This article gives dozens of worked ESFR and CMSA solutions organised by ceiling height — 7.6 m, 9.1–10.7 m, 12.2 m and above 12.2 m — for both non-storage process (FH) and storage (HHS1–HHS5) occupancies, based on the actual design tables of EN 12845-2:2024 (Tables 7 to 21). Every row states the K-factor, the number of operating sprinklers, the minimum operating pressure and the source table. Values are for information; the full text of the standard governs any actual design.

The critical distinction — the prohibition is not about storage, it is about non-storage process areas: ESFR and CMSA were developed for high hazard storage (HHS), and every table in this article exists to protect a warehouse. The prohibition applies only to non-storage high hazard process occupancies (FH3, FH4, FH5). Reference: EN 12845-2:2024 Clause 6.2, titled "Protection of non-storage occupancies with ESFR and CMSA""ESFR and CMSA protection shall not be applied for FH3 to FH5 occupancies." Class conversion is given in Table A.1 (Annex A): LH→FH1, OH1/OH2→FH2, OH3/OH4→FH3, HHP1/HHP2→FH4, HHP3→FH5. Detail: ESFR and CMSA Prohibitions.

General Rules (Applying to All Tables)

1. Non-Storage Process (FH) — CMDA Required

In FH3 to FH5 ESFR and CMSA are prohibited; only CMDA (density and area, EN 12845-1) may be used. Where ESFR or CMSA is used in FH1 or FH2, it is designed on an HHS1–HHS3 basis (the storage tables below) regardless of the actual commodity category. Process CMDA criteria:

Class (→FH)DensityOperating area, wet (m²)Operating area, dry (m²)ConceptReference
LH (→FH1)2.25 mm/min84 (wet)CMDA — conventional sprayEN 12845-1
OH1 (→FH2)5.0 mm/min72 (wet)90 (dry)CMDAEN 12845-1
OH2 (→FH2)5.0 mm/min144180CMDAEN 12845-1
OH3 (→FH3)5.0 mm/min216270CMDA (ESFR/CMSA PROHIBITED)EN 12845-1 · EN 12845-2 Cl.6.2
OH4 (→FH3)5.0 mm/min360no dry system (escalate to HHP1)CMDA (ESFR/CMSA PROHIBITED)EN 12845-1 · Cl.6.2
HHP1 (→FH4)7.5 mm/min260325CMDA (ESFR/CMSA PROHIBITED)EN 12845-1 · Cl.6.2
HHP2 (→FH4)10.0 mm/min260325CMDA (ESFR/CMSA PROHIBITED)EN 12845-1 · Cl.6.2
HHP3 (→FH5)12.5 mm/min260325CMDA (ESFR/CMSA PROHIBITED)EN 12845-1 · Cl.6.2
HHP4Delugeproject specificOpen nozzle / special engineeringEN 12845-1

2. Storage (HHS) — Ceiling Around 7.6 m (Storage Around 6.1 m)

ESFR options

CommodityConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
HHS1–3ESFR ceiling-onlyK200 pendent123.4Table 7
HHS1–3ESFR ceiling-onlyK240 pendent122.4Table 7
HHS1–3ESFR ceiling-onlyK320 pendent121.7Table 7
HHS1–3ESFR ceiling-onlyK360 pendent121.0Table 7
HHS1–3ESFR ceiling-onlyK200 upright123.4Table 7
HHS1–3ESFR ceiling-onlyK240 upright122.4Table 7
HHS1–3ESFR special (fewer sprinklers)K200 pendent92.4Table 10
HHS1–3ESFR specialK240 pendent91.7Table 10
HHS1–3ESFR specialK320 pendent91.4Table 10
HHS1–3ESFR specialK360 pendent91.4Table 10
HHS4ESFR ceiling-onlyK200 pendent123.4Table 7
HHS4ESFR ceiling-onlyK240 pendent122.4Table 7
HHS4ESFR ceiling-onlyK320 pendent125.2Table 7
HHS4ESFR ceiling-onlyK360 pendent124.1Table 7
HHS4ESFR specialK320 pendent101.7Table 10
HHS4ESFR specialK360 pendent101.4Table 10
HHS5ESFR specialK200 pendent125.2Table 10
HHS5ESFR specialK360 pendent91.7Table 10

CMSA alternatives

CommodityConceptK-factor & orientationSystemSprinklersMin. pressure (bar)Reference
HHS3CMSA block (STC1)K240 uprightWet151.5Table 16
HHS3CMSA block (STC1)K280 pendentWet151.1Table 16
HHS3CMSA block (STC1)K360 pendentWet150.7Table 16
HHS4CMSA (5.5/7.9 m)K160 uprightWet153.4Table 16
HHS4CMSA (6.1/9.1 m)K240 uprightWet151.5Table 16
HHS5CMSA (5.5/7.9 m)K160 uprightWet153.4Table 16
HHS5CMSA (5.5/7.9 m)K240 uprightWet151.5Table 16
HHS≤4 (STC1/2)CMSA dry — specialK160 uprightDry (60 s)203.5Table 21

3. Storage (HHS) — Ceiling Around 9.1 to 10.7 m

ESFR options

CommodityConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
HHS1–3 (9.1 m)ESFR ceiling-onlyK200 pendent123.4Table 7
HHS1–3 (9.1 m)ESFR ceiling-onlyK360 pendent121.0Table 7
HHS1–3 (9.1 m)ESFR specialK200 pendent123.5Table 10
HHS1–3 (9.1 m)ESFR specialK320 pendent91.4Table 10
HHS1–3 (10.7 m)ESFR ceiling-onlyK200 pendent125.2Table 7
HHS1–3 (10.7 m)ESFR ceiling-onlyK240 pendent123.6Table 7
HHS1–3 (10.7 m)ESFR ceiling-onlyK320 pendent122.4Table 7
HHS1–3 (10.7 m)ESFR ceiling-onlyK360 pendent121.4Table 7
HHS1–3 (10.7 m)ESFR specialK320 pendent122.0Table 10
HHS1–3 (10.7 m)ESFR specialK360 pendent121.6Table 10
HHS4 (9.1 m)ESFR ceiling-onlyK320 pendent125.2Table 7
HHS4 (9.1 m)ESFR specialK320 pendent103.5Table 10
HHS5 (9.1 m)ESFR ceiling-onlyK360 pendent122.0Table 7
HHS5 (9.1 m)ESFR specialK360 pendent122.8Table 10

CMSA alternatives (STC1 block and STC4 rack)

CommodityConceptK-factor & orientationSystemSprinklersMin. pressure (bar)Reference
HHS1/2 (7.6/9.1)CMSA block (STC1)K280 pendentWet151.1Table 15
HHS1/2 (7.6/9.1)CMSA block (STC1)K360 pendentWet150.7Table 15
HHS1/2 (7.6/9.1)CMSA block (STC1)K360 uprightWet121.4Table 15
HHS1/2 (7.6/10.7)CMSA blockK160 uprightWet151.7Table 15
HHS1/2 (7.6/10.7)CMSA blockK160 uprightDry251.7Table 15
HHS1/2 (7.6/10.7)CMSA blockK240 uprightWet151.0Table 15
HHS1/2 (9.1/10.7)CMSA blockK280 pendentWet151.7Table 15
HHS1/2 rack (6.1/9.1)CMSA rack (STC4)K280 pendentWet151.1Table 17
HHS1/2 rack (6.1/9.1)CMSA rack (STC4)K360 pendentWet150.7Table 17
HHS3 (7.6/9.1)CMSA rack (STC4)K280 pendentWet151.1Table 19
HHS3 (7.6/9.1)CMSA rack (STC4)K360 pendentWet150.7Table 19

4. Storage (HHS) — Ceiling Around 12.2 m

ESFR options

CommodityConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
HHS1–3ESFR ceiling-onlyK240 pendent123.6Table 7
HHS1–3ESFR ceiling-onlyK320 pendent122.8Table 7
HHS1–3ESFR ceiling-onlyK360 pendent121.7Table 7
HHS1–3ESFR specialK200 pendent125.2Table 10
HHS1–3ESFR specialK240 pendent123.6Table 10
HHS1–3ESFR specialK320 pendent93.5Table 10
HHS1–3ESFR specialK360 pendent92.8Table 10
HHS4ESFR ceiling-onlyK320 pendent125.2Table 7
HHS4ESFR ceiling-onlyK360 pendent124.1Table 7
HHS4ESFR specialK360 pendent124.1Table 10
HHS5ESFR ceiling-onlyK360 pendent124.1Table 7
HHS5ESFR specialK360 pendent205.2Table 10

CMSA alternatives

CommodityConceptK-factor & orientationSystemSprinklersMin. pressure (bar)Reference
HHS1/2 (7.6/12.2)CMSA block (STC1)K360 pendentWet151.6Table 15
HHS1/2 (10.7/12.2)CMSA block (STC1)K280 pendentWet152.1Table 15
HHS1/2 (10.7/12.2)CMSA block (STC1)K360 pendentWet151.6Table 15
HHS1/2 (10.7/12.2)CMSA blockK360 uprightDry (25 s)241.0Table 15
HHS1/2 rack (10.7/12.2)CMSA rack (STC4)K280 pendentWet152.1Table 18
HHS1/2 rack (10.7/12.2)CMSA rack (STC4)K360 pendentWet151.6Table 18
HHS1/2 rack (10.7/12.2)CMSA rack (STC4)K360 uprightDry (25 s)241.0Table 18
HHS3 (10.7/12.2)CMSA rack (STC4)K360 pendentWet151.6Table 19
HHS1/2 (10.7/12.2)CMSA dry — specialK360 uprightDry (20 s)123.5Table 21
HHS1/2 (10.7/12.2)CMSA dry — specialK160 uprightDry (30 s)363.8Table 21

5. Storage (HHS) — Above 12.2 m (13.7, 15.2 and 16.8 m)

At these heights only pendent ESFR (K400/K480) and dry CMSA (K480) remain available; aisle width and deflector clearance become the critical constraints.

Class & ceilingConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
HHS1–3 (13.7 m)ESFR ceiling-onlyK320 pendent122.8Table 7
HHS1–3 (13.7 m)ESFR ceiling-onlyK360 pendent122.8Table 7
HHS1–3 (15.2 m)ESFR ceiling-onlyK400 pendent (aisle 1.8 m)122.8Table 7
HHS1–3 (15.2 m)ESFR ceiling-onlyK480 pendent (aisle 1.8 m)123.8Table 7
HHS1–3 (16.8 m)ESFR ceiling-onlyK400 pendent (aisle 2.4 m)125.5Table 7
HHS1–3 (16.8 m)ESFR ceiling-onlyK480 pendent (aisle 1.8 m)123.8Table 7
HHS1–3 (15.2 m)ESFR special (325 mm)K320 pendent104.3Table 11
HHS1–3 (15.2 m)ESFR special (325 mm)K360 pendent103.5Table 11
HHS1–3 (15.2 m)ESFR special (425 mm)K480 pendent93.8Table 11
HHS1–3 (16.8 m)ESFR special (325 mm / 2.4 m aisle)K400 pendent95.5Table 11
HHS1/2 (12.2/13.7)CMSA dry — specialK360 veya K480 upright12 (dry, 20 s)3.5Table 21
HHS1/2 (13.7/15.2)CMSA dry — specialK480 upright (aisle 2.4 m)15 (dry, 20 s)3.5Table 21
HHS1/2 (15.2/16.8)CMSA dry — specialK480 upright (aisle 2.4 m)16 (dry, 20 s)3.5Table 21
HHS1/2 rack (13.7/15.2)CMSA rack (STC4)K480 upright (aisle 2.4 m)15 (dry, 20 s)3.4Table 18
HHS1/2 rack (15.2/16.7)CMSA rack (STC4)K480 upright (aisle 2.4 m)16 (dry, 20 s)3.4Table 18

6. Special Commodities: Rubber Tyres and Roll Paper

CommodityConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
Rubber tyres (STC3/4, ≤7.6 m stack, 9.1 m ceiling)ESFRK320 pendent121.7Table 8
Rubber tyres (≤7.6 m, 10.7 m ceiling)ESFRK360 pendent121.7Table 8
Rubber tyres (≤7.6 m, 12.2 m ceiling)ESFRK360 pendent122.8Table 8
Roll paper, heavy/medium (7.6/9.1 m)ESFRK360 pendent121.0Table 9
Roll paper, heavy (9.1/10.7 m)ESFRK360 pendent121.7Table 9
Roll paper, heavy (9.1/13.7 m)ESFRK320/K360 pendent123.4Table 9
Light roll paper (7.6/9.1 m)ESFRK200 pendent163.4Table 9
Light roll paper (7.6, 12.2 m)ESFRK200 pendent255.2Table 9

7. Combined Ceiling and In-Rack Design

Where the ceiling-only limit is exceeded, in-rack sprinklers are added. The in-rack hydraulic calculation is based on the 8 most remote heads at a minimum of 230 L/min, and the water supply duration is at least 60 minutes (Cl. 6.6.2). The ceiling side:

CommodityConceptK-factor & orientationSprinklersMin. pressure (bar)Reference
HHS3 ceilingESFR ceiling + in-rackK200 pendent125.2Table 12
HHS3 ceilingESFR ceiling + in-rackK240 pendent123.6Table 12
HHS3 ceilingESFR ceiling + in-rackK320 pendent122.8Table 12
HHS4 ceilingESFR ceiling + in-rackK360 pendent124.1Table 12
📌 Reference clauses at a glance: Cl. 6.2 (FH3–FH5 prohibition, non-storage) · Cl. 6.5 (unheated buildings and dry pendent ESFR) · Cl. 6.6.1 and Table 7 (ESFR ceiling-only) · Table 8 (rubber tyres) · Table 9 (roll paper) · Tables 10–11 (special ESFR, fewer sprinklers) · Cl. 6.6.2 and Table 12 (ceiling plus in-rack) · Cl. 6.7 and Tables 15–19 (CMSA block and rack) · Table 21 (special dry CMSA) · Table A.1 (class conversion).

Frequently Asked Questions

Are ESFR sprinklers prohibited in high hazard storage under EN 12845-2?

No - the opposite is true. ESFR and CMSA were developed for high hazard storage (HHS1 to HHS5) and EN 12845-2 protects those classes with them. The prohibition in Clause 6.2 applies to non-storage high hazard process occupancies (FH3, FH4, FH5). The clause is even titled Protection of non-storage occupancies. You protect the warehouse with ESFR or CMSA; you cannot protect the production area with them, where CMDA or deluge is required.

What ESFR options are available for HHS1-HHS3 at a 7.6 m ceiling?

From the Table 7 ceiling-only design with 12 sprinklers: K200 at 3.4 bar, K240 at 2.4 bar, K320 at 1.7 bar or K360 at 1.0 bar pendent; upright K200 at 3.4 bar or K240 at 2.4 bar. Using the special-condition route in Table 10 the count can drop to 9 sprinklers: K200 at 2.4 bar, K240 at 1.7 bar, K320 at 1.4 bar, K360 at 1.4 bar. Fewer sprinklers means a smaller pump and a smaller tank.

Which designs apply at a 12.2 m ceiling?

For HHS1-HHS3, ESFR ceiling-only gives K240 at 12 sprinklers and 3.6 bar, K320 at 12 and 2.8 bar, or K360 at 12 and 1.7 bar (Table 7). The special-condition route gives K320 at 9 and 3.5 bar or K360 at 9 and 2.8 bar (Table 10). On the CMSA side, wet K360 pendent at 15 sprinklers and 1.6 bar, or dry K360 upright at 24 sprinklers and 1.0 bar with 25 second water delivery (Tables 15 and 18). For HHS4 and HHS5 the pressures increase.

How are very tall warehouses above 12.2 m protected?

With ESFR ceiling-only: at 13.7 m, K320 or K360 at 12 sprinklers and 2.8 bar; at 15.2 m, K400 at 12 and 2.8 bar or K480 at 12 and 3.8 bar with a minimum 1.8 m aisle; at 16.8 m, K400 at 12 and 5.5 bar with a 2.4 m aisle, or K480 at 12 and 3.8 bar (Table 7). Alternatives are the Table 11 special design reducing to 9 or 10 sprinklers, or dry CMSA systems from Tables 18 and 21 using K480 upright at 15 to 16 sprinklers and 3.4 to 3.5 bar with 20 second water delivery.

ESFR is wet only and CMSA can be wet or dry - how do I choose?

ESFR may only be used on a wet pipe system, since even a dry pendent ESFR is served from a wet system. If the warehouse is unheated and freezing is a risk so a dry system is genuinely required, you move to CMSA. On dry CMSA the water delivery time and the increased operating sprinkler count both come into play, and the heads must be 141 degrees C nominal on terminal tree pipework, with gridded and looped arrangements prohibited under Clause 6.7.2.

What are the water supply duration and roof slope limits?

For ESFR and CMSA the water supply duration is generally at least 90 minutes; it can reduce to 60 minutes for combined ceiling and in-rack designs, and certain special dry CMSA designs require 120 minutes (Table 21). The maximum roof or ceiling slope is 10 degrees; beyond that you need a flat suspended ceiling, an in-rack combination, or a move to CMDA. Interpolation and extrapolation within the tables are also prohibited.

When are in-rack sprinklers required?

When the ceiling-only design exceeds its commodity or height limit. For example, up to 13.7 m in open-frame racks with commodities up to HHS4, a K200 or larger pendent ceiling ESFR is supplemented by a single level of wet in-rack sprinklers in the longitudinal flue. The in-rack hydraulic calculation uses the 8 most remote heads at a minimum of 230 L/min, and the water supply duration is at least 60 minutes (Clause 6.6.2 and Table 12).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845-2:2024 (EN 12845-2:2024) — Clauses 6.2, 6.5, 6.6 and 6.7; Tables 7, 8, 9, 10, 11, 12, 15, 16, 17, 18, 19 and 21; Annex A Table A.1. TS EN 12845:2015+A2:2026 and EN 12845-1 (CMDA density and area). Values are given for information; the full text and current edition of the standard govern any actual design.