Sprinkler design for storage areas uses two FM data sheets together. The design (sprinkler type, number of operating sprinklers and pressure, need for in-rack sprinklers, hose demand and duration) comes from FM Global DS 8-9; the installation rules (K-factor, spacing, distance below the ceiling, obstructions, in-rack sprinkler positions) come from FM Global DS 2-0 Section 2.5.4 (Storage Sprinklers). The commodity class is set by DS 8-1. Clause numbers refer to DS 2-0 October 2021, Interim Revision April 2025; DS 8-9 March 2010, Interim Revision July 2025; and DS 3-26 April 2019, Interim Revision April 2025.
When Storage Design Applies
- DS 8-9 scope (Section 1.0, p. 5): DS 8-9 applies when Class 1, 2 or 3 commodities are stored higher than 3.0 m, or Class 4 or plastic commodities higher than 1.8 m.
- Incidental storage (DS 3-26 2.3.2.1–2.3.2.3, pp. 6–7): Class 1–3 commodities up to 3.0 m high and 20 m² in area, and in HC-2 and HC-3 occupancies plastics up to 1.8 m high and 6 m² (about four pallets), are protected by the occupancy design (Table 2.3.1.10). Several such areas separated by aisles at least 2.4 m wide can still be treated as incidental.
- Low-piled storage (DS 3-26 2.3.3.1, p. 7): where the area limit is exceeded but not the height limit, protection follows DS 3-26 Table 2.3.3.1 together with the DS 2-0 installation and obstruction rules for Storage sprinklers.
- Commodity class: per DS 8-1. The April 2014 revision of DS 8-1 removed Class 4 as a separate category and combined it with cartoned unexpanded plastic (CUP), which is why DS 8-9 tables refer to “Class 4 and Cartoned Unexpanded Plastic”.
Storage Sprinklers (DS 2-0 Section 2.5.4.1)
- K-factors (Table 2.5.4.1.1, p. 111): K11.2 (K160), K14.0 (K200), K16.8 (K240), K19.6 (K280), K22.4 (K320), K25.2 (K360), K28.0 (K400) and K33.6 (K480). K11.2 with a 1/2 in. thread is accepted only as a retrofit for existing K8.0 (K115) or smaller sprinklers.
- Response (2.5.4.1.2): standard-response storage sprinklers may be used on wet and dry systems; quick-response sprinklers only on wet systems and not in the conditions listed in 2.5.4.1.2.2, such as spray application of ignitable liquids, vehicle assembly with fuelled tanks or large shielded areas.
- Venting (2.5.4.1.3.1): no gravity heat or smoke vents in buildings protected by ceiling-level storage sprinklers; where unavoidable, follow the flowchart in Figure 2.5.4.1.3.2(a) for vents of 4 ft² (0.4 m²) or less, or Figure 2.5.4.1.3.2(b) for larger vents (2.5.4.1.3.2).
- System type (DS 8-9 Section 2.3.2, p. 25): wet, dry, antifreeze, preaction, deluge or refrigerated-area according to ambient temperature; gridded piping is recommended only for wet and antifreeze systems.
Spacing and Distance Below the Ceiling
| Ceiling height | Sprinkler | Linear spacing | Area per sprinkler |
|---|---|---|---|
| Up to 9.0 m | K160–K360 and K480 standard coverage | 2.4–3.7 m | 6.0–9.3 m² |
| Over 9.0 m | K160–K360 and K480 standard coverage | 2.4–3.0 m | 6.0–9.3 m² |
| All heights | K25.2EC (K360EC) quick response | 3.0–4.3 m | 9.3–18.2 m² |
Source: DS 2-0 Table 2.5.4.3.1.1 (p. 128), unobstructed ceilings. Distance to walls is more than 100 mm and less than 50% of the maximum linear spacing (Figure 2.5.4.3.2). Under smooth ceilings the thermal element is 50–300 mm below the ceiling for K360EC, quick-response K160 and standard-response sprinklers, 50–325 mm for quick-response K200/K240 and 50–425 mm for quick-response K280 and larger; under non-smooth ceilings the lower limit is 100 mm (Figure 2.5.4.3.3.4, p. 131).
A clearance of at least 0.9 m is kept between the top of storage and the deflectors of standard-coverage ceiling sprinklers, and at least 1.5 m for extended-coverage sprinklers (DS 8-9 2.2.6.1–2.2.6.2, p. 25).
In-Rack Sprinklers (DS 2-0 2.5.4.6 and 2.2.1.6)
- Ceiling and in-rack sprinklers are arranged as separate systems with their own check valve, control valve and waterflow alarm (2.2.1.6.1). An in-rack system may be fed from the ceiling system when it has no more than 20 in-rack sprinklers, the water supply can meet both demands and a separate control valve is provided (2.2.1.6.2).
- One in-rack system covers at most 3,715 m² of floor area occupied by racks, including aisles, regardless of the number of levels (2.2.1.4.3).
- In-rack sprinklers are located within the rack structure, and face sprinklers no more than 450 mm in from the rack face (2.5.4.6.1–2.5.4.6.2).
- Deflectors at least 150 mm above the top of storage; where that cannot be achieved, in-rack sprinklers go at all flue space intersections, face and longitudinal (2.5.4.6.6).
- In-rack sprinklers and piping are arranged to avoid damage from material handling (2.5.4.6.8).
Hose Demand and Duration (DS 8-9 Table 14)
| Sprinkler type | Sprinklers in ceiling design | Hose demand | Duration |
|---|---|---|---|
| Standard coverage | Up to 12 / 13–19 / 20 or more | 950 / 1,900 / 1,900 L/min | 60 / 90 / 120 min |
| Extended coverage | Up to 6 / 7–9 / 10 or more | 950 / 1,900 / 1,900 L/min | 60 / 90 / 120 min |
For extended coverage with a maximum linear spacing of 3.7 m, a 7–9 sprinkler design may also use 950 L/min and 60 minutes (Table 14 note, p. 62). Where inside hose is provided, allow at least 380 L/min of the hose demand for it and add the balance to the sprinkler demand at the point of connection (2.3.5.1.1).
Quick Checklist
- Storage height and commodity class decide whether DS 8-9 or DS 3-26 applies
- Commodity class established per DS 8-1
- Protection option from the DS 8-9 tables, installation from DS 2-0 Section 2.5.4
- Spacing per Table 2.5.4.3.1.1 and distance below the ceiling per Figure 2.5.4.3.3.4
- Clearance above storage at least 0.9 m (1.5 m for EC sprinklers)
- In-rack positions and system separation per 2.5.4.6 and 2.2.1.6
- Hose demand and duration from DS 8-9 Table 14
Frequently Asked Questions
At what storage height does DS 8-9 apply?
Under FM DS 8-9 Section 1.0, DS 8-9 applies when Class 1, 2 or 3 commodities are stored higher than 3.0 m, or Class 4 or plastic commodities higher than 1.8 m. Storage below these heights is treated as low-piled or incidental storage and protected under DS 3-26.
Does back-of-house stock in a shop count as storage?
Under DS 3-26 2.3.2.1, Class 1 to 3 commodities up to 3.0 m high and 20 m² in area are incidental storage and are protected by the occupancy design. In HC-2 and HC-3 occupancies the limit for plastics is 1.8 m and 6 m² (2.3.2.2). If the area limit is exceeded but not the height, the low-piled storage rules apply; above the height limit, DS 8-9 applies.
How much clearance is needed above the storage?
FM DS 8-9 2.2.6.1 calls for at least 0.9 m between the top of storage and the deflectors of standard-coverage ceiling sprinklers, and 2.2.6.2 calls for at least 1.5 m for extended-coverage sprinklers.
Can in-rack sprinklers be fed from the ceiling system?
Normally not; DS 2-0 2.2.1.6.1 calls for separate ceiling and in-rack systems, each with its own check valve, control valve and waterflow alarm. Feeding from the ceiling system is accepted when there are no more than 20 in-rack sprinklers, the water supply can meet both demands and a separate, readily accessible control valve is provided on the in-rack supply (2.2.1.6.2).
How are hose demand and duration set for storage?
Per DS 8-9 Table 14: for standard-coverage sprinklers, up to 12 sprinklers in the ceiling design means 950 L/min for 60 minutes, 13 to 19 sprinklers 1,900 L/min for 90 minutes, and 20 or more 1,900 L/min for 120 minutes. For extended coverage the thresholds are 6, 7 to 9 and 10 sprinklers.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreFM Global DS 2-0, Installation Guidelines for Automatic Sprinklers, October 2021, Interim Revision April 2025 (2.2.1.4.3, 2.2.1.6, 2.5.4); FM Global DS 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities, March 2010, Interim Revision July 2025 (1.0, 2.2.6, 2.3.2, Table 14); FM Global DS 3-26, April 2019, Interim Revision April 2025 (2.3.2, 2.3.3); FM Global DS 8-1, Commodity Classification.