Sprinkler design for storage areas uses two FM data sheets together. The design (sprinkler type, number of operating sprinklers and pressure, need for in-rack sprinklers, hose demand and duration) comes from FM Global DS 8-9; the installation rules (K-factor, spacing, distance below the ceiling, obstructions, in-rack sprinkler positions) come from FM Global DS 2-0 Section 2.5.4 (Storage Sprinklers). The commodity class is set by DS 8-1. Clause numbers refer to DS 2-0 October 2021, Interim Revision April 2025; DS 8-9 March 2010, Interim Revision July 2025; and DS 3-26 April 2019, Interim Revision April 2025.

When Storage Design Applies

Storage Sprinklers (DS 2-0 Section 2.5.4.1)

Spacing and Distance Below the Ceiling

Ceiling heightSprinklerLinear spacingArea per sprinkler
Up to 9.0 mK160–K360 and K480 standard coverage2.4–3.7 m6.0–9.3 m²
Over 9.0 mK160–K360 and K480 standard coverage2.4–3.0 m6.0–9.3 m²
All heightsK25.2EC (K360EC) quick response3.0–4.3 m9.3–18.2 m²

Source: DS 2-0 Table 2.5.4.3.1.1 (p. 128), unobstructed ceilings. Distance to walls is more than 100 mm and less than 50% of the maximum linear spacing (Figure 2.5.4.3.2). Under smooth ceilings the thermal element is 50–300 mm below the ceiling for K360EC, quick-response K160 and standard-response sprinklers, 50–325 mm for quick-response K200/K240 and 50–425 mm for quick-response K280 and larger; under non-smooth ceilings the lower limit is 100 mm (Figure 2.5.4.3.3.4, p. 131).

A clearance of at least 0.9 m is kept between the top of storage and the deflectors of standard-coverage ceiling sprinklers, and at least 1.5 m for extended-coverage sprinklers (DS 8-9 2.2.6.1–2.2.6.2, p. 25).

In-Rack Sprinklers (DS 2-0 2.5.4.6 and 2.2.1.6)

Hose Demand and Duration (DS 8-9 Table 14)

Sprinkler typeSprinklers in ceiling designHose demandDuration
Standard coverageUp to 12 / 13–19 / 20 or more950 / 1,900 / 1,900 L/min60 / 90 / 120 min
Extended coverageUp to 6 / 7–9 / 10 or more950 / 1,900 / 1,900 L/min60 / 90 / 120 min

For extended coverage with a maximum linear spacing of 3.7 m, a 7–9 sprinkler design may also use 950 L/min and 60 minutes (Table 14 note, p. 62). Where inside hose is provided, allow at least 380 L/min of the hose demand for it and add the balance to the sprinkler demand at the point of connection (2.3.5.1.1).

Quick Checklist

Frequently Asked Questions

At what storage height does DS 8-9 apply?

Under FM DS 8-9 Section 1.0, DS 8-9 applies when Class 1, 2 or 3 commodities are stored higher than 3.0 m, or Class 4 or plastic commodities higher than 1.8 m. Storage below these heights is treated as low-piled or incidental storage and protected under DS 3-26.

Does back-of-house stock in a shop count as storage?

Under DS 3-26 2.3.2.1, Class 1 to 3 commodities up to 3.0 m high and 20 m² in area are incidental storage and are protected by the occupancy design. In HC-2 and HC-3 occupancies the limit for plastics is 1.8 m and 6 m² (2.3.2.2). If the area limit is exceeded but not the height, the low-piled storage rules apply; above the height limit, DS 8-9 applies.

How much clearance is needed above the storage?

FM DS 8-9 2.2.6.1 calls for at least 0.9 m between the top of storage and the deflectors of standard-coverage ceiling sprinklers, and 2.2.6.2 calls for at least 1.5 m for extended-coverage sprinklers.

Can in-rack sprinklers be fed from the ceiling system?

Normally not; DS 2-0 2.2.1.6.1 calls for separate ceiling and in-rack systems, each with its own check valve, control valve and waterflow alarm. Feeding from the ceiling system is accepted when there are no more than 20 in-rack sprinklers, the water supply can meet both demands and a separate, readily accessible control valve is provided on the in-rack supply (2.2.1.6.2).

How are hose demand and duration set for storage?

Per DS 8-9 Table 14: for standard-coverage sprinklers, up to 12 sprinklers in the ceiling design means 950 L/min for 60 minutes, 13 to 19 sprinklers 1,900 L/min for 90 minutes, and 20 or more 1,900 L/min for 120 minutes. For extended coverage the thresholds are 6, 7 to 9 and 10 sprinklers.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

FM Global DS 2-0, Installation Guidelines for Automatic Sprinklers, October 2021, Interim Revision April 2025 (2.2.1.4.3, 2.2.1.6, 2.5.4); FM Global DS 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, March 2010, Interim Revision July 2025 (1.0, 2.2.6, 2.3.2, Table 14); FM Global DS 3-26, April 2019, Interim Revision April 2025 (2.3.2, 2.3.3); FM Global DS 8-1, Commodity Classification.