This article in the NFPA 25 series covers Chapter 9: water storage tanks dedicated to fire protection. The fire pump and sprinkler system articles dealt with the side that uses the water; this one covers the structure that holds it: water level, heating system and water temperature, the tank exterior and its surroundings, interior inspection and the tests made during it, level indicators and alarm tests, maintenance, automatic tank fill valves and what to do when a component changes. Check valves, control valves and gauges on the tank are sent to Chapter 13; they are covered in the valves and common components article. Every line carries its clause or table number from NFPA 25-2026.
In short: The water level is inspected quarterly in tanks with supervised water-level alarms and monthly in tanks without them; the tank is kept full or at the designed water level (9.2.1, 9.4.2). Water temperature is not allowed below 40 °F (4 °C) (9.2.3.1); a heating system without a supervised low-temperature alarm is inspected daily during the heating season (9.2.2.2). The tank exterior, support structure, foundation, vents, ladders and surrounding area are inspected quarterly; expansion joints, hoops and grillage and coated surfaces annually (9.2.4). The interior is inspected every 3 years in steel tanks without corrosion protection and every 5 years in all other tanks (9.2.5.1). Level indicators are tested every 5 years and high and low water level signals annually (9.3.1, 9.3.5). The automatic fill valve is tested yearly and its refill rate recorded (9.5.3).
A. Scope and general rules
Chapter 9 gives the minimum requirements for routine inspection, testing and maintenance of water storage tanks dedicated to fire protection use and installed to NFPA 22 or another approved installation standard (9.1.1.1). Minimum frequencies come from Table 9.1.1.2 (9.1.1.2).
| Check | Criterion | Clause |
|---|---|---|
| ☐ Common components and valves | Inspected, tested and maintained per Chapter 13 | 9.1.2 |
| ☐ Obstruction investigation needed | Follow the procedures of Chapter 14 | 9.1.3 |
| ☐ Impairment to protection | Follow the impairment procedures of Chapter 15 | 9.1.4 |
B. Frequency summary: Table 9.1.1.2
The standard’s summary table is reproduced below. Rows marked "—" have no frequency of their own in the table; the frequency and method come from the reference in the right-hand column. Frequencies marked with an asterisk (*) apply to the cold weather / heating season only (footnote to Table 9.1.1.2).
| Item | Frequency | Reference |
|---|---|---|
| Inspection | ||
| Catwalks and ladders | Quarterly | 9.2.4.1 |
| Check valves | — | Chapter 13 |
| Control valves | — | Chapter 13 |
| Expansion joints | Annually | 9.2.4.3 |
| Foundation | Quarterly | 9.2.4.1 |
| Heating system — tanks with supervised low-temperature alarms connected to constantly attended location | Quarterly | 9.2.2.1 |
| Heating system — tanks without supervised low-temperature alarms connected to constantly attended location | Daily* | 9.2.2.2 |
| Hoops and grillage | Annually | 9.2.4.4 |
| Interior — all other tanks | 5 years | 9.2.5.1.2 |
| Interior — steel tanks without corrosion protection | 3 years | 9.2.5.1.1 |
| Painted, coated, or insulated surfaces | Annually | 9.2.4.5 |
| Support structure | Quarterly | 9.2.4.1 |
| Surrounding area | Quarterly | 9.2.4.2 |
| Tank — exterior | Quarterly | 9.2.4.1 |
| Temperature alarms — connected to constantly attended location | Quarterly* | 9.2.3.2 |
| Temperature alarms — not connected to constantly attended location | Weekly* | 9.2.3.3 |
| Vents | Quarterly | 9.2.4.1 |
| Water level — tanks equipped with supervised water-level alarms connected to constantly attended location | Quarterly | 9.2.1.1 |
| Water level — tanks without supervised water-level alarms connected to constantly attended location | Monthly | 9.2.1.2 |
| Test | ||
| High-temperature limit switches | Prior to heating season | 9.3.4 |
| Level indicators | 5 years | 9.3.1 |
| Low-water-temperature alarms | Prior to heating season | 9.3.3 |
| Pressure gauges | — | Chapter 13 |
| Tank heating system | Prior to heating season | 9.3.2 |
| Valve status test | — | Chapter 13 |
| Water-level signals (high and low) | Annually | 9.3.5 |
| Maintenance | ||
| Check valves | — | Chapter 13 |
| Control valves | — | Chapter 13 |
| Embankment-supported coated fabric (ESCF) | 2 years or per manufacturer | 9.4.6.2 |
| Water level | — | 9.4.2 |
The same table as a calendar
Because site work is planned by frequency, the items of Table 9.1.1.2 and Table 9.5.1.1 are regrouped below by frequency. Which line applies to your tank depends on whether its alarms are connected to a constantly attended location.
| Frequency | Task | Clause |
|---|---|---|
| ☐ Daily (heating season) | Heating system inspection on a tank without a supervised low-temperature alarm | 9.2.2.2 |
| ☐ Daily/weekly (cold weather) | Inspection of the automatic fill valve enclosure | Table 9.5.1.1 |
| ☐ Weekly (heating season, mean temperature below 40 °F) | Water temperature inspected and recorded on a tank without low-temperature alarms | 9.2.3.3 |
| ☐ Monthly | Water level on a tank without supervised level alarms; exterior inspection of the automatic fill valve; fill valves secured with locks or electrically supervised | 9.2.1.2, Table 9.5.1.1, 9.5.1.2 |
| ☐ Quarterly | Water level on a tank with supervised level alarms; tank exterior, support structure, foundation, vents, catwalks and ladders; surrounding area; cleaning of fill valve strainers | 9.2.1.1, 9.2.4.1, 9.2.4.2, 9.5.2.3 |
| ☐ Quarterly (heating season) | Heating system on a tank with supervised low-temperature alarms; water temperature record when the mean temperature is below 40 °F | 9.2.2.1, 9.2.3.2 |
| ☐ Prior to heating season | Test of the tank heating system, low-water-temperature signals and high-water-temperature limit switches | 9.3.2, 9.3.3, 9.3.4 |
| ☐ Annually | Expansion joints; hoops and grillage of wooden tanks; painted, coated or insulated surfaces; test of high and low water level signals; automatic fill valve test | 9.2.4.3, 9.2.4.4, 9.2.4.5, 9.3.5, 9.5.3 |
| ☐ Annually/5 years | Interior inspection of the automatic fill valve | Table 9.5.1.1 |
| ☐ 2 years or per manufacturer | Cleaning and painting of exposed ESCF tank surfaces | 9.4.6.2 |
| ☐ 3 years | Interior inspection of steel tanks without corrosion protection | 9.2.5.1.1 |
| ☐ 5 years | Interior inspection of all other tanks; level indicator test; inspection of fill valve strainers, filters and orifices | 9.2.5.1.2, 9.3.1, Table 9.5.1.1 |
C. Water level
| Check | Criterion | Clause |
|---|---|---|
| ☐ Tank with water level alarms supervised per NFPA 72 | Water level inspected quarterly | 9.2.1.1 |
| ☐ Tank without supervised water level alarms connected to a constantly attended location | Water level inspected monthly | 9.2.1.2 |
| ☐ Where a level indicator is provided | Water level inspection verified through the level indicator | 9.2.1.3.1 |
| ☐ Water in the tank | At full or at the designed water level | 9.2.1.3.2 |
| ☐ Maintenance | Tank maintained full or at the designed water level | 9.4.2 |
The explanatory material of Annex A.9.2.1.1 recommends more frequent inspection where extreme conditions such as freezing temperatures or an arid climate can increase the probability of adversely affecting the stored water; since the level alarm reports level rather than water condition, the condition of the water can be checked during the same inspection. Per Annex A.9.2.1.3.2, the designed water level should be based on the fire protection system with the largest stored water volume requirement (demand and duration) and is often used as the set point of the tank fill valve. These are explanatory notes, not mandatory requirements.
D. Heating system and water temperature
| Check | Criterion | Clause |
|---|---|---|
| ☐ Heating system on a tank with low-water-temperature alarms supervised per NFPA 72 and connected to a constantly attended location | Inspected quarterly during the heating season | 9.2.2.1 |
| ☐ Heating system without a supervised low-temperature alarm connected to a constantly attended location | Inspected daily during the heating season | 9.2.2.2 |
| ☐ Temperature of water in the tank | Not less than 40 °F (4 °C) | 9.2.3.1 |
| ☐ Water temperature, tank with low-temperature alarms supervised per NFPA 72 and connected to a constantly attended location | Inspected and recorded quarterly during the heating season when the mean temperature is below 40 °F (4 °C) | 9.2.3.2 |
| ☐ Water temperature, tank without low-temperature alarms connected to a constantly attended location | Inspected and recorded weekly during the heating season when the mean temperature is below 40 °F (4 °C) | 9.2.3.3 |
E. Exterior inspection: tank, support structure and surroundings
| Check | Criterion | Clause |
|---|---|---|
| ☐ Tank exterior, supporting structure, vents, foundation, and catwalks or ladders where provided | Quarterly: no signs of obvious damage or weakening | 9.2.4.1 |
| ☐ Surrounding area: combustibles | Free of combustible storage, trash, debris, brush or material that could present a fire exposure hazard | 9.2.4.2(1) |
| ☐ Surrounding area: accumulation | Free of material accumulating on or near parts that could result in accelerated corrosion or rot | 9.2.4.2(2) |
| ☐ Tank and support | Free of ice buildup | 9.2.4.2(3) |
| ☐ Exterior sides and top of embankments supporting coated fabric tanks | Free of erosion | 9.2.4.2(4) |
| ☐ Expansion joints (where provided) | Annually: no leaks or cracks | 9.2.4.3 |
| ☐ Hoops and grillage of wooden tanks | Inspected annually | 9.2.4.4 |
| ☐ Exterior painted, coated or insulated surfaces of the tank and supporting structure (where provided) | Annually: no signs of degradation | 9.2.4.5 |
The surrounding area is also inspected quarterly (9.2.4.2). The explanatory material of Annex A.9.2.4.1 refers lightning protection systems, where provided, to NFPA 780 for inspection, testing and maintenance.
F. Interior inspection
| Check | Criterion | Clause |
|---|---|---|
| ☐ Steel tanks without corrosion protection | Interior inspected every 3 years | 9.2.5.1.1 |
| ☐ All other types of tanks | Interior inspected every 5 years | 9.2.5.1.2 |
| ☐ Interior inspection by underwater evaluation | Silt is first removed from the tank floor | 9.2.5.2 |
| ☐ Tank interior | Inspected for pitting, corrosion, spalling, rot and other deterioration; waste materials and debris; aquatic growth; and local or general failure of interior coating | 9.2.5.3 |
| ☐ Steel tank showing interior pitting, corrosion or coating failure | Tested per 9.2.6 | 9.2.5.4 |
| ☐ Tanks on ring-type foundations with sand in the middle | Inspected for evidence of voids beneath the floor | 9.2.5.5 |
| ☐ Heating system and components including piping | Inspected | 9.2.5.6 |
| ☐ Anti-vortex plate | Inspected for deterioration or blockage | 9.2.5.7 |
Annex A notes: to aid evaluation, the owner may stencil the last known date of an interior paint job on the tank exterior, typically near a manway at eye level (Annex A.9.2.5.1.1); if written verification of interior corrosion protection per NFPA 22 cannot be provided, the interior should be inspected every 3 years (Annex A.9.2.5.1.2); voids can be found by looking for dents in the floor and by walking on it to find buckling (Annex A.9.2.5.5).
G. Tests during interior inspection of steel tanks
Where a drained interior inspection of a steel tank is required by 9.2.5.4, the following tests are conducted (9.2.6):
| Check | Criterion | Clause |
|---|---|---|
| ☐ Coating adhesion | Evaluated with the adhesion test of ASTM D3359, generally referred to as the “cross-hatch test” | 9.2.6(1) |
| ☐ Dry film thickness | Measured at random locations to determine overall coating thickness | 9.2.6(2) |
| ☐ Wall thickness | Nondestructive ultrasonic readings where there is evidence of pitting or corrosion | 9.2.6(3) |
| ☐ Pinholes, cracks or other coating compromises | Spot wet-sponge test of interior surfaces, with special attention to sharp edges such as ladder rungs, nuts and bolts | 9.2.6(4) |
| ☐ Metal loss and rust on the tank bottom underside | Ultrasonic testing where there is evidence of pitting or corrosion; removal, visual inspection and replacement of random floor coupons is an acceptable alternative | 9.2.6(5) |
| ☐ Flat-bottom tanks | Vacuum-box test at bottom seams using the procedures in NFPA 22 | 9.2.6(6) |
H. Testing: level indicators, heating and alarms
| Check | Criterion | Clause |
|---|---|---|
| ☐ Level indicators | Every 5 years: tested for accuracy and freedom of movement | 9.3.1 |
| ☐ Tank heating system (where provided) | Tested toward the beginning of the heating season, before freezing conditions, to ensure proper working order | 9.3.2 |
| ☐ Low-water-temperature signals (where provided) | Tested toward the beginning of the heating season, before freezing conditions | 9.3.3 |
| ☐ High-water-temperature limit switches on tank heating systems (where provided) | Tested toward the beginning of the heating season, before freezing conditions | 9.3.4 |
| ☐ High and low water level signals | Tested annually | 9.3.5 |
| ☐ Pressure gauges and valve status test | Per Chapter 13 | Table 9.1.1.2 |
The explanatory material of Annex A.9.3.1 gives a step-by-step procedure and a figure for the 5-year accuracy test of listed mercury gauges. Per Annex A.9.3.4 (to which A.9.3.5 also refers), the manufacturer’s instructions should be consulted for testing; where the actual initiating device cannot be tested, only the circuitry should be tested.
I. Maintenance
| Check | Criterion | Clause |
|---|---|---|
| ☐ Voids discovered beneath tank floors | Filled by pumping in grout or by accessing the sand and replenishing | 9.4.1 |
| ☐ Water level | Tank maintained full or at the designed water level | 9.4.2 |
| ☐ Roof hatch covers and the door at the top of the frostproof casing | Always kept securely fastened with substantial catches against freezing and windstorm damage | 9.4.3 |
| ☐ Waste materials | No boards, paint cans, trim or loose material left in the tank or on its surface | 9.4.4 |
| ☐ Silt | Removed during interior inspections, or more often as needed to avoid accumulation to the level of the tank outlet | 9.4.5 |
| ☐ Embankment-supported coated fabric (ESCF) suction tanks | Maintained per this section and the tank manufacturer’s instructions | 9.4.6.1 |
| ☐ Exposed surfaces of ESCF tanks | Cleaned and painted every 2 years or per the manufacturer’s instructions | 9.4.6.2 |
| ☐ Check valves and control valves | Maintained per Chapter 13 | Table 9.1.1.2 |
J. Automatic tank fill valves
Automatic tank fill valves are inspected per Table 9.5.1.1 (9.5.1.1):
| Item | Frequency | Reference |
|---|---|---|
| Inspection | ||
| Enclosure (during cold weather) | Daily/weekly | Chapter 4 |
| Exterior | Monthly | Chapter 13 |
| Interior | Annually/5 years | Chapter 13 |
| Strainers, filters, orifices (inspect) | 5 years | Chapter 13 |
| Test | ||
| Automatic tank fill valve | Annually | 9.5.3 |
| Maintenance | ||
| Strainers (clean) | Quarterly | 9.5.2.3 |
| Check | Criterion | Clause |
|---|---|---|
| ☐ OS&Y isolation valves that are part of the automatic fill valve | Inspected per Chapter 13 | 9.5.1.1.1 |
| ☐ Valves secured with locks or electrically supervised per applicable NFPA standards | Inspected monthly | 9.5.1.2 |
| ☐ Enclosure | Verified to be heated and secured | 9.5.1.3 |
| ☐ Maintenance of all automatic tank fill valves | By qualified personnel following the manufacturer’s instructions and the procedures and policies of the AHJ | 9.5.2.1 |
| ☐ Rubber parts | Replaced at the frequency required by the AHJ and the manufacturer’s instructions | 9.5.2.2 |
| ☐ Strainers | Cleaned quarterly | 9.5.2.3 |
| ☐ Annual test: actuation | Valve actuated automatically by lowering the water level in the tank | 9.5.3(1) |
| ☐ Annual test: refill rate | Refill rate measured and recorded | 9.5.3(2) |
K. When a component is adjusted, repaired or replaced: Table 9.6.1
Whenever a component in a water storage tank is adjusted, repaired, reconditioned or replaced, the action in Table 9.6.1 is performed (9.6.1). Where the original installation standard differs from the cited one, the appropriate installing standard may be used (9.6.2). These actions do not require a design review, which is outside the scope of the standard (9.6.3). In the table, "X" means the rule applies to that action and "—" marks an empty cell.
| Component | Adjust | Repair/recondition | Replace | Test criteria |
|---|---|---|---|---|
| Tank components | ||||
| Catwalks and ladders | X | X | X | Verify integrity in conformance with NFPA 22 |
| Expansion joints | X | X | X | Verify integrity in conformance with NFPA 22 |
| Heating system | X | X | X | Verify heating system is in conformance with NFPA 22 |
| Hoops and grillage | X | X | X | Verify integrity in conformance with NFPA 22 |
| Insulation | — | X | X | Verify integrity in conformance with NFPA 22 |
| Overflow piping | X | X | X | Verify integrity in conformance with NFPA 22 |
| Support structure | — | X | X | Verify integrity in conformance with NFPA 22 |
| Tank exterior | — | X | X | Verify integrity in conformance with NFPA 22 |
| Tank interior | — | X | X | Remove debris; verify integrity in conformance with NFPA 22 |
| Alarm and supervisory components | ||||
| Enclosure temperature | X | X | X | Operational test for conformance with NFPA 22 and/or NFPA 72 |
| High and low water level | X | X | X | Operational test for conformance with NFPA 22 and/or NFPA 72 and the design water levels |
| Valve supervision | X | X | X | Operational test for conformance with NFPA 22 and/or NFPA 72 |
| Water temperature | X | X | X | Operational test for conformance with NFPA 22 and/or NFPA 72 |
| Fill and discharge components | ||||
| Automatic fill valves | X | X | — | Perform annual test in accordance with 9.5.3 |
| Valves | X | X | X | See Chapter 13 |
| Status indicators | ||||
| Level indicators | X | X | X | Verify conformance with NFPA 22 |
| Pressure gauges | — | — | X | Verify at 0 psi (0 bar) and at system working pressure |
Frequently Asked Questions
How often is the water level of a fire protection tank inspected under NFPA 25?
Quarterly in tanks with water level alarms supervised per NFPA 72, and monthly in tanks without supervised alarms connected to a constantly attended location (9.2.1.1, 9.2.1.2). Where a level indicator is provided, the inspection is verified through it, and the tank must be full or at the designed water level (9.2.1.3).
How often is the tank interior inspected?
Every 3 years for steel tanks without corrosion protection and every 5 years for all other tanks (9.2.5.1.1, 9.2.5.1.2). For an underwater evaluation, silt is removed from the floor first (9.2.5.2). A steel tank showing pitting, corrosion or coating failure gets the coating, thickness, sponge, bottom and vacuum-box tests of 9.2.6 (9.2.5.4).
What is the minimum water temperature in the tank?
Not less than 40 °F (4 °C) (9.2.3.1). During the heating season, when the mean temperature is below 40 °F, the water temperature is inspected and recorded quarterly in tanks with supervised low-temperature alarms and weekly in tanks without them (9.2.3.2, 9.2.3.3).
When is the tank heating system tested?
Toward the beginning of the heating season, before freezing conditions set in (9.3.2). Low-water-temperature signals and high-water-temperature limit switches are tested at the same time (9.3.3, 9.3.4). The heating system is also inspected daily during the heating season without a supervised alarm, or quarterly with one (9.2.2).
How is an automatic tank fill valve tested?
Yearly: the valve is actuated automatically by lowering the water level in the tank, and the refill rate is measured and recorded (9.5.3). Its strainers are cleaned quarterly, and during cold weather the enclosure is verified to be heated and secured (9.5.2.3, 9.5.1.3, Table 9.5.1.1).

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreNFPA 25-2026, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems: Chapter 9 (9.1–9.6), Table 9.1.1.2, Table 9.5.1.1 and Table 9.6.1; explanatory material of Annex A.9.2.1.1, A.9.2.1.3.2, A.9.2.4.1, A.9.2.5.1.1, A.9.2.5.1.2, A.9.2.5.5, A.9.3.1 and A.9.3.4. The content of Chapters 4, 13, 14 and 15 and of NFPA 22, NFPA 72 and NFPA 780 referenced by Chapter 9 is not reproduced here.