Skip to content
Foam

Foam concentrate calculator

Pick a tank, covered floating roof, dike, loading rack, spill area or foam-water sprinklers and the NFPA 11 application rate and discharge time fill in, with supplementary hose streams added. Solution flow, concentrate and water volume on one screen.

NFPA 11-2024Low expansionFoamPreliminary sizing

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

38 more calculators ↓

How do you calculate foam concentrate quantity?

In a low-expansion foam system the stored concentrate must be enough to deliver foam solution to the protected surface at a set application rate for a set minimum discharge time. NFPA 11 tabulates both values by hazard type. The calculation is straightforward: solution flow first, then total solution volume, then the split into concentrate and water.

Q = rate × area · Vsol = Q·t + hose streams + pipe fill · Vc = p% × Vsol

A handy identity: mm/min × m² = L/min. The standard prints 0.10 gpm/ft² as 4.1 mm/min in its SI column; the calculator uses whichever column matches the selected unit system.

NFPA 11-2024 values by scenario

ApplicationMinimum rateMinimum timeSource
Fixed roof, Type II outlets — flash point 38–60 °C0.10 gpm/ft² (4.1 mm/min)30 minTable 5.2.5.2.2
Fixed roof, Type II — flash point < 38 °C or heated; crude0.10 gpm/ft²55 minTable 5.2.5.2.2
Fixed roof, polar liquid (AR foam)manufacturer listing55 minTable 5.2.5.3.4
Subsurface injection0.10 gpm/ft² (max 0.20)30 / 55 / 55 minTable 5.2.6.5.1
Floating roof, top of seal (foam dam)0.30 gpm/ft²20 minTable 5.3.5.3.1
Floating roof, below the seal0.50 gpm/ft²10 minTable 5.3.5.3.6.1
Dike — low-level outlets / monitors0.10 / 0.16 gpm/ft²Class I 30 · Class II 20 minTable 5.7.3.2
Non-diked spill — protein/fluoroprotein · AFFF/FFFP0.16 · 0.10 gpm/ft²15 minTable 5.8.1.2

For floating-roof tanks the protected area is not the whole liquid surface but the annulus between the shell and the foam dam, which must sit 300–600 mm from the shell (5.3.5.4.4). For polar liquids needing alcohol-resistant foam NFPA 11 gives no numeric rate; the value comes from the concentrate listing and is a user input here.

Supplementary foam hose streams

Tank protection also needs foam hose streams for small spill fires (5.9.2.1). Their number follows the diameter of the largest tank: 1 up to 20 m, 2 from 20 to 36 m, 3 above 36 m (Table 5.9.2.2). Each stream delivers at least 190 L/min (50 gpm) of solution (5.9.2.3). Simultaneous operating time is 10 min up to 11 m, 20 min from 11 to 29 m and 30 min above 29 m (Table 5.9.2.4). Hose flow adds to the tank flow, so the pump and proportioner are sized for the sum.

Concentrate, reserve and water

Consumption follows the design proportioning rate — for example 3 or 6 percent, or another rate such as 1% if the concentrate is so listed or the AHJ approves it (4.3.2.5.1) — and the quantity must cover the largest single hazard or group protected simultaneously (4.3.2.2). The tank needing the largest flow is not necessarily the one needing the most concentrate, because discharge times differ. A reserve able to meet the worst case again is also required to put the system back into service; it may be in separate tanks, drums, or available from an approved source within 24 hours (4.3.2.5.2). The standard gives no figure for filling the pipework, so enter your own value from the pipe volume.

Worked example

A 30 m fixed-roof tank storing a product with a flash point below 38 °C, protected by Type II outlets with 3% concentrate:

The example in the NFPA 11 annex follows the same logic: 300 gpm of solution for 30 minutes at 3% needs 270 gal of concentrate.

Monitors, internal floating roofs, loading racks and foam-water sprinklers

ScenarioRateTimeClause
Fixed-roof tank, monitors or handlines as primary protection6.5 mm/min × at least 1.550 min (FP 38–60 °C), 65 min (FP < 38 °C, crude, AR foam)Table 5.2.4.2.2, 5.2.4.2.1.2, 5.2.4.4
Covered floating-roof tank, full surface fireas a fixed-roof tank of the same diameterTable 5.2.5.2.25.4.2.2
Covered floating-roof tank, seal fire12.2 mm/min (top of seal, with foam dam)20 min5.4.2.3, Table 5.3.5.3.1
Loading rack, monitorsprotein/SFFF 6.5 · AFFF/FFFP 4.1 mm/min; 6.5 where fuel can pool deeper than 25 mm15 minTable 5.6.5.3.1, 5.6.5.3.2
Foam-water sprinklers and sprayat least 6.5 mm/min; 465 m² for wet/dry/preaction, entire system area for deluge10 min (at least 7 min when reduced)6.5.2.2.1, 6.5.2.2.2.1, 6.5.2.3

Handlines may not be the primary protection for fixed-roof tanks over 9 m (30 ft) in diameter or 6.1 m (20 ft) high (5.2.4.1.2); monitors must be part of a system that can be put in service within 4 hours and approved by the AHJ (5.2.4.1.1). On covered floating roofs, seal protection applies only to the roofs listed in 5.4.2; others need full surface protection (5.4.2.1). No supplementary hose streams are added for racks and sprinklers. Medium- and high-expansion total flooding has its own tool: high-expansion foam calculator. Check the listed minimum and maximum flow range of the proportioner as well (4.5.1).

Common mistakes

Frequently Asked Questions

How is foam concentrate quantity calculated?

Solution flow is application rate times protected area (mm/min × m² = L/min). Multiply by the NFPA 11 discharge time, add the supplementary hose stream volume, and take 3%, 6% or the listed rate (e.g. 1%) of the total solution as concentrate.

What is the discharge time for a fixed-roof tank?

With Type II fixed outlets it is 30 minutes for hydrocarbons with a flash point of 38–60 °C and 55 minutes for products below 38 °C, heated products and crude oil, at a minimum of 0.10 gpm/ft² (NFPA 11 Table 5.2.5.2.2).

How many supplementary foam hose streams are needed?

It depends on the largest tank: 1 up to 20 m (65 ft), 2 from 20 to 36 m, 3 above 36 m. Each delivers at least 50 gpm (190 L/min) for 10, 20 or 30 minutes (NFPA 11 Tables 5.9.2.2 and 5.9.2.4).

Is a reserve supply of concentrate required?

Yes. NFPA 11 4.3.2.5.2 requires a reserve that can meet the worst-case scenario again and return the system to service. It can be stored on site or be obtainable from an approved source within 24 hours.

Why is the rate a user input for polar liquids?

Water-soluble liquids such as alcohols, ketones and esters break down ordinary foam, so alcohol-resistant foam is needed and NFPA 11 refers to the concentrate listing instead of a fixed number. Take the rate from the approval of the product and the foam-making device.

Why is a factor of 1.5 applied to monitors as primary protection?

NFPA 11-2024 5.2.4.2.1 accepts that part of the foam from monitors and handlines is lost to wind and ambient conditions; the application rate is increased by a factor of at least 1.5 (5.2.4.2.1.2). The 0.16 gpm/ft² (6.5 mm/min) of Table 5.2.4.2.2 therefore becomes at least 0.24 gpm/ft² (9.75 mm/min).

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →