A mini-load ASRS is a horizontal-loading automated store in which a picking robot in the aisle places and retrieves small containers and trays. FM Global DS 8-34 (July 2017, interim revision April 2026) treats mini-load separately from shuttle systems: closed-top noncombustible containers are covered in Section 2.2.5, closed-top combustible containers and trays in 2.2.6, and open-top combustible containers in 2.2.7. For the rules that apply to every ASRS type, see the DS 8-34 overview.

Mini-Load Rack Configuration

When Is Ceiling-Only Protection Possible?

In-Rack Sprinkler Arrangement

Open-Top vs Closed-Top Containers

Quick Checklist

Frequently Asked Questions

Is ceiling-only protection enough for a mini-load ASRS?

It depends on the container. For closed-top combustible containers or trays it is enough where the flue spaces are adequate, aisles are at least 1.1 m wide (1.2 m where the ceiling exceeds 9.1 m or uncartoned expanded plastics are stored), uncartoned plastics are not stored directly on the rails, and Tables 2.2.6.1.2(a) to 2.2.6.1.2(d) offer an option (DS 8-34 2.2.6.1.1). With open-top combustible containers, ceiling-only protection is possible only where storage does not exceed 3.0 m (2.2.7.1.1).

How does a mini-load ASRS differ from a shuttle ASRS?

The difference is the rack support. In a mini-load rack the containers sit on angle irons that divert sprinkler discharge to the rack face, whereas in a shuttle system they rest on slatted or mesh shelving and water can reach the flue spaces (DS 8-34 3.1.1, Appendix A). That is why the two types use separate tables; height or load weight is not the distinguishing criterion.

How far apart vertically are the in-rack sprinkler levels?

For closed-top combustible containers or trays on a wet system, Table 2.2.6.2.2.1(a) allows a maximum of 3.0 m (minimum K11.2 at 230 L/min) or 4.6 m (minimum K14.0 at 380 L/min), with no more than 3.0 m of storage above the top in-rack level. For open-top containers, Table 2.2.7.2.2.1(a) allows a maximum of 3.0 m (minimum K11.2 at 380 L/min) or, for some wet arrangements, 4.6 m (minimum K22.4 at 530 L/min).

What does the mini-load robot do when a fire is detected?

DS 8-34 calls for an FM Approved ceiling-level fire detection system over horizontal-loading ASRS. On activation it must send an alarm to a constantly attended location and automatically shut down the robots (2.2.1.7.3). This detection is not needed where closed-top noncombustible containers are used throughout the array (2.2.1.7.4).

How are plastic containers classified?

DS 8-34 requires the design to be based on the more severe of the stored product and the container or tray material (2.1.3.1.3). Classification follows DS 8-1, and FM does not use the NFPA Group A/B/C plastics groupings. Unexpanded plastic containers are within scope; expanded plastic containers and trays are outside the scope of DS 8-34 (1.0).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

FM Global DS 8-34, Protection for Automatic Storage and Retrieval Systems (July 2017, interim revision April 2026): Sections 2.1.2.5, 2.2.1, 2.2.5–2.2.7, 3.1.1, Appendix A; Tables 2.2.6.1.2–2.2.7.2.3.2. Related: DS 8-1 (commodity classification).