A conventional sprinkler "controls" a fire — it wets the surroundings and slows the spread. ESFR "suppresses" it — driving large droplets into the seat of the fire at high velocity and finishing the job in 60–90 s. The difference lives in three numbers: K-factor, RTI and pressure. A designer has to understand all three.

In the 1980s, full-scale rack storage fires were staged in test halls to compare approaches. Once a conventional CMDA system operated, 200 to 300 sprinklers would open at once and the water demand would reach 30 000–60 000 L/min — and the fire was still only controlled, not extinguished. Engineers tried the opposite route: fewer heads, much larger droplets, fast response, aimed straight at the fire core. ESFR was the result — twelve sprinklers, around 9000 L/min, suppression within 60 s. Today it is the most widely used protection for high-bay storage in the world.

K-factor — the discharge coefficient

The K-factor links sprinkler flow to pressure:

Q = K × √P

Q is flow in L/min and P is pressure in bar. The K-factor is set by orifice diameter and geometry. Common ESFR K-factors in EN 12845-2:

K-factor (metric)K (US, gpm/psi0.5)OrificeTypical flow at 3.5 bar
K200K1415 mm374 L/min
K240K16.817 mm449 L/min
K320K22.420 mm599 L/min
K360K25.222 mm674 L/min
K480K33.625 mm898 L/min

Suppression versus control — two philosophies

AspectControl (CMDA)Suppression (ESFR)
ObjectiveWet the surroundings, limit spreadExtinguish the fire core
Operating sprinklersThe whole design area (260–360 m²)12 sprinklers
Water demand30 000–60 000 L/min8000–12 000 L/min
Duration60–90 min60 min is sufficient
Role of the fire serviceExtinguishmentConfirmation and cooling
DamageHigh, because of spreadLow, because it is contained

RTI — response speed

The Response Time Index measures how quickly a sprinkler bulb reacts to heat:

RTI = τ × √v

τ is the bulb time constant in seconds and v is gas velocity in m/s, giving units of (m·s)0.5.

ESFR requires an RTI below 50; in practice listed products sit around 28–35. A low RTI means a thin bulb that senses heat quickly.

Droplet velocity against the fire plume

A hot gas plume rises above the seat of the fire. At 5–10 m height that plume moves at 5–15 m/s and reaches 600–900 °C. A droplet has to fall against it. The ESFR droplet:

This is exactly why ESFR needs high pressure, 3.5–5.2 bar. At low pressure the droplet loses to the plume.

Field error — inadequate pump pressure

An e-commerce warehouse was designed with ESFR K360. The pump was specified at 8000 L/min and 3.5 bar, but friction losses downstream were never added, so the pressure reaching the sprinklers fell to 2.8 bar. It was found during the annual functional test. A standard sprinkler might have coped at that pressure, but the ESFR droplet velocity falls short and cannot penetrate the plume. The hydraulics were recalculated, the pump head increased and the pipe sized up one step. With ESFR, missing pressure means the system effectively does not exist.

K-factor selection matrix

Ceiling heightStorage heightCommodityK-factorPressure
≤ 9 m≤ 6 mClass I–IIIK2003.5 bar
≤ 9 m≤ 6 mGroup A plasticsK2004.1 bar
9–12 m≤ 9 mPlasticsK2403.5 bar
12–13.7 m≤ 10.7 mPlasticsK3203.5 bar
Above 13.7 mAbove 10.7 mPlasticsK360 or K4803.5–5.2 bar

ESFR placement criteria in brief

Alignment with NFPA 13

EN 12845-2 K-factor and pressure values align closely with NFPA 13. The differences are largely unit conventions — NFPA works in psi and gpm, EN in bar and L/min. NFPA K22 is close to EN K320, and NFPA K25.2 corresponds to EN K360. Design software handles the conversions automatically.

Quick check list

Frequently Asked Questions

What is the difference between suppression and control?

Control wets the surroundings and limits spread until the fire service arrives. Suppression drives large, fast droplets through the fire plume into the seat of the fire and extinguishes it, typically within 60 s.

What does the K-factor actually describe?

The discharge coefficient linking flow to pressure, Q = K × √P. It is set by the orifice size and geometry — K200 is a 15 mm orifice, K360 a 22 mm one.

Why does ESFR need such high pressure?

Because the droplet has to fall against a rising plume moving at 5–15 m/s. Resistance scales with droplet mass times velocity squared, and at low pressure the droplet simply loses.

What RTI does an ESFR head need?

Below 50. Listed products typically sit around 28–35 — a thin bulb that senses heat quickly, which is what makes early operation possible.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845:2015+A1:2019 Fixed firefighting systems — Automatic sprinkler systems. EN 12845-2:2024 (CMSA & ESFR sprinkler systems). NFPA 13 Standard for the Installation of Sprinkler Systems. Turkish Regulation on Fire Protection of Buildings (BYKHY). FM Global Property Loss Prevention Data Sheet 2-0.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.