Classification

EN 12845 hazard class finder

Choose a facility type and get its EN 12845 Annex A class, design density, area of operation, sprinkler demand, duration and water volume at once. The hazard ladder and the to-scale area of operation update live.

EN 12845Annex ALH · OH · HHPPreliminary sizing

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

How is the hazard class set in EN 12845?

EN 12845 groups protected areas by fire load and combustibility into three main families: Light Hazard (LH), Ordinary Hazard (OH1–OH4) and High Hazard. High hazard splits again into HHP1–HHP4 for production and process areas and HHS1–HHS4 for storage. The standard's Annex A links typical facility types to these classes, and its tables are a minimum classification: where the real use is more severe, choosing a higher class is the designer's responsibility.

The mappings in this calculator are checked, together with our Annex A article, against the Annex A tables (A.1, A.2, A.3) of BS EN 12845:2015+A1:2019; these tables are unchanged in the 2015+A2:2026 edition. The standard lists saw mills both as OH4 and as HHP2, so they appear as two separate entries. For occupancies not listed, the tables serve as guidance and the class is assessed for the specific facility.

Design points: density, area, duration

Unlike the NFPA 13 curves, each EN 12845 class has one fixed design point. The OH classes share the same density and differ only in area of operation; the HHP classes share the same area while the density rises.

ClassDensityArea (wet)Area (dry/alternate)DurationMinimum demand
LH2.25 mm/min84 m²not permitted → OH130 min189 L/min
OH15.0 mm/min72 m²90 m²60 min360 L/min
OH25.0 mm/min144 m²180 m²60 min720 L/min
OH35.0 mm/min216 m²270 m²60 min1080 L/min
OH45.0 mm/min360 m²not permitted → HHP160 min1800 L/min
HHP17.5 mm/min260 m²325 m²90 min1950 L/min
HHP210.0 mm/min260 m²325 m²90 min2600 L/min
HHP312.5 mm/min260 m²325 m²90 min3250 L/min
HHP4No numerical point — deluge / special protection
Q = density × area of operation → 5.0 mm/min × 216 m² = 1080 L/min (OH3)

A handy identity: mm/min × m² = L/min. For water volume, multiply by duration: for OH3, 1080 L/min × 60 min = 64.8 m³. That is a theoretical minimum without overrun; in a real hydraulic calculation the remote-area sprinklers run above minimum pressure, so the flow grows. For tank sizing, use the fire water tank calculator.

Dry and alternate systems

For dry pipe and alternate (wet/dry) systems the area of operation is increased by 25%. There are two exceptions: LH does not permit dry systems, so at least the OH1 dry criterion (90 m²) applies; OH4 has no dry row, so the design moves up to the HHP1 dry criterion (7.5 mm/min over 325 m²). The calculator applies these upgrades automatically and shows them in the class tile, for example "OH4 → HHP1".

Coverage and spacing per sprinkler

For standard sprinklers the maximum area per sprinkler is 21 m² for LH, 12 m² for OH and 9 m² for HHP, with maximum spacing of 4.6 m, 4.0 m and 3.7 m respectively. Dividing the area of operation by that coverage gives the minimum number of sprinklers expected to open together. The scaled square in the visual shows the area of operation and those sprinklers; the dashed squares are the areas of the other classes.

Common classification mistakes

If there is storage: Annex A classifies the facility type only. Stored goods are categorised through Annex B (material factor) and Annex C (alphabetical commodity list); if the height exceeds the OH limits, the area is designed separately as HHS. Where process and storage are openly connected, the higher class governs the whole zone.

Facilities not on the list

Annex A is also guidance for occupancies it does not name. Find the closest analogue, compare fire load and process conditions, and round up when in doubt. Recording the decision with clause and table references, together with the insurer's view, makes approval by the authority far smoother.

Frequently Asked Questions

What EN 12845 hazard class is a shopping centre?

Shopping centres, department stores and shops are OH3 in Annex A: 5.0 mm/min × 216 m² = 1080 L/min minimum sprinkler demand for 60 minutes (≈ 65 m³). If in-store storage exceeds the OH limits, that zone is designed separately as HHS.

Are hospitals and hotels LH or OH1?

In EN 12845 Annex A, hospitals, hotels, restaurants and libraries (excluding book stores) are on the OH1 list: 5.0 mm/min × 72 m² for 60 minutes. LH is reserved for certain school and office areas and prisons.

How does a dry system change the area of operation?

For dry and alternate systems the area grows by 25%: OH1 90 m², OH2 180 m², OH3 270 m², HHP 325 m². LH does not permit dry systems (use at least OH1 dry), and OH4 moves up to the HHP1 dry criterion.

Why are there no numbers for HHP4?

HHP4 covers processes with very fast fire growth, such as fireworks manufacture, and EN 12845 gives no density/area values for it. Protection is by deluge or foam-water, designed for the specific project with a risk assessment and authority approval.

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store