Beyond a certain point ceiling sprinklers cannot reach a fire inside a rack: the storage is too high, shelves block the water, or the commodity burns too fast. In-rack sprinklers then take water to where the fire is, inside the rack structure. Chapter 25 of NFPA 13-2025 (protection of rack storage using in-rack sprinklers) sets out when these sprinklers are needed, where they go and how they work together with the ceiling system.

What this part of the standard covers

  • When in-rack sprinklers are required, and the options available
  • Sprinkler type, K-factor, temperature rating and response
  • Vertical levels and horizontal locations (flue spaces, rack face)
  • Water shields and mechanical protection
  • Hydraulically combining in-rack and ceiling demand
  • Control valves, drains and maintenance access

When are in-rack sprinklers required?

In-rack sprinklers are not "extra safety"; usually they are mandatory because ceiling protection alone falls short. Typical triggers:

SituationWhy ceiling protection is not enough
Storage height beyond ceiling-only tablesCeiling water does not reach lower levels at adequate density
Solid shelving larger than 1.9 m² (20 ft²) (20.5.3.1.1, 25.3)Each shelf acts as an umbrella
Commodity/rack combinations with no ceiling-only optionNo test data exists
Building ceiling above ESFR/CMSA limitsCeiling sprinklers operate too late

Open-top containers are a separate case: containers that collect water fall entirely outside the rack storage criteria of Chapters 21–25 (20.3.3), so adding in-rack sprinklers is not in itself a recognised solution and a special evaluation is needed.

When you meet these situations, the first question is whether the storage can change: open-grating shelves or a lower storage height sometimes remove the need for in-rack sprinklers entirely. For how storage inputs are defined, see general requirements for storage.

Sprinkler selection

Unless stated otherwise, in-rack sprinklers are pendent or upright, standard- or quick-response, ordinary temperature and at least nominal K5.6 (K80) (25.1.6.1); intermediate and high temperature ratings are used near heat sources (25.1.6.2). In-rack sprinklers may have a different RTI from the ceiling sprinklers above them (25.1.6.3). The design pressure at the most remote in-rack sprinkler must be at least 0.5 bar (7 psi) (25.1.10.1), and most option figures also specify a flow per sprinkler of 83 L/min (22 gpm) or 114 L/min (30 gpm) and the number of sprinklers to calculate. A K5.6 (K80) at 83 L/min needs (83/80)² ≈ 1.08 bar. The sprinkler temperature rating selector helps with rating choice.

Placement: levels and flue spaces

In-rack effectiveness depends on location. The core principles:

  • In flue spaces: an in-rack sprinkler placed in a longitudinal flue must sit at an intersection with a transverse flue, within the maximum horizontal spacing (25.1.7.3), the natural path for water and heat. In single-row racks it may be anywhere in the transverse flue between load faces (25.1.7.9.1). Sprinklers stay at least 75 mm from the side of rack uprights (25.1.7.7).
  • Vertical clear space: at least 150 mm (6 in) between the deflector and the top of the storage below (25.1.8.3.1); less is permitted for Class I–IV in single- and double-row racks up to 6.1 m (25.1.8.3.2).
  • Levels: the number of levels and vertical spacing come from the applicable figures. Where no location is shown, one level goes at the first tier at or above half the highest expected storage height, and two levels at the first tiers at or above one third and two thirds (25.1.8.1, 25.1.8.2).
  • Face sprinklers: some commodities and rack arrangements need sprinklers at the rack face as well as in the flue; they sit at least 75 mm from uprights and no more than 450 mm in from the aisle face of storage (25.1.7.8).
  • Horizontal spacing: spacing along the rack is limited by the applicable figure and protection option and must be coordinated with bay dimensions. Where a higher-hazard commodity occupies only part of a rack, in-rack sprinklers extend at least 2.4 m or one bay, whichever is greater, on each side (25.1.7.6.1).

Water shields

So that water from above does not cool it and delay operation, every in-rack sprinkler not shielded by a horizontal barrier needs a water shield above it, or a listed intermediate level/rack storage sprinkler must be used (25.1.6.4).

Mechanical protection

The forklift is the in-rack sprinkler's worst enemy. Sprinklers and pipe must stay within the protection of the rack members and never project into the aisle. Listed guards are used where needed.

Horizontal barriers

For some high-challenge commodities and tall racks, in-rack sprinklers are used together with horizontal barriers at rack levels. Barriers are made of sheet metal, wood or similar material, run the full length and depth of the rack and fit within 75 mm around rack uprights (25.1.9.1, 25.1.9.2). The barrier keeps heat within a limited vertical zone so the in-rack sprinklers beneath it open quickly, and it delays fire jumping above it. In barrier designs the barrier material, gaps and sprinkler positions are interdependent; removing or cutting barriers in operation invalidates the design.

Hydraulics: ceiling and in-rack together

In-rack demand is not independent of ceiling demand. In a fire both systems operate at once, so ceiling and in-rack demands over the same protected area are balanced hydraulically to the higher pressure at their point of connection (25.1.10.5). Typical steps:

  1. Set the ceiling design area and density (from tables that change when in-rack sprinklers are present).
  2. Set the number and layout of in-rack design sprinklers (the most demanding level and zone).
  3. Balance both demands at the supply point, adjusting the flow of the lower-pressure side to the higher pressure.
  4. Add the hose allowance from Table 20.15.2.6 to the total and apply the duration (25.1.13).

For the general method see the sprinkler hydraulic calculation guide.

Valves and maintenance

Because in-rack sprinklers are damaged often, it helps to be able to repair them without shutting the ceiling system. So separate indicating control valves and drains are required, arranged so that the ceiling and in-rack systems can be controlled independently (25.1.4.2.1). Exceptions: no separate valve is needed where 20 or fewer in-rack sprinklers are supplied by any one ceiling system (25.1.4.2.2), and the valves may be sectional control valves fed from the ceiling system where the racks and adjacent aisles occupy 745 m² or less of the ceiling-protected area (25.1.4.2.3). One in-rack system may protect no more than 3,720 m² of rack floor area including aisles (25.1.4.1). The valve should be outside forklift traffic and easy to reach. Routine inspection must check in-rack sprinklers for damage, paint, dust and contact with loads; see visual inspection of sprinklers.

Common site mistakes

  1. Rack layout changes (bay width, beam levels) without moving the in-rack sprinklers.
  2. Loads touching the sprinklers; the 150 mm vertical clear space lost.
  3. Standard sprinklers used where a water shield is needed.
  4. Pipe bent and sprinklers broken by forklifts, left unrepaired for long periods.
  5. In-rack valve left closed, with no supervision.
  6. Ceiling design based on the reduced table that assumes in-rack sprinklers, which are later removed.

Design tip: design in-rack pipework on the rack supplier's final drawings. In-rack systems drawn on estimated bay sizes nearly always get redesigned during installation. For a comparison of in-rack and ESFR options in high-bay stores see rack storage in-rack sprinkler design.

Frequently Asked Questions

When are in-rack sprinklers mandatory?

When storage height, commodity or rack arrangement falls outside the ceiling-only tables, and with solid shelves larger than 1.9 m² (20.5.3.1.1, 25.3). Open-top containers fall entirely outside the Chapter 21–25 criteria (20.3.3) and need a special evaluation.

Why do in-rack sprinklers need water shields?

Water from sprinklers above can cool the heat-responsive element of a lower sprinkler and delay it. So in-rack sprinklers not shielded by horizontal barriers must have a water shield or be listed intermediate level sprinklers (25.1.6.4).

How are in-rack and ceiling demands combined?

Each demand is calculated separately and the two are balanced to the higher pressure at their point of connection (25.1.10.5). The hose allowance from Table 20.15.2.6 is added to the total flow and the duration applied (25.1.13).

Can in-rack sprinklers be combined with ESFR?

Yes, it is a defined option: Section 25.6 covers in-rack sprinklers in combination with ESFR ceiling sprinklers. Even so, the aim of most ESFR designs is to avoid in-rack sprinklers; confirm the option and product listing for each project.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025 edition) – Chapter 25 (rack storage protection using in-rack sprinklers), Chapter 20 (general storage requirements); NFPA 25 – inspection of in-rack sprinklers. Confirm against the edition in force and the authority having jurisdiction for each project. The findings here are typical defect patterns, not an account of events at any particular site.