The first decision in fire pump selection is the drive type, and it affects everything from the tank room to the electrical design. There is no single right answer to electric or diesel; but where a superior or duplicate water supply has more than one pump, at most one may be electric.

Side by side

CriterionElectric motorDiesel engine
Mains dependenceTotalNone (independent on batteries)
First costLowHigh (engine, fuel, exhaust, batteries)
Pump room areaSmallLarge (ventilation, exhaust, fuel)
VentilationOrdinaryCombustion plus cooling plus radiator air
Room temperature (EN 12845 10.3.3)At least 4 °CAt least 10 °C
Pump room fire resistanceAt least 60 min (EN 12845 10.3.1)At least 60 min (EN 12845 10.3.1)
Weekly test (EN 12845 20.2.2)Automatic start by reducing pressure; starting pressure recorded (20.2.2.4)Automatic start, run for 20 min (or the supplier's recommended time), then restart with the manual start test button (20.2.2.5)
Maintenance burdenLowHigh (oil, filters, batteries, fuel turnover)
Fuel managementNoneTank, turnover, water separation, level alarm
NoiseLowHigh; silencer and insulation needed
Redundancy roleDuty pumpStandby pump (typical)

The rule: only one electric pump on a duplicate supply

EN 12845 10.2 is explicit: where more than one pump forms part of a superior or duplicate water supply, at most one may be driven by an electric motor; the rest must be diesel. The reasoning is one sentence — a mains outage is a single point of failure. If two electric pumps are fed from the same transformer, both fall when that transformer does.

The rule is absolute: even with a second electrical source such as another transformer or a generator, EN 12845 10.2 does not permit a second electric pump. Where the electric pump itself is fed from two power sources, the cables to the controller are to be laid at least 3 m apart (10.8.2).

The hidden costs of diesel

The hidden risks of electric

The practical arrangement: on OH2 and OH3 projects in Turkey, the most common solution is a single electric duty pump plus a diesel standby. That satisfies the one-electric rule and brings a second drive independent of the mains.

Frequently Asked Questions

Can I use two electric pumps on a duplicate supply?

No. EN 12845 permits at most one electric motor driven pump within a superior or duplicate supply; the rest must be diesel. A mains outage counts as a single point of failure.

How much ventilation does a diesel pump room need?

EN 12845 10.3.4 requires adequate ventilation in accordance with the supplier's recommendations and gives no fixed figure. A 50 to 100 kW diesel pump typically needs at least 1.2 m² of net free area for combustion, cooling and radiator air; take the exact figure from the engine manufacturer's table.

What temperature must the pump room be?

Under EN 12845 10.3.3, at least 4 °C for an electric motor pump and at least 10 °C for a diesel. The difference is for oil viscosity and battery performance.

Which cable is used for an electric pump?

Under EN 12845 10.8.2, flame-retardant cable is sufficient on a protected route (buried at least 70 cm deep, in concrete with at least 10 cm cover, in the pump room, or in a sprinklered main switchboard room). Where that cannot be achieved, E 90 fire-resistant cable becomes mandatory.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection (2025). EN 12845:2015+A2:2026 pump clauses. EN 17451 (sprinkler pump sets). FM Global DS 3-7. Values are for information only.