Under NFPA 13-2025 Table 19.2.3.1.1 the design density for Extra Hazard Group 1 (EH1) is 12.2 mm/min over 230 m² (0.30 gpm/ft² over 2,500 ft²); next to unsprinklered combustible concealed spaces 11.4 mm/min over 280 m² (0.28 gpm/ft² over 3,000 ft²) applies. Hose allowance is 1,900 L/min (500 gpm) and water supply duration is 90 or 120 minutes (Table 19.2.3.1.2).

Definition

Extra Hazard Group 1 applies where the quantity and combustibility of contents are very high and dust, lint or fibres can produce a rapidly developing fire, but flammable or combustible liquids are absent or present only in small amounts. Fires develop quickly and reach a high heat release rate.

Design parameters

ParameterSIUS units
Density (standard design)12.2 mm/min0.30 gpm/ft²
Design area (standard)230 m²2,500 ft²
Density (concealed space rule, 19.2.3.1.5)11.4 mm/min0.28 gpm/ft²
Design area (concealed space rule)280 m²3,000 ft²
Theoretical sprinkler flow (standard / concealed space)2,806 / 3,192 L/min750 / 840 gpm
Hose allowance (inside + outside)1,900 L/min500 gpm
Inside hose (part of the total)0, 190 or 380 L/min0, 50 or 100 gpm
Water supply duration90 or 120 min90 or 120 min
Maximum area per sprinkler (standard spray, Table 10.2.4.2.1(c))9 m²100 ft²
Maximum distance between sprinklers3.7 m12 ft

Theoretical flow is simply density × area. Actual system demand is higher because of hydraulic imbalance and the minimum sprinkler pressure (7 psi (0.5 bar), 28.2.4.11.1). Coverage and spacing values are for standard spray sprinklers; this applies to hydraulically calculated systems with densities of 0.25 gpm/ft² or more; pipe schedule systems are limited to 90 ft².

Typical occupancies

  • Aircraft hangars (those not covered by a dedicated hangar standard)
  • Areas using combustible hydraulic fluids
  • Die casting and metal extrusion
  • Plywood and particleboard manufacturing
  • Rubber reclaiming, compounding, drying and vulcanising
  • Sawmills
  • Textile opening, blending and carding
  • Printing with inks having flash points below 100 °F (38 °C)
  • Upholstering with plastic foams

How the design area is set

NFPA 13-2025 no longer has the density/area curve of earlier editions. Table 19.2.3.1.1 gives a single design point for each class: 12.2 mm/min over 230 m² for EH1. The second column, 11.4 mm/min over 280 m², applies only to the systems or portions of systems adjacent to unsprinklered combustible concealed spaces (19.2.3.1.5); the concealed spaces listed in 19.2.3.1.5.2 are exempt. Where an area of operation smaller than 230 m² is used, the density for 230 m² still applies (19.2.3.1.4). The density must be delivered over the whole hydraulically most remote area.

For dry pipe and double interlock pre-action systems the area of operation is increased by 30% without revising the density (19.2.3.2.6). Ceilings sloping more than 2 in 12 usually need a 30% increase as well (19.2.3.2.4). Where several adjustments apply they are compounded on the area first taken from Table 19.2.3.1.1, and the concealed space rule is applied last (19.2.3.2.8).

In extra hazard areas with ceilings up to 30 ft (9.1 m), the area of operation may be reduced by 25% without revising the density where high-temperature sprinklers or sprinklers of K-11.2 (K160) or larger are used; the area may not drop below 2000 ft² (185 m²) and the reduction may be applied only once (19.2.3.2.7). Quick-response sprinklers are not permitted in extra hazard (19.2.3.2.2.2), so there is no quick-response reduction either. Above 30 ft (9.1 m) a minimum density of 0.45 gpm/ft² (18.3 mm/min) applies (19.2.3.2.5.2(D)).

The inside hose allowance (0, 50 or 100 gpm) is part of the total above. The lower duration value is accepted where the waterflow alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3).

Comparison with EN 12845

The nearest EN 12845 classes are HHP1 (7.5 mm/min) or HHP2 (10.0 mm/min), both with a 260 m² area of operation for wet or pre-action systems (325 m² for dry or alternate) and 90 minutes. The NFPA EH1 value in Table 19.2.3.1.1 is 12.2 mm/min over 230 m², a higher density than the EN values.

The class comes from how the space is actually used. A project title or the occupancy on a permit is not enough; contents, stack height and flammable liquids are checked on site and the class is recorded with a written justification. For a quick first pass, use the NFPA 13 hazard classification tool.

Checklist

  1. Is the activity and type of contents recorded in writing?
  2. Are stack heights within the class definition; if not, have storage criteria been checked?
  3. Is the system type (wet/dry/pre-action) reflected in the area adjustment?
  4. Are hose allowance and duration included in the tank volume?
  5. Are areas of different classes in the same building calculated separately?

Frequently Asked Questions

What is the minimum water demand for NFPA 13 EH1?

In theory, at the standard design point 2,806 L/min (750 gpm) of sprinkler flow plus 1,900 L/min (500 gpm) of hose allowance, multiplied by 90 or 120 minutes. The real figure comes from the hydraulic calculation and is usually higher; the fire water tank sizing calculator helps with the volume.

Is an aircraft hangar always EH1?

No. Most hangars fall under a dedicated hangar standard (NFPA 409); EH1 is listed only as an example for hangars outside that standard's scope.

Why is sprinkler spacing limited to 12 ft in EH1?

Table 10.2.4.2.1(c) limits coverage to 100 ft² (9 m²) and spacing to 12 ft (3.7 m) for hydraulically calculated extra hazard systems with a density of 0.25 gpm/ft² (10.2 mm/min) or more. At high heat release, closer sprinklers help the first heads to open control the fire while it is still small.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13, Standard for the Installation of Sprinkler Systems (2025 edition): 4.3, Table 10.2.4.2.1, 19.2.3, A.4.3 · EN 12845:2015+A2:2026. Values are for information; the binding text is the edition in force and the decision of the authority having jurisdiction.