Vinyl chloride monomer (VCM, CH2=CHCl) is a flammable carcinogenic gas/liquid used in PVC manufacture. LEL 3.6%, UEL 33%, flash point −78 °C. Closed tank leaks quickly form explosive atmospheres. ATEX 2014/34/EU and NFPA 30 require explosion-protected design for VCM tanks, transfer pumps and piping.

VCM Properties

ATEX Zone Classification

Explosion Pressure

VCM maximum explosion pressure: Pmax = 8.8 bar (1 atm initial).

Deflagration index Kst: 50 bar·m/s (St1 class).

NFPA 68 venting equation: Av = (Kst × V0.75) / (Pred × 1000). For a 100 m³ volume with Pred = 0.5 bar, Av = 50 × 31.6 / 500 ≈ 3.2 m² of vent panel — two 1.6 m² panels are a practical choice.

Fire Protection

ATEX ventilation with MEP Calc

MEP Calc supports air-change sizing, ESD flow, explosion pressure and vent area calculations for VCM storage.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.