An atrium (internal courtyard, lobby, shopping mall) traps smoke due to its large volume. Long evacuation times let smoke fall into sleeping areas. NFPA 92 (Smoke Control Systems) defines smoke reservoirs, exhaust flow, makeup air, pressurization and CFD simulation requirements.

Smoke Reservoir

Exhaust Flow Calculation

NFPA 92 Annex A:

Example: for a 5 MW fire (Q = 5000 kW), neglecting z0, z = 2.5 m gives m = 0.071 × 5000^(1/3) × 2.5^(5/3) ≈ 5.6 kg/s (about 17,000 m3/h). Flow grows with z^(5/3): keeping the smoke layer interface 15 m above the floor of a 25 m atrium requires m ≈ 111 kg/s, roughly 330,000 m3/h of exhaust (assuming ρ ≈ 1.2 kg/m3). At that scale the fan room and shafts must be coordinated with the architect at the earliest stage.

Makeup Air

Pressurization

CFD Validation

Atrium smoke with MEP Calc

MEP Calc runs NFPA 92 plume mass flow, exhaust fan sizing, makeup air and pressurization for atrium smoke control.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.