Under NFPA 13-2025 Table 19.2.3.1.1 the design density for Light Hazard (LH) is 4.1 mm/min over 140 m² (0.10 gpm/ft² over 1,500 ft²); next to unsprinklered combustible concealed spaces 2.9 mm/min over 280 m² (0.07 gpm/ft² over 3,000 ft²) applies. Hose allowance is 380 L/min (100 gpm) and water supply duration is 30 minutes (Table 19.2.3.1.2).
Definition
Light hazard covers spaces where both the amount and the combustibility of the contents are low, so the fire you expect to fight has a relatively modest heat release rate. Furniture, paper and fabric are present, but not in dense stockpiles, and a fire usually stays at the scale of a single item or room.
Design parameters
| Parameter | SI | US units |
|---|---|---|
| Density (standard design) | 4.1 mm/min | 0.10 gpm/ft² |
| Design area (standard) | 140 m² | 1,500 ft² |
| Density (concealed space rule, 19.2.3.1.5) | 2.9 mm/min | 0.07 gpm/ft² |
| Design area (concealed space rule) | 280 m² | 3,000 ft² |
| Theoretical sprinkler flow (standard / concealed space) | 574 / 812 L/min | 150 / 210 gpm |
| Hose allowance (inside + outside) | 380 L/min | 100 gpm |
| Inside hose (part of the total) | 0, 190 or 380 L/min | 0, 50 or 100 gpm |
| Water supply duration | 30 min | 30 min |
| Maximum area per sprinkler (standard spray, Table 10.2.4.2.1(a)) | 20 m² | 225 ft² |
| Maximum distance between sprinklers | 4.6 m | 15 ft |
Theoretical flow is simply density × area. Actual system demand is higher because of hydraulic imbalance and the minimum sprinkler pressure (7 psi (0.5 bar), 28.2.4.11.1). Coverage and spacing values are for standard spray sprinklers; smaller limits apply under combustible obstructed construction and in pipe schedule systems.
Typical occupancies
- Offices, including data processing areas
- Schools and other educational buildings
- Hospitals, nursing homes and other institutional buildings
- Places of worship and clubs
- Residential areas
- Restaurant seating areas (not kitchens)
- Museums; libraries without large stack rooms
- Audience areas of theatres and auditoriums (not stages)
- Unused attics
- Animal shelters, kennels and veterinary hospitals
How the design area is set
NFPA 13-2025 no longer has the density/area curve of earlier editions. Table 19.2.3.1.1 gives a single design point for each class: 4.1 mm/min over 140 m² for LH. The second column, 2.9 mm/min over 280 m², applies only to the systems or portions of systems adjacent to unsprinklered combustible concealed spaces (19.2.3.1.5); the concealed spaces listed in 19.2.3.1.5.2 are exempt. Where an area of operation smaller than 140 m² is used, the density for 140 m² still applies (19.2.3.1.4). The density must be delivered over the whole hydraulically most remote area.
For dry pipe and double interlock pre-action systems the area of operation is increased by 30% without revising the density (19.2.3.2.6). Ceilings sloping more than 2 in 12 usually need a 30% increase as well (19.2.3.2.4). Where several adjustments apply they are compounded on the area first taken from Table 19.2.3.1.1, and the concealed space rule is applied last (19.2.3.2.8).
With listed quick-response sprinklers throughout a wet system, or a portion with the same hydraulic design basis, and a ceiling no higher than 20 ft (6.1 m), the area of operation may be reduced without revising the density: by 40% for ceilings of 10 ft (3 m) or less and by 25% at 20 ft (6.1 m), linear in between (Figure 19.2.3.2.3.1). Unprotected ceiling pockets must not exceed 32 ft² (3.0 m²), there must be no unprotected areas above cloud ceilings, and the design area must always contain at least five sprinklers (19.2.3.2.3).
The inside hose allowance (0, 50 or 100 gpm) is part of the total above. The lower duration value is accepted where the waterflow alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3).
Comparison with EN 12845
The closest match is the EN 12845 LH light hazard class (2.25 mm/min, 84 m², 30 minutes). The two standards do not measure the same thing: the NFPA 13 LH value in Table 19.2.3.1.1, 4.1 mm/min over 140 m², sits well above the EN values. EN 12845 also restricts LH to a narrower set of uses, so some offices and schools that are LH under NFPA may be treated as OH1 under EN.
The class comes from how the space is actually used. A project title or the occupancy on a permit is not enough; contents, stack height and flammable liquids are checked on site and the class is recorded with a written justification. For a quick first pass, use the NFPA 13 hazard classification tool.
Checklist
- Is the activity and type of contents recorded in writing?
- Are stack heights within the class definition; if not, have storage criteria been checked?
- Is the system type (wet/dry/pre-action) reflected in the area adjustment?
- Are hose allowance and duration included in the tank volume?
- Are areas of different classes in the same building calculated separately?
Frequently Asked Questions
What is the minimum water demand for NFPA 13 LH?
In theory, at the standard design point 574 L/min (150 gpm) of sprinkler flow plus 380 L/min (100 gpm) of hose allowance, multiplied by 30 minutes. The real figure comes from the hydraulic calculation and is usually higher; the fire water tank sizing calculator helps with the volume.
What NFPA 13 hazard class is an office building?
Typical office floors are light hazard (LH). Archive rooms, dense paper storage or plant rooms can fall into a higher class and must be assessed separately.
How much area can one sprinkler cover in light hazard?
With standard spray sprinklers on a hydraulically calculated system under noncombustible unobstructed construction, 225 ft² (20 m²), with a maximum spacing of 15 ft (4.6 m) (Table 10.2.4.2.1(a)).

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreNFPA 13, Standard for the Installation of Sprinkler Systems (2025 edition): 4.3, Table 10.2.4.2.1, 19.2.3, A.4.3 · BS EN 12845+A2:2026 (EN 12845:2015+A2:2026). Values are for information; the binding text is the edition in force and the decision of the authority having jurisdiction.