The pump will not deliver, it overheats, vibrates or draws too much power: where to start? NFPA 20-2025 Annex B gives a troubleshooting chart for this: 10 troubles, 32 possible causes and a suggested remedy for each cause. The annex is informational and not part of the requirements.

In short: Figure B.1 maps each trouble to its possible causes, grouped as suction (1–4), pump (5–20), driver and/or pump (21–25) and driver (26–32). The causes are in addition to mechanical breakage that would be obvious on visual inspection, and troubles that are easy to check should be corrected or eliminated first (B.1). Annex B.3 explains how to return an electric fire pump controller to service after a fault.

NFPA 20-2025 Annex B Figure B.1: fire pump troubles and 32 possible causes; causes of the selected trouble marked in the suction, pump, driver and/or pump, and driver groups
From trouble to cause. Pick a trouble; the causes marked with X on that row of Figure B.1 light up and are listed below (Annex B, Figure B.1).

Troubles and possible causes

Figure B.1: possible cause numbers per trouble (each number is one X in the figure)
TroubleSuction (1–4)Pump (5–20)Driver and/or pump (21–25)Driver (26–32)
Excessive leakage at stuffing box—5, 1823—
Pump or driver overheats45, 6, 8, 11, 15, 18, 19, 2021, 22, 23, 24, 2527, 29, 30, 31
Pump unit will not start45, 15, 16, 172126, 27, 32
No water discharge1, 2, 38, 19——
Pump is noisy or vibrates45, 8, 10, 1821, 22, 23, 2427
Too much power required45, 8, 9, 11, 13, 15, 1821, 22, 23, 2427, 29, 30, 31
Discharge pressure not constant for same gpm15, 6, 7——
Pump loses suction after starting1, 2, 36, 7, 20——
Insufficient water discharge1, 2, 36, 7, 8, 9, 10, 11, 12, 13, 15—28, 29, 31
Discharge pressure too low for gpm discharge1, 2, 35, 6, 7, 8, 9, 10, 11, 12, 13, 14—28, 29, 31

Annex B.1 calls the chart a partial guide and the remedies a partial list. The NFPA 20 Handbook (2022) notes that Annex B may be useful in identifying and correcting problems discovered during acceptance tests.

Causes and suggested remedies

Possible causes and suggested remedies (B.1.1–B.1.32)
NoPossible causeAnnex B remedy (summary)
Suction
1Air drawn into suction connection through leak(s)Uncover suction pipe, locate and repair leak
2Suction connection obstructedExamine intake, screen and pipe; remove obstruction (see 4.16.8)
3Air pocket in suction pipeUncover and rearrange suction pipe (see 4.16.6)
4Well collapsed or serious misalignmentConsult a well driller and the pump manufacturer
Pump
5Stuffing box too tight or packing improper, worn, defective or wrong typeRemove gland halves, replace packing
6Water seal or pipe to seal obstructedRemove seal ring and packing, clean water passage
7Air leak into pump through stuffing boxesSame as B.1.6
8Impeller obstructedOpen pump, clear impeller; screen the intake
9Wearing rings wornCheck ring clearance with a feeler gauge
10Impeller damagedMinor repair or replacement from manufacturer
11Wrong diameter impellerReplace with impeller of proper diameter
12Actual net head lower than ratedCheck impeller diameter, number and model for correct curve
13Casing gasket defective, internal leakage (single- and multistage)Replace gasket; check drawing whether required
14Pressure gauge on top of pump casingPlace gauges correctly [see Figure A.6.3.1(a)]
15Incorrect impeller adjustment (vertical turbine only)Adjust impellers per manufacturer
16Impellers lockedTurbine: raise/lower by top nut; split case: remove obstruction
17Pump is frozenHeat the pump room; disassemble, remove ice, inspect
18Shaft or shaft sleeve scored, bent or wornReplace shaft or sleeve
19Pump not primedShut down; on a turbine check submergence
20Seal ring improperly located in stuffing boxReinstall seal ring in proper location
Driver and/or pump
21Excess bearing friction (lubrication, wear, dirt, rust, failure, installation)Remove bearings; clean, lubricate or replace
22Rotating element binds against stationary elementCheck clearances and lubrication; repair part
23Pump and driver misalignedAlign per manufacturer, replace bearings (see Section 6.5)
24Foundation not rigidTighten bolts or replace foundation (see Section 6.4)
25Engine-cooling system obstructedCheck regulator valve, strainer and cooling circuit
Driver
26Faulty driverCheck driver per manufacturer's instructions
27Lack of lubricationReplace seized parts, lubricate
28Speed too lowCheck speed, voltage, frequency and starting equipment
29Wrong direction of rotationCompare coupling rotation with casing arrow
30Speed too highMatch rated speeds; set governor
31Rated motor voltage different from line voltageCorrect voltage or larger motor (see Section 9.4)
32Faulty circuit, obstructed fuel system or steam pipe, dead batteryCheck wiring, switch, breaker, battery, fuel line, strainers

Numerical and diagnostic hints in Annex B

  • Wearing rings (B.1.9): clearance when new is 0.0075 in. (0.19 mm); more than 0.015 in. (0.38 mm) is excessive.
  • Obstructed impeller (B.1.8): does not show on any one instrument, but pressures fall off rapidly when a large flow is drawn.
  • Pump not primed (B.1.19): run without water in its casing, the wearing rings are likely to seize; the first warning is a change in pitch of the driver’s sound.
  • Cooling (B.1.25): if overheating persists at loads up to 150 percent of rated capacity, contact the pump or engine manufacturer.
  • Reverse rotation (B.1.29): rare but clearly recognizable by an extreme deficiency of delivery; compare the flexible coupling’s rotation with the arrow on the pump casing. With a polyphase motor two wires are reversed; where two power sources exist, check the rotation produced by each.
  • Voltage mismatch (B.1.31): the example given is a 220 V or 440 V motor on a 208 V or 416 V line.
  • Speed too low (B.1.28): low frequency and low voltage in the power supply keep a motor from reaching rated speed; on an internal combustion engine drive check the governor setting and that the hand throttle is wide open.

In a note based on NFPA 25, the Handbook (2022) lists a plugged impeller, worn wear rings and obstructed suction among the most common causes of reduced capacity; the suction gauge reading can show whether the trouble is in the water supply or suction pipe, while the difference between suction and discharge gauge readings can point to a plugged impeller or overly worn wear rings.

Controller after a fault (B.2, B.3)

  • Chapters 9 and 10 discourage disconnecting means in the power supply to electric motor–driven fire pumps to keep power available; a person servicing equipment on those circuits can therefore have unusual exposure to electrical hazards, and special safe work practices or personal protective clothing may be needed (B.2).
  • In a properly installed and coordinated circuit, tripping of the circuit breaker or isolating switch indicates a fault beyond operating overload; qualified personnel inspect and repair the controller (B.3.1).
  • All inspections and tests are made with the controller de-energized at the line terminal, disconnected, locked out and tagged (B.3.2).
  • Substantial enclosure damage such as deformation, displaced parts or burning means replacing the entire controller (B.3.2.1). If the breaker has opened several short-circuit faults or shows deterioration, replace the components; verify the external handle can open and close the breaker and isolating switch (B.3.2.2).
  • Terminals and conductors showing arcing or overheating, and heat-damaged contactor contacts, are replaced (B.3.2.3, B.3.2.4). Before return to service check connection tightness and the absence of short circuits, ground faults and leakage current; close the enclosure before energizing (B.3.2.5).

Checklist

  1. Find the trouble in Figure B.1; eliminate the easy-to-check causes first (B.1).
  2. Suction (1–4): leaks, obstruction, air pocket.
  3. Pump (5–20): packing, impeller, wearing rings, gauge location, priming.
  4. Driver (21–32): alignment, foundation, cooling, speed, rotation, voltage, battery and fuel.
  5. If the controller breaker tripped, apply B.3 with the controller de-energized, locked out and tagged.

For gauge location see the pressure gauges article; for the acceptance test see the field acceptance test article.

Frequently Asked Questions

What can cause a fire pump to deliver no water?

Per Figure B.1: air drawn in through suction leaks (1), obstructed suction (2), an air pocket in the suction pipe (3), an obstructed impeller (8) and the pump not primed (19) (NFPA 20-2025 Annex B).

What should be checked when discharge pressure is too low for the flow?

Figure B.1 lists 16 causes: suction (1–3), packing and seal (5–7), impeller and wearing rings (8–11), net head (12), casing gasket (13), gauge on top of the casing (14), low speed (28), wrong rotation (29) and motor voltage mismatch (31).

What wearing ring clearance is acceptable?

Per Annex B.1.9, 0.0075 in. (0.19 mm) when new; more than 0.015 in. (0.38 mm) is excessive.

How is reverse rotation recognized?

Delivery is extremely deficient; compare the flexible coupling’s rotation with the arrow on the pump casing. With a polyphase motor two wires are reversed (B.1.29).

Is Annex B mandatory?

No. Annex B is informational and describes itself as a partial guide (B.1).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 20-2025, Standard for the Installation of Stationary Pumps for Fire Protection: Annex B (informational) B.1, B.1.1–B.1.32, Figure B.1, B.2, B.3.1–B.3.2.5. NFPA 20 Handbook 2022 commentary: Chapter 14 introduction; 14.4 Closer Look note; Annex B Figure B.1.