One of the most significant provisions of EN 12845-2:2024 is quiet but critical: ESFR and CMSA sprinklers may not be used in non-storage occupancies of hazard classes FH3, FH4 and FH5. In other words, you cannot rely on these technologies in manufacturing and process areas of those classes. This article explains the FH classification, the likely technical reasoning behind the prohibition, and the strict conditions that apply in FH1 and FH2.
1. Groundwork: ESFR, CMSA and CMDA
- ESFR (Early Suppression Fast Response): fast-response ceiling sprinklers to EN 12259-13. In high-risk storage, particularly plastics, they suppress the heat release rate of the fire very rapidly.
- CMSA (Control Mode Specific Application): sprinklers to prEN 12259-15. They operate in control mode, limiting fire growth, with final extinguishment completed by other means.
- CMDA (Control Mode Density/Area): conventional sprinklers to EN 12259-1. An approach based on a minimum density in mm/min over a design area, used according to the Introduction in residential, commercial, industrial and storage applications.
2. The New FH (Fire Hazard) Classification
The FH classes are set out in Annex A of EN 12845-2:2024. Annex A extracts the classification from the draft prEN 12845-1: Figure A.1 was taken from it and updated, while Table A.1, which converts the EN 12845:2015 classes to FH classes, was created for this document. The current EN 12845:2015 (including A1 and A2) still uses the LH/OH/HHP classes. The conversion is given in Table A.1 (example occupancies from EN 12845 Annex A, Tables A.1–A.3):
| Former class (EN 12845:2015) | New class (FH) | Scope |
|---|---|---|
| LH (Light Hazard), OH 1 | FH 1 | LH: certain areas of schools and offices, prisons. OH1: hospitals, hotels, restaurants, libraries, computer rooms, cement works. |
| OH 2, OH 3 | FH 2 | OH2: laboratories, laundries, car parks, museums, abattoirs, bakeries, metal working. OH3: glass factories, electronics factories, paper factories, department stores and shopping centres, woodworking. |
| OH 4, HHP 1 | FH 3 | OH4: cinemas and theatres, concert halls, exhibition halls, waste paper processing. HHP1: cable factories, plastics injection moulding, printing works, rubber goods, paint application shops with solvent. |
| HHP 2 | FH 4 | Paint, colour and varnish manufacture, paper machine halls, chipboard manufacturing, bus and lorry depots, candle wax and paraffin manufacture. |
| HHP 3 | FH 5 | Cellulose nitrate manufacture, rubber tyres for cars and lorries, foam plastics and foam rubber manufacture. |
HHP4 of EN 12845 (firework manufacture) does not appear in Table A.1.
3. The ESFR/CMSA Prohibition in FH3, FH4 and FH5 (Clause 6.2)
Clause 6.2 of EN 12845-2:2024 categorically prohibits the ESFR and CMSA concepts in FH3–FH5 (non-storage) occupancies. The standard does not state its reasons; the following is an engineering interpretation:
- Storage-specific technology: The standard's Introduction describes ESFR and CMSA as approaches developed for storage fires.
- Obstruction risk: machinery, large pipework, cable trays, ductwork and platforms in a process area seriously obstruct the discharge pattern. ESFR and CMSA are very sensitive to obstruction, so the likelihood that the system fails to suppress or control the fire is high.
4. Permitted in FH1 and FH2 — but on HHS1–HHS3 Criteria
Outside storage, ESFR and CMSA may only be used in FH1 and FH2. Even then Clause 6.2 imposes a deliberate margin: irrespective of the actual fire load and storage category in the space, the design must follow the high hazard storage criteria for HHS1–HHS3 (clause 6.6 or 6.7). The standard gives no reason. In practice this means, for example, a Table 7 design with at least 12 sprinklers operating at the end pressures required for the chosen K-factor, together with all ESFR/CMSA installation requirements: spacing, obstructions and roof slope.
5. Comparative Summary: ESFR vs CMSA vs CMDA
| Criterion | ESFR | CMSA | CMDA |
|---|---|---|---|
| Operating mode | Suppression — rapidly suppresses the heat release rate. | Control — limits the rate of heat release. | Conventional control — density and area design. |
| Permitted classes (FH) | FH1–FH2 only. Prohibited in FH3, FH4, FH5. | FH1–FH2 only. Prohibited in FH3, FH4, FH5. | Permitted across FH1–FH5. |
| Process limitations | Very sensitive to obstruction and air movement; high risk of failure. | Affected by obstruction; a dry system option exists. | Falls under EN 12845-1; used across a wide variety of built environments. |
| Design approach | K-factor, end pressure, mostly 12 sprinklers (9 to 20 in Tables 10–11). | K-factor, minimum end pressure, defined operating count (12 to 36). | Design area multiplied by density. |
Frequently Asked Questions
In which hazard classes are ESFR and CMSA prohibited under EN 12845-2?
Under Clause 6.2 of EN 12845-2:2024, ESFR and CMSA protection concepts may not be applied in FH3, FH4 or FH5 occupancies. The standard gives no reason; the Introduction describes ESFR and CMSA as approaches developed for storage fires. The density/area (CMDA) design of EN 12845 is used instead.
Is ESFR prohibited in high hazard storage?
No, this is a misreading of the clause. ESFR and CMSA were developed specifically for high hazard storage, and EN 12845-2 protects storage classes HHS1 to HHS5 with them. The prohibition applies to non-storage process occupancies, which is why the official title of Clause 6.2 is Protection of non-storage occupancies with ESFR and CMSA.
How do the new FH classes map onto the former EN 12845 classes?
Under EN 12845-2 Table A.1, LH and OH1 become FH1, OH2 and OH3 become FH2, OH4 and HHP1 become FH3, HHP2 becomes FH4, and HHP3 becomes FH5. Figure A.1 was taken from the draft prEN 12845-1 and Table A.1 was created for this document.
Why do ESFR and CMSA fail in process areas?
The standard gives no reason, but the Introduction points to two things. First, ESFR and CMSA were developed for storage fires. Second, machinery, pipework, cable trays and ductwork obstruct the discharge pattern, and the Introduction notes that these designs have a low tolerance of non conformities.
If ESFR or CMSA is used in FH1 or FH2, how is it designed?
It is permitted, but Clause 6.2 imposes a strict margin: regardless of the actual fire load and storage category, the design must follow the high hazard storage criteria for HHS1 to HHS3 (clause 6.6 or 6.7). In practice that means, for example, at least 12 sprinklers operating together at the end pressures required for the selected K-factor under Table 7, plus all ESFR/CMSA installation requirements: spacing, obstructions and roof slope.
What sprinkler approach should be used in FH3 to FH5 areas?
For medium and high hazard industrial processes, use the conventional CMDA density and area design of EN 12845. CMDA may be used across all classes from FH1 to FH5.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845-2:2025 (EN 12845-2:2024), Fixed Firefighting Systems — Automatic Sprinkler Systems — Part 2: Design and Installation of ESFR and CMSA Sprinklers (Clause 6.2, Clauses 6.6 and 6.7, Annex A Table A.1). BS EN 12845:2015+A2:2026, Design, Installation and Maintenance. Values are for information; the full text of the current standard governs any actual design.