Very large crude and gasoline tanks in refineries (50,000–150,000 m³) mostly use floating roofs to reduce evaporation losses and the risk of a flammable vapor space. Lightning or static discharge ignites rim-seal fires. NFPA 11 defines seal area protection and full surface protection for floating-roof tanks (NFPA 11-2024, 5.3.1.1), and does not permit subsurface or semi-subsurface injection on open-top or covered floating-roof tanks (5.3.3.1). Buncefield 2005 (UK) and Jaipur 2009 (India) are the major reference accidents.

Tank Types

Rim-Seal Fire

NFPA 11 Foam Types

Full-Surface Fire

80 m diameter tank, full surface fire. NFPA 11 Section 5.3 gives seal area criteria for open-top floating-roof tanks; this full-surface example borrows the monitor criteria for fixed-roof tanks (Table 5.2.4.2.2):

Buncefield 2005 Lesson

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.