Short answer: BS EN 12845+A2:2026 Clause 14.2.2 (TS p.107 / EN p.104): ceiling, flush, recessed and concealed sprinklers shall not be installed in OH4, HHP or HHS areas. In addition, sprinklers without fixed deflectors (for example types with retracted deflectors which drop to the operating position on actuation) shall not be fitted in three situations: a) where the ceiling is more than 45° from the horizontal; b) where the atmosphere is corrosive or likely to have a high dust content; c) in racks or under shelves.

Sprinkler types set into a suspended ceiling are governed in three places in BS EN 12845+A2:2026: the definitions in Clause 3 (TS p.23-24 / EN p.20-21), the limits of use in Clause 14.2 (TS p.107 / EN p.104) and the positioning rules in Clause 12.4 (TS p.75 / EN p.72). This article brings the three parts together and also lists explicitly the provisions the standard does not give for these types.

The definitions in the standard

Clause Term Definition (TS p.23-24 / EN p.20-21)
3.55 sprinkler, ceiling or flush A pendent sprinkler that sits partly above the ceiling while its temperature sensitive element stays below the ceiling plane
3.56 sprinkler, concealed A recessed sprinkler with a cover plate that releases when exposed to heat
3.57 sprinkler, conventional pattern Discharges water in a spherical pattern
3.65 sprinkler, pendant Its nozzle directs the water downwards
3.66 sprinkler, recessed A sprinkler whose heat sensing element lies wholly or partly above the lower plane of the ceiling
3.67 sprinkler rosette A plate closing the gap between the ceiling and the shank or body of a sprinkler that passes through a suspended ceiling

The difference between the definitions turns on a single point: the position of the heat sensitive element relative to the plane of the ceiling. In the ceiling/flush type the element is below the plane of the ceiling; in the recessed type all or part of the element is above the plane of the ceiling; and a concealed sprinkler is a recessed sprinkler with a cover plate.

Clause 14.2.2: Restrictions on use

Clause 14.2.2 of BS EN 12845+A2:2026 (TS p.107 / EN p.104) sets up a prohibition in two layers.

First layer, for all recessed patterns: Ceiling, flush, recessed and concealed sprinklers shall not be installed in OH4, HHP or HHS areas.

Second layer, for sprinklers without fixed deflectors: a sprinkler whose deflector is not fixed (for example a retracted deflector that drops into its operating position when the sprinkler actuates) must not be used in any of these situations:

  • a) where the ceiling is more than 45° from the horizontal;
  • b) where the atmosphere is corrosive or likely to have a high dust content;
  • c) in racks or under shelves.

For comparison, the limits on the other patterns (TS p.107 / EN p.104): 14.2.3 prohibits sidewall sprinklers in HH installations (except for the protection of corridors, cable ducts and columns), in OH storage areas and above suspended ceilings; they might only be installed under flat ceilings. 14.2.4 requires flat spray sprinklers to be used only in concealed spaces, above suspended open ceilings and in racks.

Table 37a: Which K-factor for which type

Clause 14.2.1 (TS p.106 / EN p.103): the sprinkler used in each hazard class must follow Table 37a together with the limits of 14.2.2 to 14.2.4.

Hazard class Design density (mm/min) Sprinkler type Nominal K-factor
LH 2.25 conventional, spray, ceiling, flush, flat spray, recessed, concealed and sidewall 57
OH 5.0 conventional, spray, ceiling, flush, flat spray, recessed, concealed and sidewall 80 or 115
HHP and HHS, sprinklers at ceiling or roof ≤ 10 conventional or spray 80, 115 or 160
HHP and HHS, sprinklers at ceiling or roof > 10 conventional or spray 115 or 160
HHS, intermediate-level sprinklers in high piled storage - conventional, spray and flat spray 80 or 115

The ceiling, flush, recessed and concealed types do not appear at all in the HHP/HHS rows of the table, which is consistent with the prohibition in 14.2.2.

From K-factor to pressure

Clause 14.3 (TS p.107-108 / EN p.104-105): sprinkler flow must be calculated as Q = K√P, with Q in litres per minute, K the constant taken from Table 37a and P the pressure in bar.

Inverted, the formula becomes P = (Q/K)². Example: in an OH class with a design density of 5.0 mm/min and an area of coverage per sprinkler of 12 m², the required flow is 5.0 × 12 = 60 l/min. For that flow:

K-factor Required pressure P = (60/K)²
K115 0.27 bar
K80 0.56 bar

Both values have to be read together with the 0.35 bar minimum that Clause 13.4.4 gives for OH (TS p.105 / EN p.102): the 0.27 bar calculated with K115 (K8.0) falls below that threshold, so the governing value becomes 0.35 bar, while the 0.56 bar found with K80 (K5.6) is above the threshold and is itself the governing value.

Clause 14.4 and Table 37b: Temperature rating and colour code

Clause 14.4 Sprinkler temperature ratings (TS p.108 / EN p.105): the temperature rating must be close to, but not lower than, the highest expected ambient temperature plus 30 °C.

This sentence sets a lower limit: the nominal rating selected cannot be below the ambient temperature + 30 °C, and it is required to be close to that value. Reading it as a requirement not to exceed the ambient temperature by 30 °C turns the provision on its head.

The same clause continues: places such as unventilated concealed spaces and the areas under skylights or glass roofs may need a higher operating temperature, up to 93 °C or 100 °C. Near drying ovens, heaters and other equipment that radiates heat, the sprinkler rating must be given special consideration.

NOTE 1: In temperate climates and normal conditions, a 68 °C or 74 °C rating is suitable. NOTE 2: A sprinkler's temperature rating is shown by a colour code to EN 12259-1, as listed in Table 37b.

Table 37b (TS p.108 / EN p.105)

Glass bulb sprinklers: nominal operating temperature (°C) Liquid colour code Fusible link sprinklers: range (°C) Yoke arms colour code
57 orange 57–77 uncoloured
68 red 80–107 white
79 yellow 121–149 blue
93 green 163–191 red
100 green 204–246 green
121 blue 260–302 orange
141 blue 320–343 black
163 mauve
182 mauve
204 black
227 black
260 black
286 black
343 black

The point to watch: there is no 74 °C row in the table. Yellow corresponds to 79 °C. The figure 74 °C appears only in NOTE 1 to Clause 14.4, as a rating suitable in a temperate climate.

Positioning: deflector distances and clear space

Clause 12.4.2 (TS p.75 / EN p.72) contains two separate rules.

Upper limits: a sprinkler must be no more than 0.3 m below the underside of a combustible ceiling, or no more than 0.45 m below a roof or ceiling of Euroclass A1 or A2 (or the equivalent class in an existing national classification system).

Preferred band and the exception for recessed patterns: wherever possible the deflector must sit 0.075 m to 0.15 m below the ceiling or roof; this band does not apply to ceiling, flush or recessed sprinklers. If the maximum distances of 0.3 m and 0.45 m cannot be avoided, they must be confined to the smallest possible area.

Exempting the recessed patterns from this band follows directly from the definitions: the body of a ceiling/flush or recessed sprinkler is already partly or wholly above the plane of the ceiling.

Clause 12.1.2 (TS p.73 / EN p.70) gives the clear space to be maintained below the deflector:

Class Minimum clear space below the deflector
LH and OH, flat spray sprinklers 0.3 m
LH and OH, all other cases 0.5 m
HHP and HHS 1.0 m

Clause 12.4.3 (TS p.75 / EN p.72): deflectors must follow the slope of the roof or ceiling, i.e. run parallel to it. On a slope steeper than 30° from the horizontal, one row of sprinklers must be placed at the apex or within 0.75 m of it, measured radially.

Rosettes, guards and painting

Clause 14.8 Sprinkler rosettes (TS p.110 / EN p.107): a rosette must be metal or thermosetting plastic and must never carry a ceiling or any other structure. No part of it may protrude from the ceiling lower than the top of the visible part of the sprinkler's heat sensitive element.

Clause 14.6 Sprinkler guards (TS p.109 / EN p.106): any sprinkler other than a ceiling or flush sprinkler that is placed where accidental mechanical damage could occur must have a suitable metal guard. The exemption covers only the ceiling/flush pattern; recessed and concealed sprinklers installed in a position at risk of mechanical damage remain subject to this requirement.

Clause 14.1 General (TS p.106 / EN p.103): Only new (unused) sprinklers shall be used. Sprinklers shall not be painted except as permitted by EN 12259-1. They shall not be altered in any way after despatch from the manufacturing works, and no decoration or coating other than that specified in 14.9 shall be applied to them. NOTE: This standard covers only the types of sprinkler specified in EN 12259-1.

Clause 14.9 Corrosion protection of sprinklers (TS p.110 / EN p.107): where corrosive vapours are prevalent in the premises, sprinklers must carry a suitable corrosion resistant coating applied by the supplier in accordance with EN 12259-1, unless they are made of materials that are themselves suitably corrosion resistant. The anti-corrosion treatment shall not be applied to sprinkler bulbs.

What the standard does not say here

The following do not appear in the text of BS EN 12845+A2:2026:

  • A nominal release temperature for the cover plate of a concealed sprinkler (for example 57 °C) or a requirement that the cover plate be rated lower than the bulb
  • A definition of "two stage activation" for a concealed cover plate
  • A separate approval or certification provision for the concealed cover plate
  • A requirement to order factory painted cover plates, or any statement that painting on site invalidates the approval

The only thing the standard says about painting is Clause 14.1: sprinklers shall not be painted except as permitted by EN 12259-1.

Thermal sensitivity

Clause 14.5.1 (TS p.109 / EN p.106): the sensitivity of the sprinklers must be chosen according to Table 38. When there are in-rack sprinklers, the ceiling sprinklers must be as sensitive as, or slower to respond than, the sprinklers in the racks. NOTE: Most types of sprinkler are rated, in descending order of sensitivity, as one of the following (see EN 12259-1): quick response, special response, standard response 'A'.

Field note

With regard to the class limit on recessed patterns (14.2.2), the point to watch is that a store room or plant space in the same building rises to OH4 or HHS and the ceiling pattern is simply carried on into it. Showing the class boundaries area by area on the block plan (Clause 18.1 b) makes that boundary easier to follow on site. (This paragraph is engineering commentary.)

Frequently Asked Questions

Where are ceiling, flush, recessed and concealed sprinklers prohibited?

BS EN 12845+A2:2026 Clause 14.2.2 (TS p.107 / EN p.104): ceiling, flush, recessed and concealed sprinklers shall not be installed in OH4, HHP or HHS areas. In addition, sprinklers without fixed deflectors (for example types with retracted deflectors which drop to the operating position on actuation) shall not be fitted in three situations: a) where the ceiling is more than 45° from the horizontal; b) where the atmosphere is corrosive or likely to have a high dust content; c) in racks or under shelves.

How does the standard define these sprinkler types?

Clause 3.55 (ceiling or flush sprinkler): a pendent sprinkler that sits partly above the ceiling while its temperature sensitive element stays below the ceiling plane. 3.56 (concealed sprinkler): a recessed sprinkler with a cover plate that releases when exposed to heat. 3.66 (recessed sprinkler): a sprinkler whose heat sensing element lies wholly or partly above the lower plane of the ceiling. 3.65 (pendant sprinkler): its nozzle directs the water downwards. (TS p.23-24 / EN p.20-21)

How is the sprinkler temperature rating selected?

Clause 14.4 (TS p.108 / EN p.105): the temperature rating must be close to, but not lower than, the highest expected ambient temperature plus 30 °C. In other words, ambient + 30 °C is a lower limit, not an upper limit. NOTE 1: in temperate climates and normal conditions, a 68 °C or 74 °C rating is suitable. Unventilated concealed spaces and areas under skylights or glass roofs may need a higher operating temperature, up to 93 °C or 100 °C.

What temperature does a yellow bulb correspond to in Table 37b?

79 °C. The glass bulb series of Table 37b in BS EN 12845+A2:2026 (TS p.108 / EN p.105) is: 57 orange, 68 red, 79 yellow, 93 green, 100 green, 121 blue, 141 blue, 163 mauve, 182 mauve, 204 black, 227 black, 260 black, 286 black, 343 black. There is no 74 °C row in the table; 74 °C appears only in NOTE 1 to Clause 14.4 as a suitable rating.

How far below the ceiling should the deflector be?

Clause 12.4.2 (TS p.75 / EN p.72): wherever possible the deflector must sit 0.075 m to 0.15 m below the ceiling or roof; this band does not apply to ceiling, flush or recessed sprinklers. The same clause also sets the upper limits: a sprinkler must be no more than 0.3 m below the underside of a combustible ceiling, or no more than 0.45 m below a roof or ceiling of Euroclass A1 or A2.

References

  • BS EN 12845+A2:2026 Clause 3.55, 3.56, 3.57 (TS p.23 / EN p.20)
  • BS EN 12845+A2:2026 Clause 3.65, 3.66, 3.67 (TS p.24 / EN p.21)
  • BS EN 12845+A2:2026 Clause 12.1.2 Clear space below the deflector (TS p.73 / EN p.70)
  • BS EN 12845+A2:2026 Clause 12.4.2 and 12.4.3 Position of sprinklers (TS p.75 / EN p.72)
  • BS EN 12845+A2:2026 Clause 13.4.4 Minimum sprinkler discharge pressure (TS p.105 / EN p.102)
  • BS EN 12845+A2:2026 Clause 14.1 General (TS p.106 / EN p.103)
  • BS EN 12845+A2:2026 Clause 14.2.1, Table 37a, 14.2.2, 14.2.3, 14.2.4, 14.3 (TS p.107 / EN p.104)
  • BS EN 12845+A2:2026 Clause 14.4, Table 37b (TS p.108 / EN p.105)
  • BS EN 12845+A2:2026 Clause 14.5.1, Table 38, 14.6, 14.7 (TS p.109 / EN p.106)
  • BS EN 12845+A2:2026 Clause 14.8 Rosettes, 14.9 Corrosion protection (TS p.110 / EN p.107)
  • BS EN 12845+A2:2026 Clause 18.1 Block plan (TS p.118 / EN p.115)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.