Short answer: NFPA 13 does not define a separate hazard class for self-storage; based on the OH2 definition in 4.3.3.2, these facilities are designed as at least Ordinary Hazard Group 2 (OH2). Because the contents are unknown, however, most engineers prefer to design to Extra Hazard Group 1 (EH1).

Standard: NFPA 13 (2025), NFPA 1, BYKHY
Hazard class: Ordinary Hazard Group 2 (OH2) and above
Reading time: 8 min


What Is Self-Storage and Why Is the Fire Risk Different?

Self-storage facilities consist of independent storage units that customers rent for their personal belongings. They differ from conventional storage facilities in three basic ways:

  1. The stored goods are unknown — The customer is not obliged to declare what is stored. One unit may hold a sofa set, another a set of tyres, another paint tins or an electric scooter. The fire load cannot be calculated in advance.
  2. 24/7 access — Customers can come at any hour to drop off or collect belongings. This means automatic door locks, motion sensors and uncontrolled people traffic.
  3. Corridor layout — Units open onto narrow corridors. Smoke exhaust and escape routes must be designed differently from standard storage facilities.

The self-storage market in Turkey has grown quickly over the last five years, and several operators have opened dozens of branches, mainly in Istanbul and Ankara. However, the Turkish Regulation on Fire Protection of Buildings (BYKHY) contains no specific section on self-storage. At the same time, under BYKHY Article 96/5 the sprinkler system design must follow TS EN 12845; the NFPA 13 values in this article are for comparison and good practice.


NFPA 13 Design Criteria

Hazard Class

NFPA 13 gives no separate hazard class for self-storage. The standard's OH2 definition (NFPA 13-2025, 4.3.3.2): occupancies where the quantity and combustibility of contents are moderate to high; stockpiles of contents with moderate heat release rates do not exceed 3.7 m (12 ft), and stockpiles with high heat release rates do not exceed 2.4 m (8 ft). Under this definition, units storing personal belongings are designed as at least Ordinary Hazard Group 2 (OH2). The design point for OH2 is a density of 8.1 mm/min (0.20 gpm/ft2) over a 140 m2 (1,500 ft2) design area (NFPA 13-2025 Table 19.2.3.1.1; the 2025 edition has no density/area curves and gives a single point for each hazard class).

Because the contents are unknown, however, most design engineers prefer to design to Extra Hazard Group 1 (EH1). Decision matrix:

Situation Recommended class Design density Area of operation
Customer declaration is mandatory (contract) OH2 8.1 mm/min (0.20 gpm/ft2) 140 m2 (1,500 ft2)
Customer can store anything (unrestricted) EH1 12.2 mm/min (0.30 gpm/ft2) 230 m2 (2,500 ft2)
High plastics content (past experience) EH2 16.3 mm/min (0.40 gpm/ft2) 230 m2 (2,500 ft2)

At Least One Sprinkler per Unit

Under the IBC (International Building Code), every storage unit must have at least one sprinkler; this rule applies regardless of wall height or construction type. NFPA 13 has no rule specific to self-storage units; layout follows the standard's general spacing rules.

Rule of thumb: in ordinary hazard, the protection area of a standard sprinkler is at most 12.1 m2 (130 ft2), the spacing between sprinklers at most 4.6 m (15 ft), and the distance to a wall cannot exceed half that spacing, i.e. 2.3 m (NFPA 13-2025 Table 10.2.4.2.1(b), 10.2.6.2.1). A unit larger than 12.1 m2, or with a side longer than 4.6 m, needs a second sprinkler.

Storage Height Limit

With standard pendent and upright sprinklers, at least 450 mm (18 in.) of clearance must remain between the deflector and the top of storage (NFPA 13-2025, 10.2.9.1); storage height in self-storage facilities is limited accordingly. In typical practice:

Many facilities cover the tops of units with an open-grid ceiling or wire mesh to stop customers stacking too high. This does not obstruct the sprinkler discharge pattern but physically limits the storage height.

Sprinkler Type Selection

Sprinkler type K-factor Recommendation Reason
Standard-response pendent K80 (K5.6) Minimum If OH2 is sufficient
Quick-response pendent K80 (K5.6) Recommended Fast response, water saving
ESFR K360 (K25.2) Open storage under high ceilings Storage above 4.5 m
Sidewall K80 (K5.6) Narrow units Wall mounting

Water Supply and Pump Sizing

Water Demand Calculation

Basic water demand for an OH2 design:

Q = Design density × Design area + Hose allowance

Q = 8.1 × 139 + 950 ≈ 1,126 + 950 ≈ 2,080 L/min

Hose allowance: per NFPA 13-2025 Table 19.2.3.1.2, a total of 250 gpm (≈ 950 L/min) for ordinary hazard; the inside hose allowance (0/50/100 gpm) is included in this total.

For an EH1 design:

Q = 12.2 × 232 + 1,900 ≈ 2,830 + 1,900 ≈ 4,730 L/min

Hose allowance: per the same table, a total of 500 gpm (≈ 1,900 L/min) for extra hazard.

Water Tank Capacity

Under BYKHY Article 92, the water tank capacity is calculated from the simultaneous water demand of the sprinkler system plus the hose cabinets plus the hydrants. Typical for self-storage:

Pump Selection

The pump is selected for the system demand from the hydraulic calculation:


Compartmentation and Passive Protection

Fire Compartments

Self-storage facilities follow one of two fire compartment strategies:

Approach 1: Full compartmentation

Approach 2: Sprinkler protection + compartmentation

Smoke Control

Because of the corridor layout, smoke control is critical:


Fire Alarm and Detection System

System Selection

An addressable fire alarm system is recommended for self-storage facilities. Putting a smoke detector in every unit is not practical (customers' belongings can obstruct it), but detectors should be provided in corridors and common areas.

Component Location Standard
Smoke detector Corridors and common areas NFPA 72
Heat detector Each unit entrance (optional) NFPA 72
Flow switch Each sprinkler zone NFPA 13
Manual call point At each exit door NFPA 72
Sounder with strobe Corridors and common areas NFPA 72

24/7 Access and Alarm Management

Customers in self-storage facilities have 24/7 access. This means the fire alarm system has to work in two modes:

  1. Working hours (building occupied): alarm → sounder + strobe + automatic notification to the fire brigade
  2. Out of hours (building empty): alarm → sounder + strobe + automatic notification to the fire brigade + notification to the security company

BYKHY Compliance

Although BYKHY contains no rules specific to self-storage, the following articles apply:

Most self-storage facilities in Turkey are assessed as "storage" for fire protection purposes and are subject to the BYKHY requirements for storage.


Example Projects in Turkey

Facilities of Multi-Branch Operators

The facilities of multi-branch self-storage operators in Istanbul and Ankara are usually set up by converting basements or industrial-type buildings. This creates extra difficulties for fire protection:

Compliance Difficulties

The biggest problems of self-storage facilities in Turkey:

  1. Regulatory gap — BYKHY does not recognise self-storage; whether it is "storage" or "workplace" is unclear
  2. Lack of insurance — Are customers' belongings insured? Who pays after a fire?
  3. Inspection — Periodic maintenance (NFPA 25) is generally not carried out
  4. Customer education — Even with a contract banning combustibles, enforcing it is difficult

Practical Design Checklist


References

  1. NFPA 13 — Standard for the Installation of Sprinkler Systems, 2025 Edition. National Fire Protection Association. https://www.nfpa.org/codes-and-standards/nfpa-13/standard-development/13

  2. NFPA 1 — Fire Code, 2024 Edition. National Fire Protection Association. https://www.nfpa.org/codes-and-standards/nfpa-1/standard-development/1

  3. NFPA 72 — National Fire Alarm and Signaling Code, 2025 Edition. National Fire Protection Association. https://www.nfpa.org/codes-and-standards/nfpa-72/standard-development/72

  4. NFPA 92 — Standard for Smoke Control Systems, 2024 Edition. National Fire Protection Association. https://www.nfpa.org/codes-and-standards/nfpa-92/standard-development/92

  5. International Code Council — International Building Code (IBC), Section 903 (Automatic Sprinkler Systems) and Section 422 (Self-Service Storage Facility). https://codes.iccsafe.org/s/IBC2024P1

  6. Turkish Regulation on Fire Protection of Buildings (Binaların Yangından Korunması Hakkında Yönetmelik, BYKHY) — Official Gazette 19/12/2007-26735. Amendments: OG 09/09/2009-27344; OG 05/04/2012-28255; OG 09/07/2015-29411; Council of Ministers Decision 2017/10459 of 14/06/2017 (in force 29/06/2017); Council of Ministers Decision 2018/11347 of 05/02/2018 (in force 15/03/2018); OG 04/11/2020-31294 (Presidential Decision 3167); OG 20/11/2021-31665 (Presidential Decision 4825); OG 01/07/2025-32943 (Presidential Decision 10026). Articles used: 24, 33, 85-88, 92, 94, 95, 96. https://www.mevzuat.gov.tr/MevzuatMetin/21.5.200712937.pdf

  7. Self Storage Association (SSA) — Industry Standards and Best Practices. https://www.selfstorage.org

  8. SFPE — Society of Fire Protection Engineers. Fire Protection Engineering Resources. https://www.sfpe.org

  9. FM Global — Property Loss Prevention Data Sheets. https://www.fmglobal.com/research-and-resources/fm-global-data-sheets


Frequently Asked Questions

What is the minimum sprinkler hazard class for self-storage facilities?

NFPA 13 does not define a separate hazard class for self-storage; based on the OH2 definition in 4.3.3.2, these facilities are designed as at least Ordinary Hazard Group 2 (OH2). Because the contents are unknown, however, most engineers prefer to design to Extra Hazard Group 1 (EH1).

Does every self-storage unit need a sprinkler?

Yes. Under the IBC, every storage unit must have at least one sprinkler; this rule applies regardless of wall height or construction type. Under the general spacing rules of NFPA 13, in ordinary hazard one sprinkler protects at most 12.1 m2 and can be at most 2.3 m from a wall; units exceeding these limits need a second sprinkler.

Does BYKHY contain specific rules for self-storage?

No. BYKHY does not contain a specific section for self-storage. Self-storage facilities in Turkey are usually assessed as storage and are subject to the BYKHY requirements for storage (Articles 24, 85-88, 94, 95, 96).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13, Standard for the Installation of Sprinkler Systems, 2025 edition (4.3.3.2, Tables 19.2.3.1.1 and 19.2.3.1.2, 10.2.4.2.1(b), 10.2.6.2.1, 10.2.9.1); Turkish Regulation on Fire Protection of Buildings (BYKHY), Articles 24, 33, 85-88, 92, 94, 95, 96. Other references are listed under References. General information only: the editions in force and the authority having jurisdiction govern, and design must be carried out by a qualified engineer.