Storage protection is the largest part of NFPA 13 and the one where most mistakes are made. The reason is simple: in a warehouse the fire load is set by operations, not by the architectural drawings. Chapter 20 of NFPA 13-2025 (general requirements for storage) defines the questions every warehouse design must answer first, whichever protection option follows (density/area, CMSA, ESFR or in-rack).
What this part of the standard covers
The general requirements standardise the input data for storage design. You cannot enter any protection table until you have answered six questions:
- What is stored? Commodity class and packaging.
- How is it stored? Palletised, solid-piled, racks, shelving, bin boxes.
- How high? Maximum storage height.
- Where is the ceiling? Highest ceiling point and roof slope.
- How much space in between? Clearance from deflector to top of storage.
- How does water get down? Rack flue spaces, aisle widths, horizontal barriers.
Commodity classification
NFPA 13 classifies stored goods by how they burn (20.3, 20.4). Classification is based on the individual storage unit, taking the product, its primary packaging and the pallet together:
| Class | General description | Example |
|---|---|---|
| Class I | Non-combustible product placed directly on wooden pallets, in single-layer corrugated cartons, or shrink- or paper-wrapped as a unit load | Metal parts, drinks in glass bottles |
| Class II | Non-combustible product in slatted wooden crates, solid wooden boxes or multi-layer corrugated cartons | Crated machine parts |
| Class III | Products of wood, paper, natural fibre or Group C plastics; may contain up to 5% by weight unexpanded or 5% by volume expanded Group A plastic | Paper products, wooden furniture |
| Class IV | Products partly or wholly of Group B plastics, free-flowing Group A plastics, or cartoned products with 5–15% by weight unexpanded or 5–25% by volume expanded Group A plastic | Small appliances with plastic parts |
| Group A plastics | Highest heat release plastics; split into cartoned/exposed and expanded/unexpanded (nylon and natural rubber are also Group A, 20.4.5.1) | Polystyrene foam, PE/PP products |
Group B plastics and free-flowing Group A plastics are protected as Class IV, and Group C plastics as Class III (20.4.8). Special commodities such as rubber tyres, roll paper and baled cotton have their own rules. For the logic behind classification see commodity classification in NFPA 13.
Pallets and mixed commodities
Pallets are fuel too. Classification assumes wooden or metal pallets, or pallets listed as equivalent to wood (20.3.2.1). For Class I–IV commodities, unreinforced polypropylene or high-density polyethylene pallets raise the class by one, and reinforced plastic pallets by two (Class IV becomes cartoned unexpanded Group A plastic); unmarked pallets are assumed to be reinforced (20.3.2.2). There is no increase for Group A plastic commodities, nor for ceiling-only protection with spray sprinklers of at least K16.8 (K240) (20.3.2.2.3, 20.3.2.2.4).
Mixed storage is protected for the highest classified commodity and storage arrangement (20.4.15.2). Designing for the lower class is allowed in only two cases: up to 10 pallet loads of the higher hazard (five for Class IV or Group A where the ceiling design is for Class I–II) randomly dispersed with no adjacent loads in any direction within an area of up to 3,720 m² (20.4.15.3), or the higher hazard confined to a designated area protected for that hazard (20.4.15.4).
Storage arrangement and geometry
The same commodity behaves very differently in different arrangements. In solid piles the fire travels over the outer faces; in racks the flue spaces act as chimneys and the fire spreads vertically very quickly. That is why the tables are split by arrangement.
| Parameter | Criterion / note (NFPA 13-2025) |
|---|---|
| Deflector to top of storage (general) | At least 450 mm (18 in) (20.9.6.1); 900 mm for rubber tyres (20.9.6.4) |
| Deflector to top of storage (CMSA and ESFR) | At least 900 mm (36 in) (20.9.6.5) |
| Longitudinal flue in double-row open racks | Not required up to 7.6 m (25 ft) storage; nominal 150 mm (6 in) above that (20.6.2.1) |
| Transverse flue spaces | Nominal 150 mm (6 in) between loads and at rack uprights (20.6.2.2) |
| Aisle width | Affects design density in some tables |
| Miscellaneous storage | Up to 3.7 m (12 ft) high, no more than 10% of the building area or 370 m² (whichever is greater), 93 m² per pile, 7.6 m from other storage; protected under Chapter 4 criteria (4.3.1.4, 4.3.1.7) |
Flue spaces are vital, especially in racks protected by ceiling sprinklers only: they let water run down into the rack and let heat reach the sprinklers. Pallets pushed back until they close the flues defeat this function.
Heights: storage and ceiling
Storage tables have two axes: storage height and ceiling (building) height. Higher storage means a bigger fire; a higher ceiling means later sprinkler operation and a harder journey for the drops. As the gap grows, protection gets harder, which is why many tables limit ceiling height as well as storage height. The design is based on the storage height that routinely or periodically exists and creates the greatest water demand (20.9.3.1); building height is measured to the underside of the roof deck or ceiling in the storage area (20.9.2.1). The Chapter 20–26 criteria essentially assume ceiling slopes not exceeding 2 in 12 (16.7%); steeper ceilings need one of the options in 20.9.1.1.
Special cases
- Idle pallets: empty wooden and especially plastic pallets are a very high fire load with their own tables (20.17). High-piled idle plastic pallets indoors exceed the limits of most protection options.
- Encapsulation: plastic sheeting over the top and sides of a pallet load stops water reaching the product; the CMDA tables give separate values for encapsulated storage; in multiple-row racks, for example, the ceiling density for Class I–III goes up by 25% (21.4.1.5.1).
- Dry systems: storage systems must be wet pipe (20.16.2.1). Dry pipe and preaction systems are permitted where there is a risk of freezing or similar special conditions; with CMDA criteria the design area is then increased by 30% without changing the density (20.16.3). ESFR needs a wet system unless specifically listed for dry or preaction use (14.2.2).
- Solid shelving: shelves less than 50% open and larger than 1.9 m² (20 ft²) count as solid shelves (20.5.3.1.1); they cut off ceiling sprinkler discharge and require in-rack sprinklers under Section 25.3.
Choosing the protection option
Once the input data is fixed, the options are compared: density/area (CMDA), CMSA, ESFR and, where needed, in-rack sprinklers. Water demand, roof construction, operational flexibility and ease of maintenance are weighed together. The ESFR suitability checker gives a quick view on ESFR, and the fire water tank sizing calculator helps with volume.
Defects to check
- The actual commodity differs from the design commodity (particularly more plastic packaging).
- Storage height rises above the design and clearance disappears.
- Flue spaces closed up.
- Temporary solid piles in aisles.
- Idle pallets stacked between racks or against walls.
- Sheet metal or boards laid on rack levels after handover.
Handover note: put the design assumptions (commodity class, maximum storage height, rack arrangement, flue spaces) in writing on the system information sign and in the warehouse operating procedure. The weakest link in storage protection is a shift manager who does not know them. For field observations see warehouse protection field findings.
Frequently Asked Questions
At what height do the NFPA 13 storage rules apply?
Storage of Class I–IV commodities above 3.7 m (12 ft) and Group A plastics above 1.5 m (5 ft) is protected under Chapters 20–25. Low-piled storage within those heights, and miscellaneous storage meeting its conditions, is protected under the Chapter 4 criteria (4.3.1.4, 4.3.1.5, 20.1.1).
How much clearance is needed between deflector and storage?
The general rule is at least 450 mm (20.9.6.1); at least 900 mm for CMSA and ESFR sprinklers (20.9.6.5) and 900 mm for rubber tyre storage (20.9.6.4). The clearance lets the sprinkler's spray pattern develop.
Do plastic pallets change the commodity class?
Yes. For Class I–IV commodities, unreinforced PP/HDPE pallets raise the class by one and reinforced plastic pallets by two (20.3.2.2). There is no increase for pallets listed as equivalent to wood, for Group A plastics, or for ceiling-only protection with spray sprinklers of at least K16.8 (K240).
How is mixed commodity storage designed?
For the highest classified commodity and storage arrangement (20.4.15.2). Designing for the lower class is only possible for small dispersed quantities (up to 10 pallet loads in 3,720 m², 20.4.15.3) or where the higher hazard is confined to a designated area protected for that hazard (20.4.15.4).
Why do flue spaces matter?
They let ceiling sprinkler water run down into the rack and let heat reach the sprinklers. In NFPA 13-2025 transverse flue spaces are nominally 150 mm (20.6.2.2). Closing them seriously weakens protection in racks protected only at ceiling level.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreNFPA 13 (2025 edition) – Chapter 20 (general requirements for storage, commodity classification), Chapter 4 (miscellaneous and low-piled storage). Confirm against the edition in force and the authority having jurisdiction for each project. The findings here are typical defect patterns, not an account of events at any particular site.