Water trapped inside a wet pipe sprinkler system expands as the temperature rises. Add surge effects such as water hammer and the pressure can quietly climb past the rated limit of the equipment, typically 175 psi (12 bar). To prevent this, NFPA 13 (2025) requires small 1/2 inch pressure relief valves or auxiliary expansion reservoirs throughout the system. This article sets out, in field terms, which is required where.

⚠️ Do not confuse the two: the 1/2 inch (15/16 mm) auxiliary relief valves described here are entirely separate from the large circulation relief valve fitted at the fire pump discharge under NFPA 20. These small valves exist for the static and seismic protection of the sprinkler network itself, the alarm valve trim and antifreeze loops.

1. Relief Valve Requirements on Wet Pipe Systems

NFPA 13 sets the following rules to protect a wet system against pressure build-up:

2. Auxiliary Air Reservoirs and Antifreeze Expansion Control

Auxiliary air reservoir

Where a suitable auxiliary air reservoir is installed to absorb pressure increases, the relief valve requirement is waived. The air reservoir is a sealed vessel that holds air at the same pressure as the water in the wet pipe system and acts as a flexible air cushion accommodating the expansion of the water.

Expansion in antifreeze systems

The expansion of antifreeze solution as it warms produces a significant pressure rise. There are two routes:

3. Relief at Pressure-Reducing Valve Outlets

On the discharge side of pressure-reducing valve stations, used in high-rise buildings and dedicated zones, a listed relief valve of at least 1/2 inch (15 mm) is installed, set so that the rated pressure of the system components is not exceeded. So that operation does not discharge water onto walkways or sensitive equipment, the outlet must be piped to a drain or to a safe external discharge point.

4. Marine Wet Systems

Vessels and marine structures are exposed to greater vibration, temperature swing and impact, so the rules are stricter:

Summary: What Is Required Where?

ApplicationMinimum sizeSetting / operating limit
Standard wet pipe sprinkler network1/2 in (15/16 mm)175 psi (12 bar) or maximum working pressure plus 10 psi
Antifreeze loops (volume below 150 L / 40 gal)1/2 in (15 mm)Relief set to absorb expansion
Pressure-reducing valve outlets1/2 in (15 mm)Set below the rated pressure of system components
Marine wet systems1/2 in (15 mm)Continuous wet pipe protection and tank safety

Frequently Asked Questions

Why does a wet pipe sprinkler system need a 1/2 inch relief valve?

Water trapped in the pipework expands as ambient temperature rises, and surges such as water hammer add to that. The resulting quiet pressure build-up can exceed the rated limit of the equipment, typically 175 psi (12 bar), and damage pipework and sprinkler heads. NFPA 13 therefore requires either a 1/2 inch relief valve or an auxiliary air reservoir on every wet system.

What pressure is the relief valve set to?

It is set to 175 psi (12 bar), or 10 psi (0.7 bar) above the maximum pressure the system can be subjected to, whichever is greater. A listed valve opens within 90% to 105% of its rated pressure and closes fully above 80% of that rating.

If I install an auxiliary air reservoir, is the relief valve still mandatory?

No. Where a suitable auxiliary air reservoir is installed to absorb pressure increases, the relief valve requirement is waived. The reservoir is a sealed vessel holding air at the same pressure as the system water, providing a flexible air cushion that accommodates thermal expansion.

For an antifreeze system, should I use an expansion chamber or a 1/2 inch relief valve?

On small systems where the total antifreeze volume does not exceed 150 litres (40 gallons), a listed 1/2 inch relief valve is permitted instead of a costly and space-consuming expansion chamber. On larger systems an expansion chamber sized with the pre-charge air temperature and pressure taken into account is required.

Is a relief valve mandatory at a pressure-reducing valve outlet?

Yes. A listed relief valve of at least 1/2 inch is installed on the discharge side of the PRV, set so that the rated pressure of the system components is not exceeded. The discharge must be piped to a drain or a safe external point so that operation does not flood walkways or sensitive equipment.

Is this the same as the large circulation relief valve at the fire pump?

No, they are entirely different. The large circulation relief valve at the fire pump discharge, required under NFPA 20, protects the pump from overheating at churn. The 1/2 inch auxiliary relief valves discussed here protect the sprinkler network, alarm valve trim and antifreeze loops from static and thermal pressure build-up.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13, Standard for the Installation of Sprinkler Systems, 2025 Edition — relief valves and auxiliary air reservoirs, antifreeze expansion provisions, pressure-reducing valve outlet safety, marine system requirements, and the associated Annex A explanatory material. Values are for information; the full text of the standard governs any actual design.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.