This article in the NFPA 25 series covers Chapter 6: standpipe and hose systems. After the fire pump and sprinkler system articles, this one deals with the standpipes themselves as installed to NFPA 14: hose, hose nozzles, hose storage devices, cabinets, piping and hangers, the hydraulic design information sign, the 5-year flow test and hydrostatic test, and what to do when a component changes. Common components such as valves, hose valves, pressure-reducing valves, gauges and alarm devices are sent to Chapter 13; they are covered in the valves and common components article. The underground mains and hydrants that feed the building are the subject of the Chapter 7 article. Every line carries its clause number from NFPA 25-2026.

In short: Hose, hose storage devices, cabinets, piping, hangers and the hydraulic design sign are inspected annually; hose nozzles annually and after each use (6.2, Table 6.1.1.2). Automatic standpipes get a flow test every 5 years: for Class I and Class III, 500 gpm (1892 L/min) at the most remote standpipe plus 250 gpm (946 L/min) for each additional standpipe, flowing simultaneously (6.3.1.1, 6.3.1.2). Manual standpipes and semiautomatic dry standpipes get a hydrostatic test of at least 200 psi (13.8 bar) for 2 hours every 5 years (6.3.2.1). Where water damage is a possibility, a 25 psi (1.7 bar) air test comes before water is introduced (6.3).

A. Scope and general rules

Chapter 6 gives the minimum requirements for routine inspection, testing and maintenance of standpipe and hose systems installed to NFPA 14 or another approved installation standard (6.1.1.1). Minimum frequencies come from Table 6.1.1.2 (6.1.1.2). All required activities are carried out to determine that components are free of corrosion, foreign material, physical damage, tampering or other conditions that adversely affect system operation (6.1.2).

CheckCriterionClause
☐ Common components and valvesInspected, tested and maintained per Chapter 136.1.3
☐ Obstruction investigation neededFollow the procedures of Chapter 146.1.4
☐ ITM results in or involves a system out of serviceFollow the impairment procedures of Chapter 156.1.5
☐ Removal of existing hoseWhere approved by the AHJ, existing hose may be removed and is not recorded as a deficiency6.1.6

B. Frequency summary: Table 6.1.1.2

The standard’s summary table is reproduced below. Rows marked "—" have no frequency of their own in the table; the frequency and method come from the reference in the right-hand column (mostly Chapter 13, and NFPA 1930 for hose testing).

ItemFrequencyReference
Inspection
CabinetAnnually6.2.9
Control valves—Chapter 13
Gauges—Chapter 13
HoseAnnually6.2.6
Hose nozzleAnnually and after each use6.2.7
Hose storage deviceAnnually6.2.8
Hydraulic design information signAnnually6.2.2
Hose valves and hose connections—Chapter 13
PipingAnnually6.2.4
Pressure-regulating devices—Chapter 13
Supervisory devices (except valve supervisory devices)—Chapter 13
Valve supervisory devices—Chapter 13
Test
Control valves—Chapter 13
System valves—Chapter 13
Flow test5 years6.3.1
Hose—NFPA 1930
Hose connection pressure-regulating devices—Chapter 13
Hose valves—Chapter 13
Hydrostatic test (manual and semiautomatic dry standpipes)5 years6.3.2
Main drain test—Chapter 13
Pressure-reducing valve—Chapter 13
Master pressure-reducing valve—Chapter 13
Supervisory signal devices (except valve supervisory switches)—Chapter 13
Valve status test—Chapter 13
Valve supervisory devices—Chapter 13
Waterflow alarm devices—Chapter 13
Maintenance
Hose valves—Chapter 13
Pressure gauges—Chapter 13
Valves (all types)Annually/as neededChapter 13

C. Annual inspection: components and the hydraulic design sign

Components of standpipe and hose systems are visually inspected annually or as specified in Table 6.1.1.2 (6.2.1).

CheckCriterionClause
☐ Hydraulic design information signAnnually: provided, attached securely and legible6.2.2
☐ Missing or illegible hydraulic design signReplaced6.2.2.1
☐ Standpipe system not sized by hydraulic designThe hydraulic design sign reads “Pipe Schedule System”6.2.2.2
☐ Deficiency at hose connectionsAppropriate corrective action taken6.2.3.1

The Annex A.6.2.2 explanation recommends securing the sign with durable wire, chain or equivalent to the water supply control valve for automatic or semiautomatic standpipe systems, and at an approved location for manual systems. The sample sign in the same explanation (Figure A.6.2.2) lists: the location of the two hydraulically most remote hose connections; the design flow rate for those connections; the design residual inlet and outlet pressures for those connections; and the design static pressure and design system demand (flow and residual pressure) at the system control valve, or at the pump discharge flange where a pump is installed, and at each fire department connection.

D. Pipe, fittings, hangers and supports

CheckCriterionClause
☐ Pipe and fittingsInspected annually from the floor level6.2.4.1
☐ Use of pipingNot used to support nonsystem components6.2.4.2
☐ Pipe and fittings in concealed spaces such as above suspended ceilingsNo inspection required6.2.4.3
☐ Pipe and fittings in areas inaccessible for safety reasons due to process operationsInspected during each scheduled shutdown6.2.4.4
☐ Pipe hangers, braces and supportsInspected annually from the floor level6.2.5
☐ Condition of hangers, braces and supportsNot damaged, loose or unattached6.2.5.1
☐ Damaged, loose or unattached hangers and supportsReplaced or refastened6.2.5.2
☐ Hangers, braces and supports in concealed spacesNo inspection required6.2.5.3
☐ Hangers, braces and supports in areas inaccessible due to process operationsInspected during each scheduled shutdown6.2.5.4

Per the Annex A.6.2.4.1 explanation, surface corrosion that does not affect pipe strength or raise concern of leakage should not by itself warrant pipe replacement; judgment is applied in deciding how much corrosion calls for replacement. Annex A.6.2.4.3 and A.6.2.5.3 list some floor/ceiling and roof/ceiling assemblies, areas under theater stages and pipe chases as further examples of concealed spaces.

E. Hose, hose nozzle and hose storage device

Hose is inspected annually, as required by NFPA 1930, for the following conditions (6.2.6.1); where any deficiency is noted, appropriate corrective action is taken (6.2.6.2):

CheckCriterionClause
☐ Mildew, cuts, abrasions and deteriorationNone6.2.6.1(1)
☐ Couplings and hose threadsNot damaged6.2.6.1(2)
☐ GasketsNot missing or deteriorated6.2.6.1(3)
☐ Coupling threadsNo incompatible threads6.2.6.1(4)
☐ Hose connectionConnected to the hose rack nipple or valve6.2.6.1(5)

Hose nozzles are inspected annually for the following conditions (6.2.7.1); Table 6.1.1.2 also calls for nozzle inspection after each use. Where any deficiency is noted, appropriate corrective action is taken (6.2.7.2).

CheckCriterionClause
☐ Hose nozzlePresent, not missing6.2.7.1(1)
☐ Nozzle gasketNot missing or deteriorated6.2.7.1(2)
☐ Nozzle boreNo obstructions6.2.7.1(3)
☐ Nozzle operationOperates smoothly6.2.7.1(4)

Hose storage devices (racks, reels) are inspected annually for the following conditions (6.2.8.1); where any deficiency is noted, appropriate corrective action is taken (6.2.8.2):

CheckCriterionClause
☐ Ease of operationNot difficult to operate6.2.8.1(1)
☐ Physical conditionNot damaged6.2.8.1(2)
☐ AccessNo visible or physical obstruction6.2.8.1(3)
☐ Hose stowageProperly racked or rolled6.2.8.1(4)
☐ Nozzle clipIn place, nozzle correctly contained6.2.8.1(5)
☐ Hose rack enclosed in a cabinetSwings out at least 90 degrees6.2.8.1(6)

F. Cabinet

Cabinets are inspected annually for the following conditions (6.2.9.1); where any deficiency is noted, appropriate corrective action is taken (6.2.9.2):

CheckCriterionClause
☐ Overall conditionNo corroded or damaged parts6.2.9.1(1)
☐ OpeningNot difficult to open6.2.9.1(2)
☐ Cabinet doorOpens fully6.2.9.1(3)
☐ Door glazingNot cracked or broken6.2.9.1(4)
☐ Lock on break glass–type cabinetFunctions properly6.2.9.1(5)
☐ Glass break devicePresent and attached6.2.9.1(6)
☐ IdentificationProperly identified as containing fire equipment6.2.9.1(7)
☐ AccessNo visible or physical obstructions6.2.9.1(8)
☐ ContentsAll valves, hose, nozzles, fire extinguishers, etc. easily accessible6.2.9.1(9)

G. Air test before water, and the 5-year flow test

Where water damage is a possibility, an air test at 25 psi (1.7 bar) is conducted on the system before water is introduced (6.3). A flow test is conducted every 5 years on all automatic standpipe systems to verify that the required flow and pressure are available at the hydraulically most remote hose valve outlet(s) while flowing the standpipe system demand (6.3.1.1).

CheckCriterionClause
☐ Class I and Class III system demand500 gpm (1892 L/min) for the most remote standpipe and 250 gpm (946 L/min) for each additional standpipe until the total system demand is flowing simultaneously6.3.1.2
☐ Horizontal standpipe on a Class I or Class III system supplying three or more hose connections750 gpm (2840 L/min) for the most remote standpipe and 250 gpm (946 L/min) for each additional standpipe until the total system demand is flowing simultaneously6.3.1.2.1
☐ The 250 gpm (946 L/min) from each additional Class I and Class III standpipeMay be flowed from the most convenient hose valve on that standpipe6.3.1.2.2
☐ 250 gpm (946 L/min) cannot be flowed from each additional standpipeThe AHJ determines where the additional flow can be taken6.3.1.2.3
☐ Class II system demand100 gpm (379 L/min) for the most remote standpipe connection6.3.1.3
☐ Basis of the demandDesign criteria in effect at the time of installation6.3.1.4
☐ Demand cannot be determinedThe AHJ determines the demand6.3.1.4.1
☐ Test method and performance criteriaDiscussed in advance with the AHJ6.3.1.4.2
☐ Flow test at the most remote outlet(s) not practicalThe AHJ is consulted for the appropriate test location6.3.1.1.1
☐ Test gaugesGauges maintained in accordance with 8.3.3.5.2 are provided6.3.1.1.2
☐ Standpipes, sprinkler connections to standpipes and hose stations with pressure-reducing or pressure-regulating valvesThese valves inspected, tested and maintained per Chapter 136.3.1.5

The Annex A explanations add practical notes. The hydraulically most remote hose connections in a building are generally at a roof manifold, if provided, or at the top of a stair leading to the roof; in a multizone system the testing means is generally a test header at grade or a suction tank on higher floors (Annex A.6.3.1.1). Section 6.3.1.2.1 is not intended to flow test both vertical and horizontal standpipes in the same building, only the more demanding of the two, and the other hose valve and pressure-regulating valve testing required by Chapter 13 is unchanged (Annex A.6.3.1.2.1). Since pressures at each standpipe need not be balanced, any hose valve on the standpipe can be flowed for the additional 250 gpm, and one on an upper level may be more convenient than the lowest (Annex A.6.3.1.2.2). Where attaching a hose to a standpipe is not reasonable, the AHJ can allow the additional flow from other outlets, such as another standpipe or the fire pump test header; the results will not match the hydraulic calculations, but the test still proves the most remote standpipe can deliver the flow and pressure needed by the fire department while the full system demand flows (Annex A.6.3.1.2.3).

H. Main drain test

CheckCriterionClause
☐ All standpipe systems with automatic water suppliesMain drain test performed per Chapter 136.3.1.6
☐ Test locationThe low point drain of each standpipe, or the main drain test connection where the supply main enters the building (when provided)6.3.1.6.1
☐ Test gaugesGauges maintained per Chapter 13 are provided6.3.1.6.2

I. 5-year hydrostatic test

Manual standpipe systems and semiautomatic dry standpipe systems, including the piping in the fire department connection, are hydrostatically tested every 5 years at not less than 200 psi (13.8 bar) for 2 hours, or at 50 psi (3.4 bar) above the maximum pressure where the maximum pressure exceeds 150 psi (10.3 bar) (6.3.2.1).

CheckCriterionClause
☐ Manual wet standpipes that are part of a combined sprinkler/standpipe systemNot required to be tested per 6.3.2.16.3.2.1.1
☐ Where test pressure is measuredAt the low elevation point of the individual system or zone being tested6.3.2.2
☐ Standpipe pipingNo visible signs of leakage6.3.2.2.1
☐ Gauge pressure dropA drop of 5 psi (0.3 bar) or less is not a failure6.3.2.2.2

Per the Annex A.6.3.2.1 explanation, the intent is to find out whether the system keeps its integrity under fire conditions; minimum leakage existing only under test pressure is not cause for repair. Annex A.6.3.2.2.1 notes that some minor leakage may occur that is not visible; the test is meant to confirm there is no visible leakage from pipe and fittings, since such leakage would indicate corrosion or other damage to the standpipe.

J. Waterflow alarm and supervisory alarm devices

CheckCriterionClause
☐ Waterflow alarm and supervisory alarm devices (where provided)Tested per 13.2.3 and 13.3.3.56.3.3.1
☐ Freezing conditions delay testingTests performed as soon as weather allows6.3.3.2

K. Maintenance

CheckCriterionClause
☐ Maintenance and repairsPer 6.1.3 and Table 6.1.1.26.4.1
☐ Equipment failing inspection or testing requirementsRepaired and tested again, or replaced6.4.2

L. When a component is adjusted, repaired or replaced: Table 6.5.1

Whenever standpipe and hose system components are adjusted, repaired, reconditioned or replaced, the actions in Table 6.5.1 are performed (6.5.1). Where the original installation standard differs from the cited one, the appropriate installing standard may be used (6.5.2). These actions do not require a design review, which is outside the scope of the standard (6.5.3). Fire hose appears on two rows: no action is required when hose is replaced, while repaired hose gets a hydrostatic test per NFPA 1930.

ComponentAdjustRepairReplaceRequired action
Water delivery components
Backflow prevention deviceXXXSee Chapter 13
Control valvesXXXSee Chapter 13
Fire department connectionsXXXSee Chapter 13
Fire hose——XNo action required
Fire hose—X—Perform hydrostatic test in accordance with NFPA 1930
Hose valveXXXSee Chapter 13
Hose valve pressure-regulating devicesXXXSee Chapter 13
PipingXXXHydrostatic test in conformance with NFPA 14
System pressure-regulating devicesXXXSee Chapter 13
Alarm and supervisory components
Pressure switch–type waterflowXXXOperational test using inspector’s test connection
Valve supervisory deviceXXXOperational test for receipt of alarms and verification of conformance with NFPA 14 and/or NFPA 72
Vane-type waterflowXXXOperational test using inspector’s test connection
Water motor gongXXXOperational test using inspector’s test connection
Status-indicating components
GaugesX—XVerify at 0 psi (0 bar) and system working pressure
System housing and protection components
CabinetXXXVerify conformance with NFPA 14
Hose storage rackXXXVerify conformance with NFPA 14
Testing and maintenance components
Auxiliary drainsXXXInspect for leaks at system working pressure
Drain riserXXXInspect for leaks while flowing from connection above the repair
Main drainXXXInspect for leaks and residual pressure during main drain test
Structural components
Hanger/seismic bracingXXXVerify conformance with NFPA 14
Pipe standsXXXVerify conformance with NFPA 14
Informational components
Hydraulic design information signXXXVerify conformance with NFPA 14
Identification signsXXXVerify conformance with NFPA 14

M. Calendar summary: Chapter 6’s own frequencies

The table below gathers the tasks whose frequency is stated in Chapter 6’s own clauses. Frequencies for valves, gauges, pressure-reducing valves and alarm devices are not in this table; they come from Chapter 13.

TaskFrequencyClause
☐ Inspection of the hydraulic design sign, piping, hangers, hose, hose storage devices and cabinetsAnnually6.2.2, 6.2.4.1, 6.2.5, 6.2.6.1, 6.2.8.1, 6.2.9.1
☐ Hose nozzle inspectionAnnually and after each use6.2.7.1, Table 6.1.1.2
☐ Pipe and hangers in areas inaccessible due to process operationsEach scheduled shutdown6.2.4.4, 6.2.5.4
☐ Air test where water damage is a possibilityBefore water is introduced, 25 psi (1.7 bar)6.3
☐ Flow test on automatic standpipesEvery 5 years6.3.1.1
☐ Hydrostatic test on manual and semiautomatic dry standpipesEvery 5 years6.3.2.1
☐ Alarm device tests delayed by freezingAs soon as weather allows6.3.3.2
☐ Maintenance of valves (all types)Annually/as needed (Chapter 13)Table 6.1.1.2

Frequently Asked Questions

How often are hose cabinets and hose inspected under NFPA 25?

Annually. Hose is checked for mildew, cuts, abrasions, damaged threads, missing gaskets, incompatible threads and not being connected (6.2.6.1); cabinets for corrosion, door, glazing, lock, identification, obstructions and access (6.2.9.1). Per Table 6.1.1.2, hose nozzles are inspected annually and after each use.

When is a standpipe flow test required and at what flow?

Every 5 years on all automatic standpipe systems (6.3.1.1). For Class I and III, 500 gpm (1892 L/min) at the most remote standpipe and 250 gpm (946 L/min) for each additional one; 750 gpm (2840 L/min) at the most remote standpipe where a horizontal standpipe supplies three or more hose connections; 100 gpm (379 L/min) at the most remote connection for Class II (6.3.1.2, 6.3.1.2.1, 6.3.1.3). The demand is based on the design criteria in effect at installation (6.3.1.4).

Which standpipes need a hydrostatic test?

Manual standpipes and semiautomatic dry standpipes, including fire department connection piping, every 5 years: at least 200 psi (13.8 bar) for 2 hours, or 50 psi (3.4 bar) above the maximum pressure where it exceeds 150 psi (10.3 bar) (6.3.2.1). Manual wet standpipes that are part of a combined sprinkler/standpipe system are exempt (6.3.2.1.1).

Does a pressure drop during the hydrostatic test mean failure?

A drop of 5 psi (0.3 bar) or less is not a failure (6.3.2.2.2). Pressure is measured at the low elevation point of the system or zone being tested, and the piping must show no visible leakage (6.3.2.2, 6.3.2.2.1).

Can existing fire hose be removed?

Where approved by the AHJ, existing hose may be removed and is not recorded as a deficiency (6.1.6). Per Table 6.5.1, no action is required when hose is replaced; repaired hose is hydrostatically tested per NFPA 1930.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 25-2026, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems: Chapter 6 (6.1–6.5), Table 6.1.1.2, Table 6.5.1 and Annex A explanations (A.6.2.2, A.6.2.4.1, A.6.2.4.3, A.6.2.5.3, A.6.3.1.1, A.6.3.1.2.1–A.6.3.1.2.3, A.6.3.2.1, A.6.3.2.2.1). The content of Chapters 8, 13, 14 and 15 and of NFPA 14, NFPA 72 and NFPA 1930 referenced by Chapter 6 is not reproduced here.