer or heat exchanger, or throttled valves. The ΔT at the most remote terminal grows, and heating or cooling response becomes slow. Clean the strainer, review valve openings, and compare the pump curve with the real system loss. If the pump is genuinely inadequate, a higher speed setting or a larger pump is required. Use the balancing valves to direct flow toward critical distant circuits.
Little or no differential pressure reading across the pump
On a running pump, a flow-to-return pressure difference close to zero is a serious sign: the pump may be running backwards, the impeller may be spinning free on the shaft (sheared key or failed weld), a full bypass may be open, or the pump may not actually be turning. Check rotation and the shaft-to-impeller connection first, then bypass and check valve positions. The gauges themselves may also be blocked or faulty — confirm with a calibrated test gauge.
Low delta-T syndrome on chiller plant
When evaporator ΔT falls below design (typically 5–7 °C), the chiller runs at low load but high flow, which reduces efficiency and can bring a second machine on line unnecessarily. Root causes are three-way valves, open bypass lines, fouled or undersized coils, oversized pumps and incorrect control. The fixes are moving to two-way valves with variable primary flow, minimising bypass, cleaning coils, and modulating the pump to the actual load.
Continuous flow through the bypass on a variable primary flow system
In variable primary flow systems the bypass should open only to maintain the chiller minimum flow when terminal valves close. If it flows continuously, the minimum flow bypass valve is wrongly set, the differential pressure sensor is in the wrong position (it should be at the most hydraulically remote terminal), or the pump control mode is incorrect. The result is low ΔT and wasted energy. Review the sensor location and the bypass setpoint, and control the pump from the Δp at the most remote zone.
Flow and pressure are correct but the space still will not heat or cool
If the hydraulic values — flow, Δp and ΔT — are all normal, the problem is not the pump but the source or the terminal. The boiler or chiller may not be reaching its target water temperature, the terminal capacity may be inadequate, or there may be an air-side problem such as a fan, grille or filter issue. Check the source flow temperature, the terminal capacity and the air flow rate. Increasing pump size is not the answer here; excessive flow would only lower ΔT and make matters worse.
Frequently Asked Questions
What does a very high flow/return temperature difference tell me?
A high delta-T means the flow rate through the system is too low. Since the heat carried is proportional to flow multiplied by temperature difference, when flow falls the temperature difference must rise to move the same heat. Look for a blocked strainer, a throttled valve, an undersized pump or one running too slowly, trapped air, or reverse rotation.
What causes low delta-T syndrome and why does it matter?
Low delta-T means water is returning without having given up its heat, usually because of excessive flow or short-circuiting. Common causes are an open bypass line, a leaking or wrongly set three-way mixing valve, fouled terminal coils and an oversized pump. On chiller plant it forces the machine to run at low load and high flow, which cuts efficiency and can bring a second chiller online unnecessarily.
How do I know if the pump is cavitating?
Cavitation sounds like gravel passing through the pump, or a continuous rumble that increases with speed. It happens when suction pressure falls below the vapour pressure of the water and vapour bubbles collapse in the impeller. Raise the system fill pressure, check the expansion vessel pre-charge, clean the suction strainer and confirm the suction valve is fully open.
Why is my pump short cycling?
Rapid start-stop cycling usually points to a deadband that is too narrow, or an expansion vessel that has lost its air cushion - a ruptured diaphragm produces this symptom classically. Check the vessel pre-charge, widen the start-stop differential, and if thermostatic valves are closing abruptly, fit a differential pressure bypass valve.
Should I use constant pressure or proportional pressure control?
Proportional pressure generally suits systems with distributed terminals and long index circuits, because the required head falls as flow falls, so the pump does not over-pressurise the near circuits at part load. Constant pressure suits systems with high fixed resistance close to the pump. On unbalanced installations, proportional pressure usually gives better distribution and lower energy use.
The pump appears to run but there is almost no pressure difference. What should I check?
This points to something more fundamental than a setting. Check rotation direction first, because a reversed three-phase pump still turns but produces very little head. Then check that the impeller is actually driven by the shaft, that no full bypass is open, and that the gauges themselves are not blocked. Confirm readings with a calibrated test gauge before drawing conclusions.
Why does the pump seize at the start of the heating season?
Wet rotor pumps that stand idle for months accumulate scale and sludge around the rotor, which glues it in place, so the motor hums but does not turn. Free the shaft by hand through the centre plug. To prevent it, run the pump briefly once a month out of season or specify a pump with an automatic anti-blocking function.
Will fitting a bigger pump fix poor heating performance?
Usually not, and it often makes things worse. If flow, differential pressure and delta-T are all within design, the limitation lies with the heat source or the terminal, not the pump. Increasing flow further only reduces delta-T, wastes pump energy and can trigger low delta-T syndrome on chilled water systems.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreThis guide collects general fault-finding notes based on field experience. Isolate the electrical supply before any intervention and always follow the manufacturer’s installation and service manual. Electrical work and work on pressurised systems must be carried out by suitably qualified personnel. For design background see ASHRAE Handbook — HVAC Systems and Equipment (hydronic systems and pumps) and EN 12828 for water-based heating system design.