Diesel fire pump fuel tank: three standards, three separate calculations
A diesel-driven fire pump is chosen so that water supply survives a mains power failure. That promise only holds if enough fuel sits next to the engine to run the pump through the fire. Three sources define the quantity differently, and the calculator works each one separately: NFPA 20-2025 asks for at least 12 hours of running; on EN 12845 projects the rule sits in EN 17451:2024 clause 4.4, which EN 12845:2015+A2:2026 clause 10.9.1 refers to, and is 3, 4 or 6 hours by hazard class; FM Global DS 3-7 asks for at least 8 hours. The three results for the same engine are compared below:
| Standard and clause | Rule | 100 kW engine at 0.25 L/kWh |
|---|---|---|
| NFPA 20-2025 11.4.1.3.1 | 12 h on the maker’s consumption + 5% expansion + 5% sump | 25 L/h × 12 h × 1.10 = 330 L |
| NFPA 20-2025 11.4.1.3.1.1 | Consumption not known: 1 gal/hp (5.07 L/kW) + 5% + 5% | 507.6 L × 1.10 = 558 L |
| EN 17451:2024 4.4 · EN 12845 LH | 3 h on full load | 25 × 3 = 75 L |
| EN 17451:2024 4.4 · EN 12845 OH | 4 h on full load | 25 × 4 = 100 L |
| EN 17451:2024 4.4 · EN 12845 HHP/HHS | 6 h on full load | 25 × 6 = 150 L |
| EN 17451:2024 4.4 · EN 12845-2 | At least 4 times the water supply duration (60 min → 4 h) | 25 × 4 = 100 L |
| FM DS 3-7 2.4.21.6 | 8 h run time + 5% expansion + 5% sump | 25 × 8 × 1.10 = 220 L |
1 · NFPA 20-2025: 12 hours on the maker’s consumption, otherwise 1 gal/hp
Under NFPA 20-2025 clause 11.4.1.3.1 the fuel tank must be sized for at least 12 hours of running on the engine manufacturer's published fuel consumption; where the consumption is not known (11.4.1.3.1.1), it must hold at least 1 US gallon for every horsepower of the engine. In both cases 5% is added for expansion and 5% for the sump, where sediment and water collect at the bottom of the tank. In SI units 1 gal/hp is 3.7854 L ÷ 0.7457 kW = 5.076 L/kW; the standard prints the ratio as 5.07 L/kW.
Consumption known: Vtank = P × SFC × 12 h × 1.10 Consumption not known: Vtank = P [kW] × 5.076 L/kW × 1.10The 1 gal/hp rule is generous: at 0.25 L/kWh the tank’s usable 507.6 L runs the engine at full load for about 20 hours, so using the maker's data usually gives a smaller tank. NFPA 20 also reserves the tank and fuel for the fire pump engine, requires a separate tank and separate supply and return lines for each engine (11.4.1.2), places the supply connection so that 5% of the tank volume is a sump the engine cannot use (11.4.1.5.4.2), and calls for a fuel level indicator at the two-thirds level (11.4.2.2). The calculator adds the two 5% allowances of 11.4.1.3.1 to the net fuel volume (net × 1.10); because the 11.4.1.5.4.2 sump is 5% of the tank volume, reading the allowances against the tank volume gives tank ≈ net ÷ 0.90 (about 1% larger).
2 · EN 12845 → EN 17451:2024: 3, 4 or 6 hours by hazard class
EN 12845:2015+A2:2026 clause 10.9 sets no fuel running time of its own; clause 10.9.1 places diesel pump sets and their ancillaries under EN 17451. Under EN 17451:2024 clause 4.4 the tank must hold the fuel to run the engine on full load, in the most unfavourable atmospheric and environmental conditions, for the period of duty. The minimum periods for EN 12845 are:
- LH: 3 hours
- OH: 4 hours
- HHP and HHS: 6 hours
The client specification may extend these. For EN 12845-2:2024 (ESFR and CMSA) installations the tank must last at least 4 times the water supply duration; under EN 12845-2 Table 6 that duration is 60 min for 9–12 ceiling sprinklers (fuel for 4 h), 90 min for 15–16 sprinklers (6 h) and 120 min for 20–30 sprinklers (8 h); CMSA roll paper storage takes 120 min and CMSA rubber tyre storage 180 min (12 h). In the calculator you choose the number of ceiling sprinklers in the design, or the CMSA roll paper or tyre case, rather than the duration; the water and fuel durations follow from Table 6. For in-rack designs the duration comes from the specific design clauses, not Table 6.
EN 12845: V = P × SFC × t (LH 3, OH 4, HHP/HHS 6 h) EN 12845-2: V = P × SFC × 4 × twaterEN 17451 defines no expansion or sump percentage; instead it requires the feed pipe at least 20 mm above the tank bottom. Adding an allowance for that dead volume and the ullage is the designer’s decision; in the calculator it is optional and defaults to 0%. The same clause requires a welded steel tank; a tank higher than the engine fuel pump but not directly above the engine; a separate tank and separate feed pipes for each pump set where there is more than one diesel pump set; a drain valve of at least DN15 at the base; a level gauge and a low fuel alarm when the level falls below 75% of the required minimum; no soldered joints, with metallic pipes and steel hoses. The tank must be marked with the required fuel grade (4.5).
3 · FM Global DS 3-7: 8 hours + 5% + 5%
Under FM Global Data Sheet 3-7 (April 2012, interim revision April 2025) clause 2.4.21.6 the fuel tank is sized for at least 8 hours of engine run time, plus 5% volume for expansion and 5% for the sump. FM gives no per-hp ratio for an unknown consumption; use the engine maker’s full-load figure.
FM DS 3-7: Vtank = P × SFC × 8 h × 1.10The same section calls for a double-walled steel or concrete vault tank (2.4.21.1), located in the pump room with fill and vent lines extended outdoors (2.4.21.3), curbing for the entire contents plus 5 cm (2.4.21.4), no glass or plastic sight tubes (2.4.21.5), a supply line not taken from the tank bottom, leaving 5% of the volume as sump, with the connection higher than the engine fuel pump (2.4.21.9), and separate tanks and lines for each engine in multi-pump installations (2.4.21.8). Reading the sump as 5% of the tank volume gives tank ≈ net ÷ 0.90; the calculator uses the same reading as NFPA 20, net × 1.10.
Specific fuel consumption
q [L/h] = P [kW] × SFC [L/kWh]Specific fuel consumption (SFC) varies by engine. Modern fire pump diesels typically burn 200–230 g/kWh at full load; with diesel at 0.83–0.85 kg/L that is roughly 0.25 L/kWh. The calculator uses this as an assumption; always replace it with the full-load consumption from the engine manufacturer's data sheet. EN 17451 asks for the consumption in the most unfavourable atmospheric and environmental conditions, so check the maker’s derating data for altitude and high ambient temperature.
Choosing a standard tank and reading the calculator
The calculated volume is rounded up to the common sizes of 200, 300, 500, 750, 1000, 1500, 2000 and 3000 litres; above 95% fill the next size up is advisable. The large result tile gives the required tank capacity and clause for the chosen standard; the three tiles beneath it show the NFPA 20, EN 12845 / EN 17451 and FM DS 3-7 results for the same engine side by side and mark the selected one. The strip at the top of the drawing names the standard and clause used. The hatched band in the tank section marks the sump allowance (none under EN 17451); the light dashed line shows the net fuel + 5% sump level under NFPA 20 and FM DS 3-7, and the level of the fuel for the duty period under EN 12845 / EN 17451; the clock dial at bottom left shows the running time.
Fuel quality: fuel may sit in the tank for a long time; do not miss the seasonal switch between summer and winter diesel, drain water from the tank bottom regularly and check the level at every weekly run test. Confirm double-wall and bunding requirements with local environmental and fire regulations and the authority having jurisdiction.
Frequently Asked Questions
How is a diesel fuel tank sized to NFPA 20?
Under NFPA 20-2025 11.4.1.3.1 the tank is sized for at least 12 hours of running on the maker's fuel consumption data: for 100 kW at 0.25 L/kWh, 25 L/h × 12 h = 300 L, or 330 L with 5% expansion and 5% sump. Where the consumption is not known (11.4.1.3.1.1), allow 1 US gallon per engine horsepower (5.07 L/kW): a 100 kW (134 hp) engine needs 507.6 L × 1.10 ≈ 558 L (147.5 gal).
How many hours of fuel does EN 12845 require?
EN 12845:2015+A2:2026 clause 10.9.1 places diesel pump sets under EN 17451. Under EN 17451:2024 clause 4.4 the engine must run on full load, in the most unfavourable conditions, for 3 hours for LH, 4 hours for OH and 6 hours for HHP and HHS; for EN 12845-2 (ESFR/CMSA) installations the period is at least 4 times the water supply duration. For a 100 kW engine at 0.25 L/kWh, OH needs 100 L.
What does FM Global require for a diesel fuel tank?
FM Global DS 3-7 clause 2.4.21.6 sizes the tank for at least 8 hours of engine run time and adds 5% volume for expansion and 5% for the sump: for a 100 kW engine at 0.25 L/kWh, 25 L/h × 8 h × 1.10 = 220 L. The tank should be double-walled steel or a concrete vault type and sit in the pump room.
What specific fuel consumption should I use?
Use the full-load consumption from the engine manufacturer's data sheet; EN 17451 asks for it in the most unfavourable atmospheric and environmental conditions. Without it, 0.25 L/kWh (about 210 g/kWh) is a reasonable starting point for preliminary sizing.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design in Three Standards
Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.
Get SprinkCalc on the App Store