Choose the standard, rack type and size, tier height and commodity; the tool gives the number and height of in-rack levels, the spacing along and across the rack, the head count and the sprinkler type with clause and figure numbers, and shows them in elevation, plan and a 3D rack model.

NFPA 13 Chapter 25EN 12845 12.5FM DS 8-9 2.3.43D rack model

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

31 more calculators ↓

What are in-rack sprinklers and when are they needed?

In-rack (intermediate level) sprinklers are fitted inside the rack structure, in the flue spaces between loads, where the water from the ceiling sprinklers cannot reach the lower tiers of high-bay storage. All three standards place them at the intersections of transverse and longitudinal flues; the number of levels depends on storage height, tier height and commodity. This tool calculates the layout; the ceiling design, pipe sizes and hydraulic calculation are done separately.

EN 12845: the 3.50 m rule and clause 12.5

FM DS 8-9: IRAS(E) and IRAS(EO)

FM Global selects the horizontal arrangement with the flowcharts in Figs. 5, 5a, 6, 6a and 7. The decision depends on:

IRAS(EO) places sprinklers at every other transverse flue, 1.2–3.0 m apart; IRAS(E) at every transverse flue, 0.6–2.4 m apart. The vertical increment follows Fig. 15 by commodity: 7.5, 6.0, 4.5 or 3.0 m, with at most 3.0 m of storage above the top level. In-rack sprinklers are FM Approved, quick response, 70 °C nominal (2.3.4.3). The design comes from Table 12 and the ceiling protection table from Table 13.

NFPA 13-2025: Chapter 25 figures

NFPA 13 gives in-rack arrangements combined with CMDA ceiling sprinklers as figures by commodity and height (25.4.2).

For NFPA 13 the tool covers arrangements with CMDA ceiling sprinklers. Arrangements with CMSA and ESFR ceilings (25.5, 25.6), in-rack options independent of the ceiling (25.7) and rubber tyres are not in this version.

Counting convention: if the gap from the last sprinkler to the rack end exceeds half the spacing, the end also gets a sprinkler. Cases the figure does not dimension (e.g. the spacing along a double-row rack in NFPA) are flagged separately in the result.

Frequently Asked Questions

What is the maximum vertical distance between in-rack levels in EN 12845?

Under clause 12.5.2, floor to the lowest level and between levels at most 3.50 m or two tiers, whichever is less. The highest level may not be more than one tier below the top of storage.

Is a level needed above the top of storage?

In EN 12845 not if all ceiling sprinklers are less than 4 m above the storage; otherwise yes (12.5.2). In FM DS 8-9 at most 3.0 m of storage may remain above the top level (Fig. 15).

What is the difference between IRAS(E) and IRAS(EO) in FM DS 8-9?

IRAS(EO) puts sprinklers at every other transverse flue intersection (1.2–3.0 m), IRAS(E) at every transverse flue intersection (0.6–2.4 m). The flowcharts in Figs. 5–7 decide which is acceptable.

Where does a single in-rack level go in NFPA 13?

Where the figure does not show it, at the first tier level at or above half the storage height (25.1.8.1). For two levels, one-third and two-thirds are used (25.1.8.2).

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →