If sprinkler pipe breaks during an earthquake, water damage — not fire — becomes the threat. Beyond structural damage, fire protection itself is lost. NFPA 13 Chapter 18 defines seismic design for sprinkler systems. Critical in Turkey's active seismic belt. An engineer's view of seismic protection below.
Earthquake and Sprinkler Systems
- Lateral ground motion can tear pipe from hangers
- Structure and pipe have different natural frequencies: the building moves, the pipe acts as an inert mass and separates at joints
- Secondary damage: racks, ceiling parts and boilers strike piping
- Risers: very large displacement forces; one bad detail drains the whole line
NFPA 13 Chapter 18 Requirements
NFPA 13 does not define seismic zones; Chapter 18 applies where systems are required to be protected against earthquake damage by the AHJ or building regulations (NFPA 13-2025, 18.1.1). In Turkey, BYKHY Article 96(6) sets this condition (see below). Main elements:
- Sway braces (18.5)
- Flexible couplings where piping must move with individual building sections (18.2)
- Seismic separation assemblies at building seismic joints (18.3)
- Riser clamps for vertical support
Sway Brace Design
Two bracing types:
- Lateral brace: Blocks side motion; required on all feed and cross mains regardless of size and on branch lines 2½ in (65 mm) and larger (18.5.5.1); spacing per Table 18.5.5.2, max 12 m (40 ft)
- Longitudinal brace: Blocks forward-back motion; on feed and cross mains at max 24 m (80 ft) (18.5.6.1)
- Load calculation: Fpw = Cp × Wp (18.5.9.3); Wp = 1.15 × weight of water-filled piping (18.5.9.2); Cp = 0.75 × SDS, or Cp = 0.5 where data are not available (18.5.9.5)
- The structural member the brace is anchored to is critical; do not choose anchor points without engineering
Flexible Coupling Use
Main locations per NFPA 13-2025 18.2.4.1:
- Within 24 in (600 mm) of the top and bottom of risers
- Within 12 in (300 mm) above and 24 in (600 mm) below floors in multistory buildings
- On both sides of concrete or masonry walls within 1 ft (300 mm), unless clearance per 18.4 is provided
- Within 24 in (600 mm) of building expansion joints
- Within 24 in (600 mm) of the top of drops over 15 ft (4.6 m) supplying more than one sprinkler
Piping of any size crossing building seismic separation joints requires a seismic separation assembly (18.3.1).
Turkey Seismic Zones
BYKHY's "first- and second-degree earthquake zones" come from the 2007 earthquake regulation. According to the BYKHY Guide, that regulation was repealed by the Turkish Building Earthquake Code of 18.03.2018 (TBDY 2018), which has no earthquake zones; the condition therefore applies to buildings in earthquake design classes (DTS) 1, 1a, 2 and 2a, which depend on the building use class.
- DTS 1, 1a, 2, 2a: seismic protection required under BYKHY 96(6); detailing per NFPA 13 Chapter 18
- Other design classes: scope of seismic protection depends on the AHJ and the design decision
Turkey's fire code (BYKHY Article 96(6)) does require seismic measures for sprinkler piping in first- and second-degree seismic zones: four-way bracing so risers cannot drift in any direction, flexible connections where pipes of 65 mm nominal diameter and larger connect floor branches to the main distribution pipes, two-way lateral and longitudinal restraint hangers where pipes are fixed to ceilings, and details that accommodate movement in all three directions at expansion joints. It gives no calculation method or spacing rules, so NFPA 13 Chapter 18 is used for the detailing; on site the provision is still often skipped.
Lesson from Feb 6, 2023
After the Kahramanmaraş earthquakes, sprinkler pipes broke in many malls, hospitals, and hotels. No fire, but water damage followed. Systems without seismic protection drained. This experience shows that the seismic bracing BYKHY Article 96(6) already requires must actually be designed, installed and checked on site.
Test and Acceptance
- Every sway brace: visual check and torque wrench verification
- Flexible coupling: manufacturer certificate and installation verification
- At acceptance: engineer signature and as-built documentation
- Annual inspection: seismic components checked under NFPA 25
Common Mistakes
- No sway bracing: Missing even in new Turkish projects.
- Wire ties instead of listed braces: Non-UL improvisation, the first element to fail.
- Flexible coupling missing: Guaranteed break at expansion joint.
- Too few riser clamps: Vertical pipe sways and joints fatigue.
Conclusion
Earthquake and fire together are one of Turkey's heaviest risk combinations. Sprinkler designs without seismic protection fail when they are needed. BYKHY Article 96(6) already requires seismic restraint; NFPA 13 Chapter 18 paired with TBDY 2018 is how that general requirement should be detailed. The engineer must close this gap at the design stage.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreCore references: NFPA 13 Chapter 18, NFPA 25-2026 Chapter 5 (5.2.3), TBDY 2018, ASCE 7, BYKHY Article 96(6). Original NFPA post: NFPA Today - Seismic Bracing.