The fire pump room is where a sprinkler system can fail at a single point. Even a correctly selected pump will not run when needed if it is installed in the wrong place, with the wrong suction arrangement, in a room that is neither heated nor ventilated. This guide is a checklist for getting the pump room right at the design stage, on the drawing board.

For inspecting an existing room on site there is a separate list: the fire pump room inspection checklist. This article is aimed at the engineer drawing the project and sets NFPA 20 and EN 12845 side by side. For selecting the pump itself, see the fire pump selection guide.

1. Location and fire separation

The pump room must not be affected by the fire it exists to fight. That is why both standards start with location.

TopicNFPA 20EN 12845
Preferred locationA separate pump house or a fire-separated room within the building; the choice depends on whether the building is sprinklered and whether it is a high-rise.Order of preference: separate building → room attached to the sprinklered building with direct outside access → compartment inside the building with direct outside access.
Fire resistanceTypically 1 hour in a fully sprinklered building, 2 hours in an unsprinklered one; 2 hours in high-rise buildings. A detached structure at a set distance (of the order of 15 m) may be accepted instead.A compartment with at least 60 minutes' fire resistance; no other use permitted.
Protection within the roomThe pump room is sprinkler protected.The pump room is sprinkler protected.
Other usesNot to be used for storage beyond fire protection equipment.Reserved for fire protection equipment only.

Add two practical questions at design stage: is the room exposed to flooding or surface water (at basement level, next to a sump)? Is it far enough from escape routes and high-risk areas (transformers, generator fuel stores, flammable liquid stores)? Confirm fire resistance periods and separation-distance alternatives against the current NFPA 20 edition and local regulations; in Türkiye the pump and tank provisions of the national fire regulation also apply (Turkish regulation on fire pumps and water tanks).

2. Access and maintenance space

3. Suction arrangement

A large share of pump failures start on the suction side: cavitation, air pockets, turbulent entry. These rules are non-negotiable in design:

4. Discharge side, test header and flowmeter

A pump is flow-tested on the day it is commissioned and every year of its life. If the test arrangement is not resolved in design, the test is either never done or it floods the building.

5. Relief valves, circulation and drainage

6. Ventilation and heating

TopicNFPA 20EN 12845
Minimum room temperatureGenerally 5 °C (40 °F); in diesel engine rooms, not below the engine manufacturer's recommended value.4 °C for electric pumps, 10 °C for diesel pumps.
VentilationCombustion and cooling air for diesel engines; room temperature kept below the upper limit for the engine and controller.Adequate ventilation for diesel pumps to the manufacturer's instructions; the numerical airflow comes from the manufacturer.

Ventilation in a diesel pump room does three jobs: it supplies combustion air, removes heat from radiator-cooled engines and keeps room temperature acceptable for the controller and batteries. On radiator engines the hot air should be ducted straight outside, with the fresh air louvre on the opposite side and of adequate free area. In winter those louvres can freeze the room; consider motorised dampers with thermostatic control. Heaters should be sized to rule out freezing, with insulation that holds the room temperature for a while even during a power cut.

Exhaust: the diesel exhaust should be insulated, fitted with a flexible connection for expansion and a silencer, and discharged outside away from building openings. Back pressure must stay within the engine manufacturer's limit; on long exhaust runs, check the diameter by calculation.

7. Fuel tank (diesel)

To compare the two standards' results, use the diesel fire pump fuel tank calculator.

8. Controllers and power supply

For controller requirements in detail, see NFPA 20 fire pump controllers.

9. Lighting, signage and documentation

NFPA 20 vs EN 12845: where design differs most

TopicNFPA 20EN 12845
Suction liftNot accepted for horizontal pumps; use a vertical turbineAccepted with conditions (foot valve, priming, lift limit)
Pump curveAt least 65% of rated pressure at 150% of rated flow; churn not above 140%Selected against the demand point; curve and power conditions follow the standard's own rules
Diesel fuel5.07 L/kW + 5% + 5%LH/OH 3 h, HHP/HHS 6 h at full load
Room temperature5 °C; manufacturer's value for dieselElectric 4 °C, diesel 10 °C
Fire separation1 or 2 hours (by building) or distance60 minutes, direct outside access

For a detailed side-by-side reading see the NFPA 20 vs EN 12845 pump comparison and, on the EN side, EN 12845 pump room requirements.

The hand-over test for the design: once the drawing is finished, ask yourself: "Could a technician, at midnight, with the building on fire and a torch in hand, get into this room from outside, start the pump by hand, read the gauges and open the test valve?" If the answer is no at any step, the room has not been designed yet.

Frequently Asked Questions

Can the pump room be in a basement?

The standards do not forbid it outright, but direct outside or protected access, fire separation, flood risk and drainage must all be resolved. EN 12845's order of preference puts a separate building and direct outside access first.

What is the minimum temperature for a diesel pump room?

At least 10 °C under EN 12845. NFPA 20 generally asks for 5 °C, but a diesel engine room must not fall below the engine manufacturer's recommended value.

How large should the diesel fuel tank be?

Under NFPA 20, about 5.07 L/kW plus 5% for expansion and 5% for sump; under EN 12845, enough for 3 hours at full load for LH/OH and 6 hours for HHP/HHS.

Is a test header needed if a flowmeter is fitted?

NFPA 20 accepts a flowmeter as a test method, but in some cases, or at the authority's preference, a hose valve test header may still be required. Either way, where test water discharges must be resolved in design.

How does this differ from the inspection checklist?

This guide is for getting the room right in the project: location, size, suction geometry, ventilation capacity. The inspection checklist is for checking a working room on site: valve positions, records, fuel and battery condition.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection (2022/2025) · BS EN 12845:2015+A1:2019 · NFPA 25 · Turkish Regulation on Fire Protection of Buildings. Fire resistance periods, velocity limits and distances vary between editions; the binding text is the current standard and the authority having jurisdiction.