Pipe and hanger arrangement is covered in FM Global DS 2-0 Section 2.4 (Sprinkler System Piping, pp. 32–42): 2.4.1 pipe, 2.4.2 connections and 2.4.3 hangers and supports. Additional rules for earthquake zones are in DS 2-8. Clause and page numbers in this article refer to DS 2-0, October 2021, Interim Revision April 2025.
Pipe Material and Wall Thickness
- Minimum size: 1 in. (25 mm) for sprinkler piping; every size chosen must be proven by hydraulic calculation to meet the design in the occupancy-specific data sheet (2.4.1.1.1.1–2.4.1.1.1.2).
- Wet and deluge systems: black steel, or steel pipe resistant to internal oxidation (2.4.1.1.2.2).
- Dry, preaction and other systems: steel pipe resistant to internal oxidation, or black steel where the gaseous medium complies with 2.2.1.10 (an inert gas such as nitrogen, or air with a regenerative dryer) (2.4.1.1.2.3).
- Internally galvanized pipe: not in wet systems, and not where the ambient temperature can exceed 130°F (54°C) unless specifically FM Approved for it (2.4.1.1.2.4). See DS 2-1 for corrosion.
- Water-sensitive occupancies (data centres, museums, semiconductor fabs): minimum wall thickness per Table 2.4.1.1.2.1(b) is 3.2 mm for DN25–40, 3.6 mm for DN50–65, 4.0 mm for DN80, 4.5 mm for DN100 and 5.0 mm for DN125–150.
- Nonmetallic pipe (CPVC etc.): nonstorage occupancies only, shielded by a non-removable barrier rated at least 15 minutes (2.4.1.3.2–2.4.1.3.3). Exposed pipe needs all of the following: pipe FM Approved specifically as exposed pipe, an HC-1 occupancy per DS 3-26, a ceiling no higher than 9.1 m, a wet system, quick-response ceiling sprinklers and metallic vertical sections (2.4.1.3.4). Systems with rigid thermoplastic pipe are tested with water, never pneumatically (2.7.3.2.9).
Connections (2.4.2)
- Two pipe sizes are joined with one-piece FM Approved reducing fittings; connections such as mechanical tees must not project into the flow path (2.4.2.1).
- Minimum wall thickness, Table 2.4.2.2.1(2): welded or roll-grooved pipe 2.6 mm for DN25–65, 2.9 mm for DN80, 3.2 mm for DN100, 4.0 mm for DN150; threaded or cut-grooved pipe 3.2 mm for DN25–40, 3.6 mm for DN50–65, 4.0 mm for DN80, 4.5 mm for DN100, 5.0 mm for DN150. Roll-grooved pipe may go down to 1.7 mm with couplings listed in the Approval Guide for that thickness.
- Threaded: sealant on the male threads only, without preventing full thread engagement (2.4.2.2.2.2).
- Grooved: groove dimensions to the coupling manufacturer’s requirements; roll grooves formed before galvanizing or painting (2.4.2.2.3).
- Welded: FM Approved welded connections; welder qualification to ANSI/AWS B2.1 or EN ISO 9606-1; removal of all cut coupons documented (2.4.2.2.4).
- Plain-end connections: pipe thinner than 0.133 in. (3.38 mm) must be FM Approved pipe specifically listed with FM Approved plain-end connections (2.4.2.3.1).
Hanger Spacing (Table 2.4.3.3.1.1)
| Nominal size | Wall thinner than Table 2.4.3.1.1(1) | Wall equal to or thicker than Table 2.4.3.1.1(1) |
|---|---|---|
| DN25–32 | 3.7 m | 3.7 m |
| DN40–80 | 3.7 m | 4.6 m |
| Above DN80 | Not applicable; use the table wall thickness | 4.6 m |
The threshold wall thicknesses in Table 2.4.3.1.1(1) are 2.7 mm for DN25–50, 2.9 mm for DN65–100, 3.3 mm for DN125–150 and 4.6 mm for DN200–300. Where a pipe has its own listing in the Approval Guide, that listing governs (2.4.3.3.1.1).
- Every section of pipe longer than 1.8 m has at least one hanger (2.4.3.3.1.2).
- Main hangers within 0.9 m of the last branch line and within 0.6 m of any connection to vertical pipe (2.4.3.3.1.4–2.4.3.3.1.5).
- Branch line hangers: within 0.3 m of the main where the main hanger is more than 1.8 m from the branch connection; within 0.3 m of a horizontal change of direction; 0.3–0.9 m from the last sprinkler on single-path lines (2.4.3.3.1.6–2.4.3.3.1.8).
- Main hanger spacing may increase by 1.5 m when branch line hangers meet 2.4.3.3.1.3; for DN65 and larger, up to 8 m with paired hangers no more than 0.9 m apart either side of the coupling (2.4.3.3.1.9).
- Hangers at least 75 mm horizontally from upright sprinklers in nonstorage occupancies and at least 300 mm in storage (2.4.3.3.1.11).
- Vertical pipe supported at least every 3.6 m; additional support for vertical pipe 1.2 m or longer with an upright or pendent sprinkler attached directly (2.4.3.3.2.2–2.4.3.3.2.4).
- Minimum rod diameter (Table 2.4.3.1.3): 10 mm for DN25–100, 12 mm for DN125–200, 16 mm for DN250–300.
- No hangers attached directly to roof decking; attachment to steel deck is limited to branch lines up to DN80 under the conditions of 2.4.3.2.2.2. Supporting members must carry the hanger loads plus a single additional 250 lb (113 kg) point load at the most critical hanger (2.4.3.2.1.2).
- Nothing, including conduit, cable trays, air piping, speakers or signs, is hung from sprinkler pipe (2.4.1.1.5.4).
Additional Rules in Earthquake Zones (DS 2-8)
DS 2-8 applies in FM 50-year to 500-year earthquake zones as defined in DS 1-2 (DS 2-0 Section 2.1.5). The main additions:
- A four-way brace within 0.6 m of the top of every riser (2.2.1.1.2.1).
- Feed and cross mains are braced regardless of size: on straight runs, lateral braces at no more than 12.2 m and longitudinal braces at no more than 24.4 m (2.2.1.1.4.4).
- Lateral bracing on branch lines is needed from DN65 upwards (2.2.1.1.5.1); smaller dead-end branch lines get a short hanger or lateral restraint within 1.8 m of the end (2.2.1.1.6).
- Diagonal brace members on horizontal pipe at least 30° from vertical, preferably at least 45° (2.2.1.3.5.2).
- No powder-driven fasteners for hangers (2.2.1.8.1.1); no two-piece plain-end couplings without torque indication (2.2.1.7.2); no nonmetallic pipe above ground (2.2.1.9.2).
See the DS 2-8 earthquake protection article for details.
Quick Checklist
- Pipe type suits the system type; no internally galvanized pipe on wet systems
- Wall thickness checked against Table 2.4.2.2.1(2) for the joining method
- Nonmetallic pipe only in nonstorage areas and under the conditions of 2.4.1.3
- Hanger spacing from Table 2.4.3.3.1.1 and the wall thickness threshold
- Hanger distances at the last branch line, vertical connections and last sprinkler met
- In earthquake zones, DS 2-8 bracing, flexibility and clearances applied
Frequently Asked Questions
Where can CPVC (nonmetallic) pipe be used?
Under FM DS 2-0 Section 2.4.1.3, nonmetallic pipe is limited to nonstorage occupancies and is normally shielded by a fixed barrier rated at least 15 minutes. Exposed pipe needs a product FM Approved specifically as exposed pipe, an HC-1 occupancy, a ceiling no higher than 9.1 m, a wet system, quick-response ceiling sprinklers and metallic vertical sections. In earthquake zones DS 2-8 does not allow nonmetallic pipe above ground.
Can a DN50 pipe have hangers 4 m apart?
Yes, if the wall is thick enough. Under DS 2-0 Table 2.4.3.3.1.1, DN50 steel pipe with a wall at or above the 2.7 mm value of Table 2.4.3.1.1(1) may have hangers up to 4.6 m apart; thinner pipe is limited to 3.7 m. On mains the spacing can increase by 1.5 m under the conditions of 2.4.3.3.1.3.
Does FM DS 2-0 set a pipe velocity limit?
No. DS 2-0 gives no limit on water velocity in the pipe. Under 2.4.1.1.1.2 each pipe size must be proven by hydraulic calculation to meet the design in the occupancy-specific data sheet; the calculation method is in DS 3-0.
What pipe should be used on a dry system?
DS 2-0 2.4.1.1.2.3 calls for steel pipe resistant to internal oxidation, or black steel where the system is pressurised with a gaseous medium meeting 2.2.1.10, such as nitrogen or air with a regenerative dryer. Internally galvanized pipe is acceptable on dry systems but not on wet systems (2.4.1.1.2.4); see DS 2-1 for corrosion.
Does a vertical drop to a sprinkler need extra support?
Yes. DS 2-0 2.4.3.3.2.3 and 2.4.3.3.2.4 call for additional support on vertical pipe 1.2 m or longer with an upright or pendent sprinkler attached directly. Where a pendent sprinkler is secured to a supported structure such as a suspended ceiling, that length may increase to 3.6 m (2.4.3.3.2.5).

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreFM Global Property Loss Prevention Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers, October 2021, Interim Revision April 2025, Section 2.4 (pp. 32–42) and 2.7.3.2.9; DS 2-8, Earthquake Protection for Water-Based Fire Protection Systems, October 2017, Interim Revision April 2025, Section 2.2.1.