Hotel lobbies, shopping centres, hospitals, offices: the architect wants sprinklers hidden and the designer's density and K-factor arithmetic gets tight. A field guide to picking the right one of the four types.

If, while concealed sprinklers are going into the plasterboard ceiling of a five-star hotel lobby, somebody says "the cover plates don't match the RAL, let's have the painter spray them" — you need to stop. That sentence is where site practice leaves the standard and its EN 12259-1 approval behind and starts improvising. This article sorts out which of flush, recessed and concealed goes where, how high a K-factor you can reach, and which type suits which architectural setting.

Definitions

EN 12845 defines four pendent geometries separately, and calling them all "hidden sprinklers" is the main source of confusion:

Deflector position

The general rule is often overlooked: the sprinkler deflector must sit between 0.075 m and 0.15 m below the ceiling, except where ceiling, flush or recessed sprinklers are used. So the 75–150 mm window is mandatory for a standard pendent, while for flush, recessed and concealed types the manufacturer's approved installation template governs — usually leaving the deflector within 0–30 mm of the ceiling. The lower limits are fixed: a sprinkler may not be brought more than 0.3 m below a combustible ceiling, or more than 0.45 m below a non-combustible (A1/A2) ceiling.

Separately, the clear volume required below the deflector is 0.3 m for flat spray sprinklers in LH and OH, 0.5 m for other types, and 1.0 m for HHP and HHS. Because a concealed deflector drops down when the plate releases, take the operating position from the manufacturer's data, not the cover plate line.

Where each type is prohibited

EN 12845 sums up the selection in one sentence: ceiling, flush, recessed and concealed sprinklers shall not be installed in OH4, HHP or HHS areas. In other words:

Hazard classPendentFlushRecessedConcealed
LH (hotel rooms, office floors, libraries)OKOKOKOK
OH1–OH3 (retail, hospitals, restaurants)OKOKOKOK
OH4 (printing, textiles)OKProhibitedProhibitedProhibited
HHP (chemicals, plastics process)OKProhibitedProhibitedProhibited
HHS (storage)OK (K160 and above)ProhibitedProhibitedProhibited

Three further prohibitions apply to drop-down deflector types, meaning concealed heads: where the ceiling slope exceeds 45°, where the atmosphere is corrosive or heavily dust laden, and in or under racking. A concealed sprinkler in a workshop ceiling is a defect waiting to be found; a concealed cover plate above a cold store duct is a poor idea.

K-factor and density compatibility

The permitted K-factors are fixed by hazard class. The critical point: the practical K range for flush, recessed and concealed bodies is limited.

HazardDesign density (mm/min)Permitted KConcealed in practice
LH2.25K57K57 standard from manufacturers
OH1–OH35.0K80 or K115K80 and K115 available
OH45.0K80 or K115Prohibited
HHP/HHS (up to 10 mm/min)≤ 10K80, K115 or K160Type prohibited — pendent required

The field consequence: 5.0 mm/min over an average 12 m² area with a K115 sprinkler gives roughly 0.75 bar. The same duty on K80 needs about 1.5 bar, which pushes the pump curve up and feeds through into pipe sizes. When the architect asks for "slim concealed plates", the decision effectively caps you at K80 and multiplies the system pressure. That negotiation belongs in the design office, not on site.

Cover plate temperature logic

A concealed sprinkler operates in two stages:

  1. The cover plate separates from the body as its solder releases at a set temperature, typically 57 °C.
  2. Once the plate falls, the deflector drops into its operating position; the main glass bulb then bursts at the normal fire temperature, usually 68 °C red or 74 °C yellow.

The sprinkler rating must not exceed the ambient by more than 30 °C, and 68 or 74 °C suits normal environments. The concealed plate must always be rated lower than the main bulb — otherwise the sprinkler tries to operate with the plate still in place, pressure throws the plate off and the spray pattern is disturbed. A 57 °C plate under a 100 °C bulb is the typical pairing.

Choosing by architectural setting

SpaceHazardRecommended typeReason
Hotel room, corridor, lobbyLHConcealed with RAL plateDesign led, should not be visible in the plasterboard
Hotel kitchen service areaOH3Pendent or recessedGrease and vapour foul a concealed plate
Shopping centre unitOH3 by contentsRecessed or concealedArchitectural demand, density held with K115
Mall common area, atrium ceilingOH2Pendent, exposed concrete soffitThe soffit is visible; concealment is pointless
Hospital ward and corridorOH1Concealed, cleanable plateHygiene, appearance, infection control
Hospital laboratory or sterilisationOH2RecessedSteam and cleaning loosen a concealed solder joint
Open-plan officeLHConcealed or flushArchitectural, low hazard
Office archive or IT storeOH3PendentK115 and above needed; concealed bodies too limited
Car park, plant floorOH2Pendent, exposed soffitNo aesthetic concern, mechanical impact risk
Places of worship, museums, historic buildingsLHConcealed where achievableVisual sensitivity

Testing and approval

EN 12845 requires sprinklers to comply with EN 12259-1, which covers the body, bulb or solder, deflector, K-factor, temperature rating and K-factor tolerance; the concealed cover plate falls under the same family plus the manufacturer's specific approval (LPCB, VdS, FM or UL).

For a site check, look for three marks on the body or yoke: the K-factor, the nominal temperature (with its colour code) and the approval mark. The concealed plate carries its own nominal temperature stamp, usually 57 or 68. Mixing manufacturers — sprinkler from one, plate from another — voids the approval; the assembly must be listed as a matched set.

The most common field errors

Comparison with NFPA 13

NFPA 13 defines the same four types. The numerical differences:

Turkish context

BYKHY treats a sprinkler system as compliant when designed to TS EN 12845 or equivalent, and accepts the TS EN 12259 series for components. So on Turkish projects using concealed, flush or recessed sprinklers, the product schedule must show:

Fire brigade approval inspections specifically ask for the RAL code and manufacturer's label on concealed plates in plasterboard ceilings; site painting found on inspection fails acceptance. On hospital projects, health ministry inspectors additionally ask about cleanability of the plate surface.

A short decision matrix

Frequently Asked Questions

Where are concealed sprinklers prohibited?

In OH4, HHP and HHS areas, and for drop-down types also on ceilings steeper than 45 degrees, in corrosive or dusty atmospheres, and in or under racking.

At what temperature does the cover plate fall?

Typically 57 C. The plate must always be rated below the main bulb, so it releases first and lets the deflector drop into position.

Can the cover plate be painted on site?

No. An extra paint layer insulates the solder, the plate does not fall and the sprinkler never operates. Order factory-finished plates instead.

What K-factor can a concealed head reach?

K57 for LH and K80 or K115 for OH1 to OH3. Higher K bodies are not made in concealed form, and those hazard classes prohibit the type anyway.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845:2015+A1:2019 Fixed firefighting systems — Automatic sprinkler systems. EN 12845-2:2024 (CMSA & ESFR sprinkler systems). NFPA 13 Standard for the Installation of Sprinkler Systems. Turkish Regulation on Fire Protection of Buildings (BYKHY). FM Global Property Loss Prevention Data Sheet 2-0.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.