Under NFPA 13-2025 Table 19.2.3.1.1 the design density for Extra Hazard Group 2 (EH2) is 16.3 mm/min over 230 m² (0.40 gpm/ft² over 2,500 ft²); next to unsprinklered combustible concealed spaces 15.5 mm/min over 280 m² (0.38 gpm/ft² over 3,000 ft²) applies. Hose allowance is 1,900 L/min (500 gpm) and water supply duration is 90 or 120 minutes (Table 19.2.3.1.2).

Definition

Extra Hazard Group 2 covers spaces with moderate to substantial amounts of flammable or combustible liquids, or where combustibles are extensively shielded from sprinkler discharge. The speed of a liquid fire and the difficulty of getting water onto the burning surface call for the highest density among NFPA 13's general hazard classes.

Design parameters

ParameterSIUS units
Density (standard design)16.3 mm/min0.40 gpm/ft²
Design area (standard)230 m²2,500 ft²
Density (concealed space rule, 19.2.3.1.5)15.5 mm/min0.38 gpm/ft²
Design area (concealed space rule)280 m²3,000 ft²
Theoretical sprinkler flow (standard / concealed space)3,749 / 4,340 L/min1,000 / 1,140 gpm
Hose allowance (inside + outside)1,900 L/min500 gpm
Inside hose (part of the total)0, 190 or 380 L/min0, 50 or 100 gpm
Water supply duration90 or 120 min90 or 120 min
Maximum area per sprinkler (standard spray, Table 10.2.4.2.1(c))9 m²100 ft²
Maximum distance between sprinklers3.7 m12 ft

Theoretical flow is simply density × area. Actual system demand is higher because of hydraulic imbalance and the minimum sprinkler pressure (7 psi (0.5 bar), 28.2.4.11.1). Coverage and spacing values are for standard spray sprinklers; this applies to hydraulically calculated systems with densities of 0.25 gpm/ft² or more; pipe schedule systems are limited to 90 ft².

Typical occupancies

  • Flammable liquid spraying (spray booths and similar)
  • Flow coating
  • Varnish and paint dipping
  • Solvent cleaning
  • Open oil quenching
  • Asphalt saturating
  • Plastics manufacturing
  • Assembly of modular or manufactured buildings with combustible interiors
  • Car stackers and car lift systems with two cars stacked vertically and ceiling-only protection
  • Diesel fire pump houses and rooms containing pump drivers and fuel tanks

How the design area is set

NFPA 13-2025 no longer has the density/area curve of earlier editions. Table 19.2.3.1.1 gives a single design point for each class: 16.3 mm/min over 230 m² for EH2. The second column, 15.5 mm/min over 280 m², applies only to the systems or portions of systems adjacent to unsprinklered combustible concealed spaces (19.2.3.1.5); the concealed spaces listed in 19.2.3.1.5.2 are exempt. Where an area of operation smaller than 230 m² is used, the density for 230 m² still applies (19.2.3.1.4). The density must be delivered over the whole hydraulically most remote area.

For dry pipe and double interlock pre-action systems the area of operation is increased by 30% without revising the density (19.2.3.2.6). Ceilings sloping more than 2 in 12 usually need a 30% increase as well (19.2.3.2.4). Where several adjustments apply they are compounded on the area first taken from Table 19.2.3.1.1, and the concealed space rule is applied last (19.2.3.2.8).

In extra hazard areas with ceilings up to 30 ft (9.1 m), the area of operation may be reduced by 25% without revising the density where high-temperature sprinklers or sprinklers of K-11.2 (K160) or larger are used; the area may not drop below 2000 ft² (185 m²) and the reduction may be applied only once (19.2.3.2.7). Quick-response sprinklers are not permitted in extra hazard (19.2.3.2.2.2), so there is no quick-response reduction either. Above 30 ft (9.1 m) a minimum density of 0.45 gpm/ft² (18.3 mm/min) applies (19.2.3.2.5.2(D)).

Spaces with substantial amounts of flammable or combustible liquids are protected to EH2 criteria (4.3.4.2); for ignitible liquids NFPA 30 also applies, and where the requirements differ the referenced standard governs (27.1.3, 27.2).

The inside hose allowance (0, 50 or 100 gpm) is part of the total above. The lower duration value is accepted where the waterflow alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3).

Comparison with EN 12845

The nearest EN 12845 classes are HHP2 (10.0 mm/min) or HHP3 (12.5 mm/min), both with 260 m² for wet or pre-action systems (325 m² for dry or alternate) and 90 minutes. The NFPA EH2 value in Table 19.2.3.1.1 is 16.3 mm/min over 230 m². EN 12845 Table 3 calls for special consideration of HHP4 and excludes deluge systems from its scope, while NFPA 13 requires sprinkler protection of ignitible liquids to be designed to NFPA 13 together with NFPA 30 (27.2).

The class comes from how the space is actually used. A project title or the occupancy on a permit is not enough; contents, stack height and flammable liquids are checked on site and the class is recorded with a written justification. For a quick first pass, use the NFPA 13 hazard classification tool.

Checklist

  1. Is the activity and type of contents recorded in writing?
  2. Are stack heights within the class definition; if not, have storage criteria been checked?
  3. Is the system type (wet/dry/pre-action) reflected in the area adjustment?
  4. Are hose allowance and duration included in the tank volume?
  5. Are areas of different classes in the same building calculated separately?

Frequently Asked Questions

What is the minimum water demand for NFPA 13 EH2?

In theory, at the standard design point 3,749 L/min (1,000 gpm) of sprinkler flow plus 1,900 L/min (500 gpm) of hose allowance, multiplied by 90 or 120 minutes. The real figure comes from the hydraulic calculation and is usually higher; the fire water tank sizing calculator helps with the volume.

Is a spray booth EH2?

Areas where flammable liquids are sprayed are given as EH2 examples. The booth itself and its ducts also carry the requirements of the standard specific to spray application.

Can EH2 be used for a flammable liquid store?

EH2 covers spaces with substantial amounts of flammable or combustible liquids (NFPA 13, 4.3.4.2); for ignitible liquids NFPA 30 also applies, and where the requirements differ the referenced standard governs (27.1.3, 27.2).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13, Standard for the Installation of Sprinkler Systems (2025 edition): 4.3, Table 10.2.4.2.1, 19.2.3, A.4.3 · EN 12845:2015+A2:2026. Values are for information; the binding text is the edition in force and the decision of the authority having jurisdiction.