On the subject of diesel engine driven pump sets, BS EN 12845+A2:2026 contains a structural change compared with earlier editions: Clause 10.9 now consists of three short subclauses and hands the technical requirements over to EN 17451. This article shows what A2:2026 actually says, gathers the general Clause 10 provisions that continue to apply to a diesel pump set, and gives the diesel tests on the maintenance side with their source. Source: BS EN 12845+A2:2026, Clauses 10 and 20.
The full content of Clause 10.9 in A2:2026
10.9.1 General (TS p.68 / EN p.65)
Diesel driven pump sets and their ancillaries must comply with EN 17451. The pump room is required to have enough fresh air at all times for the diesel set to keep running within the limits set by the manufacturer and by EN 17451.
10.9.2 Starter alarm indication (TS p.69 / EN p.66)
Four conditions must each be signalled by a warning light, both locally and at a responsibly manned location:
- a) pump running;
- b) start failure;
- c) common faults;
- d) automatic mode off.
The alarm type of each signal is given in Annex I (see Monitoring and marking below).
10.9.3 Site commissioning test (TS p.69 / EN p.66)
Site commissioning test shall be performed in accordance with EN 17451.
That is the whole of Clause 10.9. In the text of A2:2026, Clause 10.9 consists only of subclauses 10.9.1, 10.9.2 and 10.9.3. Provisions such as fuel tank capacity (running time in hours), exhaust arrangements, the air filter, the starting attempt sequence (the number and duration of attempts), the number and standard of battery sets, and the cell voltage of the charger are therefore not to be looked for in this standard.
One cross-reference is left dangling in the text: Clause 20.3.4.3 (TS p.125 / EN p.122) states that in the yearly routine the failure to start alarm shall be tested "in accordance with 10.9.7.2", but there is no clause 10.9.7.2 in A2:2026. The second sentence of the same clause remains applicable: immediately after this test the engine shall be started using the manual starting system.
The European foreword of the standard gives the reason for the change (TS p.13 / EN p.10): compared with EN 12845:2015+A1:2019, technical changes have been made in order to integrate the references to EN 17451, EN 12845-2 and EN 12845-3 and their use into this document.
Other references to EN 17451
EN 17451 appears in several other places in the text of A2:2026:
| Clause | Reference | Page |
|---|---|---|
| 4.4.4.4 | Pump set documentation shall be provided in accordance with EN 17451 | TS p.31 / EN p.28 |
| 10.1 | Water supplies consisting of pumps shall conform to EN 17451 | TS p.60 / EN p.57 |
| 10.6.2.1 | The available NPSH in the suction pipe shall exceed the required NPSH by at least 1 m at the maximum pump set flow shown in Table 14, according to EN 17451 | TS p.62 / EN p.59 |
| 18.2.5.2 | On fully calculated installations the installer data in accordance with EN 17451 shall be displayed at the pump | TS p.119 / EN p.116 |
| Annex P | Three 50 % pump sets in accordance with EN 17451 are recommended for the ESFR water supply | TS p.167 / EN p.164 |
Provisions that continue to apply to a diesel pump set
Although Clause 10.9 has been narrowed, the general provisions of Clause 10 cover diesel sets as well, as "pump sets".
10.2 Multiple pump set arrangements (TS p.60 / EN p.57)
- The pump sets must have compatible characteristic curves and must be able to run in parallel at every possible flow rate.
- With two pumps, each must be able to deliver the specified flows and pressures on its own.
- With three pumps, each must be able to deliver at least 50 % of the specified flow at the specified pressure.
- A superior or duplicate water supply with more than one pump must have no more than one of them driven by an electric motor.
In practice the last item means that in a superior or duplicate water supply with two or more pumps, at least one pump has to be diesel (or otherwise non-electrically) driven.
10.3 Compartments for pump sets (TS p.60-61 / EN p.57-58)
10.3.1 General: Pump sets must be installed in a compartment with a fire resistance of at least 60 min that serves fire protection only. In order of preference, this compartment must be:
- a) a separate building;
- b) a building next to a sprinkler protected building, reached directly from outside;
- c) a compartment inside a sprinkler protected building, also reached directly from outside.
10.3.2 Sprinkler protection: Pump set compartments must have sprinkler protection. If the pump compartment is separate and feeding its sprinklers from the control valve sets in the premises would be impractical, the protection may instead be taken from the nearest accessible point downstream of the pump's outlet non-return valve, through a subsidiary stop valve secured open, together with a water flow detector to EN 12259-5 that gives a visible and audible signal when the sprinklers operate. Downstream of the flow alarm a 15 mm nominal diameter drain and test valve is required, so that the alarm system can be tested in practice.
10.3.3 Temperature: The pump set compartment must be kept at no less than the temperatures below:
| Pump type | Minimum compartment temperature |
|---|---|
| Electric driven pump sets | 4 °C |
| Diesel driven pump sets | 10 °C |
10.3.4 Ventilation: Diesel pump set compartments must be adequately ventilated, as recommended by the supplier.
10.4 Maximum temperature of water supply (TS p.61 / EN p.58)
The temperature of the water supply must not be higher than 40 °C. For submersible pump sets the limit is 25 °C, unless the motor has been shown to be suitable for temperatures up to 40 °C.
10.5 Valves and accessories (TS p.61 / EN p.58)
The pump suction pipe needs a stop valve, except where the maximum water level is below the pump. The delivery pipe of every pump must have a non-return valve and a stop valve. If a taper pipe is used at the pump outlet, it must widen in the flow direction at an angle of no more than 20°.
The same clause also requires a continuous flow of water through the pump, large enough to stop it overheating when it runs against a closed valve; this flow must be included in the hydraulic calculation of the system and in pump selection. Its discharge must be easy to see, and each pump must have its own discharge where there are several. It then adds a note specific to diesel sets: diesel engine cooling circuits normally use this same water, but any additional water they use must also be allowed for.
10.6 Suction conditions (TS p.62-63 / EN p.59-60)
10.6.1: Horizontal centrifugal pump sets must, wherever possible, be installed with a positive suction head: two thirds or more of the effective suction tank capacity must lie above the pump centre line, and the pump centre line must be at most 2 m above the suction tank's low water level (level X in 9.3.5).
10.6.2.2 Positive head: The suction pipe diameter must be at least 65 mm, and large enough that the velocity stays at or below 1.8 m/s with the pump at maximum demand flow.
10.6.2.3 Suction lift: The diameter of the suction pipe shall be no less than 80 mm and a velocity of 1.5 m/s shall not be exceeded at maximum demand flow. Where more than one pump set is installed, the suction pipes shall not be interconnected. The height from the low water level to the centre line of the pump shall not exceed 3.2 m. A foot valve shall be fitted at the lowest point on the suction pipe.
10.6.2.4 Pump priming: Every pump set must have its own automatic priming arrangement, made up of a tank placed above the pump and a pipe falling from the tank to the delivery side of the pump, with a non-return valve in that pipe. If the tank water level drops to 2/3 of normal, the pump must start; as an alternative, an alarm must be transmitted to a permanently attended location so that action is taken at once.
Table 15 Pump set priming tank capacity and pipe size (TS p.65 / EN p.62):
| Hazard class | Minimum tank capacity (litres) | Minimum priming pipe diameter (mm) |
|---|---|---|
| LH | 100 | 25 |
| OH, HHP and HHS | 500 | 50 |
Monitoring and marking
Annex I, Table I.1 (TS p.158 / EN p.155) gives the alarm types for the diesel pump set (the reference is to Clause 10.9.2):
| Alarm | Type |
|---|---|
| Automatic mode off | B |
| Start failure | B |
| Running | A |
| Common fault | B |
Annex I, I.2 Alarm levels (TS p.159 / EN p.156): signals from water flow alarms and/or alarm valves shall be indicated as a fire alarm (level A in Table I.1). Depending on local conditions, a signal indicating that the sprinkler pump set is running might alternatively be treated as a fault alarm. Technical faults such as a loss of power that could prevent the system operating correctly in a fire shall be indicated as a fault alarm (level B).
Annex H, H.2.6 Electrical power (TS p.157 / EN p.154): the power supply to electric pump sets or other critical electrical equipment shall be monitored, and an indication shall be given if one or more phases fail at any point in the main supply, the control circuit or the electric or diesel pump set control unit. H.2.4 (TS p.156 / EN p.153) requires an indication before the fuel level falls by more than 25 % of the nominal fill level. H.2.7 (TS p.157 / EN p.154) requires the minimum temperature of the sprinkler valve and pump rooms to be monitored.
Clause 18.2.6.2 (TS p.119-120 / EN p.116-117): the alarms specified in 10.8.5.1 and 10.9.2 shall be marked, both at the pump set controller and at the responsibly manned location, as appropriate: 'diesel fire pump starter switched off', 'diesel fire pump failure to start', 'pump running', 'diesel controller fault'. The manually operated shut-down mechanism shall be labelled 'SPRINKLER PUMP SHUT-OFF'.
Clause 18.2.5.1 (TS p.119 / EN p.116): a nameplate shall be fixed to each suction or booster pump giving the outlet pressure in bar at the inlet condition and flow value specified in Table 16, the corresponding nominal speed and the flow in litres per minute, and the maximum power absorbed at any flow value at the relevant speed.
For comparison: the 15 seconds for an electric pump set
A point that is often confused: in A2:2026 the 15 second requirement remains only for the electric pump. Clause 10.8.1.3 (TS p.67 / EN p.64), under the heading "10.8 Electrically driven pump sets", states that "after starting, the pump set shall operate at nominal capacity within 15 s". There is no run-up time provision for the diesel pump in Clause 10.9 of A2:2026.
The monitoring list for the electric set is separate too. Clause 10.8.5.1 (TS p.68 / EN p.65) lists the monitored conditions: power available to the motor (on all three phases where AC); pump on demand; pump running; start failure. 10.8.5.2: in the pump room each monitored condition must have its own visual indication, and pump running and a fault alarm must additionally be given audibly and visually at a location that responsible personnel attend permanently.
Maintenance: the tests belonging to the diesel pump
| Period | Clause | Content | Page |
|---|---|---|---|
| Weekly | 20.2.2.4 | The fuel and engine lubricating oil levels in diesel engines are checked; the water pressure on the starting device is reduced, simulating automatic starting; when the pump starts, the starting pressure is checked and recorded; on diesel pumps the oil pressure and the flow of cooling water through open circuit cooling systems are checked | TS p.122 / EN p.119 |
| Weekly | 20.2.2.5 | The engine is run for 20 min (or for the time recommended by the supplier), stopped and immediately restarted using the manual start test button; the water level in the primary circuit of closed circuit cooling is checked; oil pressure, engine temperatures and coolant flow are monitored throughout the test; the oil hoses are checked; a general inspection is made for leakage of fuel, coolant or exhaust fumes | TS p.122-123 / EN p.119-120 |
| Monthly | 20.2.3 | Electrolyte level and density are checked in every lead acid cell, diesel engine starter batteries and control panel supply batteries included; where density is low, the battery charger is checked first and, if it is working normally, the battery is replaced | TS p.123 / EN p.120 |
| Quarterly | 20.3.2.6 | Secondary electrical supplies from diesel generators are checked for satisfactory operation | TS p.124 / EN p.121 |
| Yearly | 20.3.4.2.1 | Each water supply pump set in the installation shall be tested at full load condition by means of the test line connection on the delivery leg downstream of the pump set outlet non-return valve, and shall give the pressure/flow values specified on the nameplate; appropriate allowances shall be made for the pressure losses in the supply pipe and valves between the source and each control valve set | TS p.124-125 / EN p.121-122 |
| Yearly | 20.3.4.3 | Test of the diesel engine failure to start alarm; immediately afterwards the engine shall be started using the manual starting system | TS p.125 / EN p.122 |
| Yearly | 20.3.4.5 | The pump set suction strainers, the settling chamber and its screens shall be inspected at least once a year and cleaned as necessary | TS p.125 / EN p.122 |
The same tests are used at commissioning: Clause 19.1.3 (TS p.120 / EN p.117) requires the water supplies to be tested once in accordance with 8.6 and the diesel engine driven pumps to be tested as specified in 20.2.2.5.
Field note
Clause 10.9 of A2:2026 has not been emptied but redirected: the internal requirements of the diesel set are to be found in EN 17451, while the system side requirements (compartment, temperature, ventilation, suction, priming, monitoring, marking, periodic testing) stay in EN 12845. A specification whose diesel pump clause refers only to EN 12845 now leaves out most of the technical requirements. (This paragraph is engineering commentary.)
Frequently Asked Questions
Which clause applies to diesel pump sets in A2:2026?
BS EN 12845+A2:2026 Clause 10.9 consists of three subclauses. 10.9.1 General (TS p.68 / EN p.65): diesel driven pump sets and their ancillaries must comply with EN 17451, and the pump room must always have enough fresh air for the diesel set to keep running within the limits set by the manufacturer and by EN 17451. 10.9.2 Starter alarm indication (TS p.69 / EN p.66). 10.9.3 Site commissioning test: it shall be performed in accordance with EN 17451. There is no 10.9.4 or any later subclause in A2:2026.
What is the minimum temperature of a diesel pump room?
Clause 10.3.3 (TS p.61 / EN p.58): the pump set compartment shall be maintained at or above 4 °C for electric driven pump sets and 10 °C for diesel driven pump sets. Clause 10.3.4 additionally requires compartments for diesel pump sets to be provided with adequate ventilation in accordance with the supplier's recommendations.
Which four conditions are indicated on a diesel pump set?
Clause 10.9.2 (TS p.69 / EN p.66): four conditions must each be signalled by a warning light, both locally and at a responsibly manned location: a) pump running; b) start failure; c) common faults; d) automatic mode off. Table I.1 of Annex I (TS p.158 / EN p.155) treats the 'running' signal as a type A alarm and the other three as type B.
Does the 15 second requirement apply to the diesel pump?
No, it applies to the electric pump. Clause 10.8.1.3 (TS p.67 / EN p.64): 'After starting, the pump set shall operate at nominal capacity within 15 s.' That clause sits under the heading 10.8 Electrically driven pump sets. Clause 10.9 of A2:2026 contains no run-up time provision for the diesel pump; the subject has been handed over to EN 17451.
What flow must each pump deliver where three pumps are installed?
Clause 10.2 (TS p.60 / EN p.57): with three pumps, each must be able to deliver at least 50 % of the specified flow at the specified pressure. With two pumps, each must be able to deliver the specified flows and pressures on its own. In every case the pump sets must have compatible characteristic curves and be able to run in parallel at every possible flow rate, and a superior or duplicate water supply with more than one pump must have no more than one of them driven by an electric motor.
References
- BS EN 12845+A2:2026 European foreword, integration of EN 17451 / EN 12845-2 / EN 12845-3 (TS p.13 / EN p.10)
- BS EN 12845+A2:2026 Clause 4.4.4.4 Automatic pump set documentation (TS p.31 / EN p.28)
- BS EN 12845+A2:2026 Clauses 10.1, 10.2, 10.3.1 (TS p.60 / EN p.57)
- BS EN 12845+A2:2026 Clauses 10.3.2, 10.3.3, 10.3.4, 10.4, 10.5 (TS p.61 / EN p.58)
- BS EN 12845+A2:2026 Clauses 10.6.1, 10.6.2.1, Table 14, 10.6.2.2 (TS p.62 / EN p.59)
- BS EN 12845+A2:2026 Clauses 10.6.2.3, 10.6.2.4 (TS p.63 / EN p.60)
- BS EN 12845+A2:2026 Table 15 Priming tank (TS p.65 / EN p.62)
- BS EN 12845+A2:2026 Clause 10.8.1.3 (TS p.67 / EN p.64)
- BS EN 12845+A2:2026 Clauses 10.8.5.1, 10.8.5.2, 10.9.1 (TS p.68 / EN p.65)
- BS EN 12845+A2:2026 Clauses 10.9.2, 10.9.3 (TS p.69 / EN p.66)
- BS EN 12845+A2:2026 Clauses 18.2.5.1, 18.2.5.2, 18.2.6.2 (TS p.119-120 / EN p.116-117)
- BS EN 12845+A2:2026 Clause 19.1.3 (TS p.120 / EN p.117)
- BS EN 12845+A2:2026 Clauses 20.2.2.4, 20.2.2.5, 20.2.3 (TS p.122-123 / EN p.119-120)
- BS EN 12845+A2:2026 Clauses 20.3.2.6 (TS p.124 / EN p.121), 20.3.4.2.1 (TS p.125 / EN p.122)
- BS EN 12845+A2:2026 Clauses 20.3.4.3, 20.3.4.5 (TS p.125 / EN p.122)
- BS EN 12845+A2:2026 Annex H, H.2.4 (TS p.156 / EN p.153), H.2.6 and H.2.7 (TS p.157 / EN p.154)
- BS EN 12845+A2:2026 Annex I, Table I.1 (TS p.158 / EN p.155), I.2 (TS p.159 / EN p.156)
- BS EN 12845+A2:2026 Annex P (TS p.167 / EN p.164)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.