Pipe and hanger arrangement is covered in FM Global DS 2-0 Section 2.4 (Sprinkler System Piping, pp. 32–42): 2.4.1 pipe, 2.4.2 connections and 2.4.3 hangers and supports. Additional rules for earthquake zones are in DS 2-8. Clause and page numbers in this article refer to DS 2-0, October 2021, Interim Revision April 2025.

Pipe Material and Wall Thickness

Connections (2.4.2)

Hanger Spacing (Table 2.4.3.3.1.1)

Nominal sizeWall thinner than Table 2.4.3.1.1(1)Wall equal to or thicker than Table 2.4.3.1.1(1)
DN25–323.7 m3.7 m
DN40–803.7 m4.6 m
Above DN80Not applicable; use the table wall thickness4.6 m

The threshold wall thicknesses in Table 2.4.3.1.1(1) are 2.7 mm for DN25–50, 2.9 mm for DN65–100, 3.3 mm for DN125–150 and 4.6 mm for DN200–300. Where a pipe has its own listing in the Approval Guide, that listing governs (2.4.3.3.1.1).

Additional Rules in Earthquake Zones (DS 2-8)

DS 2-8 applies in FM 50-year to 500-year earthquake zones as defined in DS 1-2 (DS 2-0 Section 2.1.5). The main additions:

See the DS 2-8 earthquake protection article for details.

Quick Checklist

Frequently Asked Questions

Where can CPVC (nonmetallic) pipe be used?

Under FM DS 2-0 Section 2.4.1.3, nonmetallic pipe is limited to nonstorage occupancies and is normally shielded by a fixed barrier rated at least 15 minutes. Exposed pipe needs a product FM Approved specifically as exposed pipe, an HC-1 occupancy, a ceiling no higher than 9.1 m, a wet system, quick-response ceiling sprinklers and metallic vertical sections. In earthquake zones DS 2-8 does not allow nonmetallic pipe above ground.

Can a DN50 pipe have hangers 4 m apart?

Yes, if the wall is thick enough. Under DS 2-0 Table 2.4.3.3.1.1, DN50 steel pipe with a wall at or above the 2.7 mm value of Table 2.4.3.1.1(1) may have hangers up to 4.6 m apart; thinner pipe is limited to 3.7 m. On mains the spacing can increase by 1.5 m under the conditions of 2.4.3.3.1.3.

Does FM DS 2-0 set a pipe velocity limit?

No. DS 2-0 gives no limit on water velocity in the pipe. Under 2.4.1.1.1.2 each pipe size must be proven by hydraulic calculation to meet the design in the occupancy-specific data sheet; the calculation method is in DS 3-0.

What pipe should be used on a dry system?

DS 2-0 2.4.1.1.2.3 calls for steel pipe resistant to internal oxidation, or black steel where the system is pressurised with a gaseous medium meeting 2.2.1.10, such as nitrogen or air with a regenerative dryer. Internally galvanized pipe is acceptable on dry systems but not on wet systems (2.4.1.1.2.4); see DS 2-1 for corrosion.

Does a vertical drop to a sprinkler need extra support?

Yes. DS 2-0 2.4.3.3.2.3 and 2.4.3.3.2.4 call for additional support on vertical pipe 1.2 m or longer with an upright or pendent sprinkler attached directly. Where a pendent sprinkler is secured to a supported structure such as a suspended ceiling, that length may increase to 3.6 m (2.4.3.3.2.5).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

FM Global Property Loss Prevention Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers, October 2021, Interim Revision April 2025, Section 2.4 (pp. 32–42) and 2.7.3.2.9; DS 2-8, Earthquake Protection for Water-Based Fire Protection Systems, October 2017, Interim Revision April 2025, Section 2.2.1.