A manufacturing plant has its sprinkler scheme drawn to NFPA 13 as light hazard. When the insurance surveyor arrives, the production line is assessed as HC-2 against the examples in FM DS 3-26 Table 2.2.2 and Appendix C; for standard sprinklers the allowable area per sprinkler drops from 20.9 m² at HC-1 to 12.1 m² at HC-2 (FM DS 2-0 Tables 2.5.2.3.1.1(a) and (b), ceilings up to 9.1 m). The result is several hundred additional sprinklers and a complete rehydraulic. This article summarises the practical content of DS 2-0 (October 2021, Interim Revision April 2025): it speaks the same language as NFPA 13, but sets several critical decisions differently.
FM Approved Components (Section 2.1.4)
The fundamental rule of DS 2-0 Section 2.1.4.1 is to install only new, FM Approved (where available) sprinkler system components, each applied in accordance with its Approval Guide listing (2.1.4.2). Where NFPA 13 accepts listed components, an insurer working to FM can reject products that are not FM Approved at survey, so the procurement list should be restricted to products found in the FM Approval Guide.
- Sprinkler heads: FM Approved for K-factor, response index and temperature rating
- Pipe: black steel or steel resistant to internal oxidation, depending on system type (2.4.1.1.2); nonmetallic pipe only under the conditions of 2.4.1.3
- Joints: threaded, welded or grooved with FM Approved couplings
- Hangers and their fasteners: FM Approved (2.4.3.1.1)
- Valves, alarm valves and dry pipe valves: from the FM Approved list
Hazard Classification
The hazard categories are defined not in DS 2-0 but in FM DS 3-26 (Fire Protection for Nonstorage Occupancies), Table 2.2.2; DS 2-0 states its installation rules in terms of those categories. They are close to, but not identical with, the NFPA light, ordinary and extra hazard classes. Design density and demand area come from DS 3-26 Table 2.3.1.10; the values below are for wet systems under ceilings up to 9 m:
- HC-1: light overall combustible loading with limited combustibles in processes — examples: residential, offices, noncombustible manufacturing, hospitals. Design: 4 mm/min over 140 m² (0.1 gpm/ft² over 1500 ft²).
- HC-2: moderate continuous combustible loading with limited plastics or ignitable liquids — examples: machine shops, woodworking, electronic assembly, retail, theatres, food production. Design: 8 mm/min over 230 m² (0.2 gpm/ft² over 2500 ft²).
- HC-3: generally continuous heavier combustible loading with heavier amounts of plastics — examples: plastic manufacturing, vehicle manufacturing and assembly, printing plants. Design: 12 mm/min over 230 m² (0.3 gpm/ft² over 2500 ft²).
In the same table the demand rises with ceiling height (for example HC-1 under a 9 to 13.5 m ceiling, wet system: 8 mm/min over 230 m²). A minimum design pressure of 0.5 bar applies at the most remote sprinkler (DS 3-26, 2.3.1.11); the hose stream allowance is 950 L/min for HC-1 and HC-2 and 1900 L/min for HC-3 (2.3.1.12); the water supply duration is 60 minutes for all categories (2.3.1.13). Storage hazards are handled separately in DS 8-9, where the design is given as sprinkler K-factor, number of operating sprinklers and pressure rather than density and area.
Sprinkler Spacing and Coverage (Section 2.5.2.3)
- Source: DS 2-0 Tables 2.5.2.3.1.1(a), (b) and (c) for nonstorage pendent and upright sprinklers under unobstructed ceilings; the values below are for ceilings up to 9.1 m
- HC-1, standard sprinklers (K80 and larger): area per sprinkler min 6.0 / max 20.9 m²; linear spacing min 2.1 / max 4.6 m (max 12.1 m² where combustible exposed vertical members are closer than 0.9 m on centres)
- HC-2, standard sprinklers: max 12.1 m²; linear spacing max 4.6 m
- HC-3, standard sprinklers: max 9.3 m²; linear spacing max 3.7 m
- Extended coverage: K14.0EC (K200EC) quick-response sprinklers reach max 37.2 m² and 6.1 m in all three categories (upright only at HC-3); K11.2EC (K160EC) 37.2 m² in HC-1 and 23.8 m² / 4.9 m in HC-2 and HC-3; K25.2EC (K360EC) 18.2 m² / 4.3 m (subject to ceiling type and slope)
- Distance to walls (Fig. 2.5.2.3.2): perpendicular distance greater than 100 mm and less than 50% of the linear spacing; up to 75% of the maximum spacing to wall corners narrower than 90°
Pipe and Hangers (Section 2.4)
- Hazen-Williams C (Table 2.2.1.3.3): wet systems: black steel 120, polymer enhanced 140, plastic 150; dry and preaction systems: black steel 100 (120 with an inert gas such as nitrogen), internally galvanized 120, polymer enhanced 140; vacuum systems: black steel 100 (120 when the conditions of 2.2.1.3.4 are met)
- Hanger spacing (Table 2.4.3.3.1.1): steel pipe thinner than Table 2.4.3.1.1(1): max 3.7 m for DN25–80 (not applicable above DN80); steel pipe at or above that wall thickness: 3.7 m for DN25–32, 4.6 m for DN40 and larger
- Seismic: in FM 50-year to 500-year earthquake zones (DS 1-2) the design follows DS 2-8, Earthquake Protection for Water-Based Fire Protection Systems
- Return bends and armovers: additional support against upward movement, always where branch lines are joined with grooved couplings and, with other joining methods, where the horizontal length exceeds 0.6 m (2.4.3.3.2.7 and 2.4.3.3.2.8)
- Nonmetallic pipe: nonstorage occupancies only; shielded by a fixed 15-minute-rated enclosure or FM Approved specifically as exposed pipe (2.4.1.3.2 to 2.4.1.3.4)
Practical Differences From NFPA 13
| Topic | FM DS 2-0 | NFPA 13 |
|---|---|---|
| Equipment | FM Approved where available (2.1.4.1) | Listed acceptable |
| Hazard classes | HC-1/2/3 (DS 3-26) plus storage (DS 8-9) | LH, OH-1/2, EH-1/2 plus storage |
| Design density and area | A single value per hazard category and ceiling height in DS 3-26 Table 2.3.1.10 | Since the 2022 edition, single-point density/area for new systems; curves only for existing systems |
| Hazen-Williams C (wet, black steel) | 120 (Table 2.2.1.3.3) | NFPA 13 C-value table |
| Nonmetallic pipe | Nonstorage only; shielded, or FM Approved as exposed pipe (2.4.1.3) | Per listing scope |
When FM Applies in Practice
In Turkey, BYKHY Article 96(5) requires sprinkler design to TS EN 12845 and does not reference NFPA 13 or FM data sheets directly. FM becomes the baseline through the insurance relationship, as an added layer that must still meet the regulation's minimum requirements:
- Plants supplying European OEMs in automotive, electronics and chemicals
- Large investors negotiating international insurance premiums
- Facilities inside an FM Global or major international insurer portfolio
- Data centres pursuing certification (Uptime Tier III/IV targets), where FM compliance runs alongside
Quick Checklist
- All components FM Approved
- Hazard class correctly assigned
- Sprinkler coverage and spacing within the table limits
- Hazen-Williams C-value taken from Table 2.2.1.3.3
- Hanger spacing correct for pipe size
- Seismic bracing per DS 2-8 where applicable
- Minimum design pressure achieved at the most remote sprinkler (DS 2-0 Table 2.5.1.1.2; 0.5 bar under DS 3-26)
Frequently Asked Questions
Why does FM require FM Approved equipment rather than listed products?
DS 2-0 2.1.4.1 calls for new, FM Approved (where available) components. FM Approval is a separate testing and certification programme run to FM's own criteria, and the insurer relies on it as evidence that the component performs as assumed in the data sheets. A product listed elsewhere may be perfectly good but has not been evaluated against those criteria, so it can be rejected at survey.
How do FM hazard classes map onto NFPA classes?
They are close but not identical. HC-1 corresponds broadly to light hazard, HC-2 to ordinary hazard and HC-3 to extra hazard, but the boundaries and design values differ and an occupancy can sit in a higher class under FM. The category is assigned from DS 3-26 Table 2.2.2 and Appendix C, which is why the same building can require substantially more sprinklers under FM than under NFPA.
What is the biggest practical difference in design?
Hazard classification and coverage. DS 3-26 Table 2.3.1.10 gives a single density and demand area per hazard category and ceiling height, and the maximum area per standard sprinkler falls from 20.9 m² at HC-1 to 12.1 m² at HC-2 and 9.3 m² at HC-3 (DS 2-0 Tables 2.5.2.3.1.1(a) to (c)). An occupancy placed one class higher under FM therefore often means a denser sprinkler layout and a higher water demand.
Is FM compliance legally required?
No. The Turkish fire regulation (BYKHY, Article 96(5)) requires sprinkler design to TS EN 12845 and does not reference NFPA 13 or FM data sheets. FM becomes binding commercially, through the insurance policy or through a customer's supplier requirements, which means it is a contractual obligation rather than a legal one but no less real.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreFM Global Property Loss Prevention Data Sheet DS 2-0, Installation Guidelines for Automatic Sprinklers, October 2021, Interim Revision April 2025 (2.1.4, 2.2.1.3, Section 2.4, 2.5.2.3); DS 3-26, April 2019, Interim Revision April 2025 (Table 2.2.2, Section 2.3.1); related data sheets DS 8-9 (storage) and DS 2-8 (earthquake protection); NFPA 13 (2025) for comparison; BYKHY.