If sprinkler pipe breaks during an earthquake, water damage — not fire — becomes the threat. Beyond structural damage, fire protection itself is lost. NFPA 13 Chapter 18 defines seismic design for sprinkler systems. Critical in Turkey's active seismic belt. An engineer's view of seismic protection below.

Earthquake and Sprinkler Systems

NFPA 13 Chapter 18 Requirements

NFPA 13 does not define seismic zones; Chapter 18 applies where systems are required to be protected against earthquake damage by the AHJ or building regulations (NFPA 13-2025, 18.1.1). In Turkey, BYKHY Article 96(6) sets this condition (see below). Main elements:

Sway Brace Design

Two bracing types:

Flexible Coupling Use

Main locations per NFPA 13-2025 18.2.4.1:

Piping of any size crossing building seismic separation joints requires a seismic separation assembly (18.3.1).

Turkey Seismic Zones

BYKHY's "first- and second-degree earthquake zones" come from the 2007 earthquake regulation. According to the BYKHY Guide, that regulation was repealed by the Turkish Building Earthquake Code of 18.03.2018 (TBDY 2018), which has no earthquake zones; the condition therefore applies to buildings in earthquake design classes (DTS) 1, 1a, 2 and 2a, which depend on the building use class.

Turkey's fire code (BYKHY Article 96(6)) does require seismic measures for sprinkler piping in first- and second-degree seismic zones: four-way bracing so risers cannot drift in any direction, flexible connections where pipes of 65 mm nominal diameter and larger connect floor branches to the main distribution pipes, two-way lateral and longitudinal restraint hangers where pipes are fixed to ceilings, and details that accommodate movement in all three directions at expansion joints. It gives no calculation method or spacing rules, so NFPA 13 Chapter 18 is used for the detailing; on site the provision is still often skipped.

Lesson from Feb 6, 2023

After the Kahramanmaraş earthquakes, sprinkler pipes broke in many malls, hospitals, and hotels. No fire, but water damage followed. Systems without seismic protection drained. This experience shows that the seismic bracing BYKHY Article 96(6) already requires must actually be designed, installed and checked on site.

Test and Acceptance

Common Mistakes

  1. No sway bracing: Missing even in new Turkish projects.
  2. Wire ties instead of listed braces: Non-UL improvisation, the first element to fail.
  3. Flexible coupling missing: Guaranteed break at expansion joint.
  4. Too few riser clamps: Vertical pipe sways and joints fatigue.

Conclusion

Earthquake and fire together are one of Turkey's heaviest risk combinations. Sprinkler designs without seismic protection fail when they are needed. BYKHY Article 96(6) already requires seismic restraint; NFPA 13 Chapter 18 paired with TBDY 2018 is how that general requirement should be detailed. The engineer must close this gap at the design stage.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

Core references: NFPA 13 Chapter 18, NFPA 25-2026 Chapter 5 (5.2.3), TBDY 2018, ASCE 7, BYKHY Article 96(6). Original NFPA post: NFPA Today - Seismic Bracing.