The electric motor of a pump that injects foam concentrate or another additive into the system also runs from a controller. NFPA 20-2025 Section 10.9 lists the four points in which these controllers differ from the general electric controller rules: starting, stopping, lockout and marking. The pump itself (NPSH, relief discharge) is covered in foam concentrate and additive pumps.

In short: an additive pump controller complies with 10.1 through 10.5 (and 10.8 where required); only 10.9.2 through 10.9.5 differ (10.9.1). Automatic starting must be possible by the automatic opening of a closed circuit loop containing the fire protection equipment, in lieu of a pressure switch (10.9.2). Manual shutdown is provided and automatic shutdown is not permitted (10.9.3.1, 10.9.3.2). Where required in duty-standby use a lockout is provided, with a visible indicator and remote annunciation (10.9.4). The controller is marked “Additive Pump Controller” (10.9.5).

NFPA 20-2025 additive pump controller: the pump starts when the closed circuit loop containing the fire protection equipment opens; stopping is manual only, no automatic shutdown; lockout indicator and remote annunciation in duty-standby use; Additive Pump Controller marking
Additive pump controller. The pump starts when the closed circuit loop opens (10.9.2); stopping is manual only (10.9.3); a lockout, where supplied, has an indicator and remote annunciation (10.9.4.2). Loop and pump drawing is schematic.

Which rules apply?

Additive pump motor controllers comply with all of Sections 10.1 through 10.5 (and 10.8 for a transfer switch, where required), except where 10.9.2 through 10.9.5 specifically address a topic (10.9.1). Per the NFPA 20 Handbook (2022) commentary, before the 2003 edition this section was titled “Controllers for Foam Concentrate Pump Motors”; the title was revised to make clear it covers controllers in all systems where additives aid fire suppression.

TopicRule for the additive pump controllerClause
Automatic startingIn lieu of the pressure switch of 10.5.2.1, capable of starting by automatic opening of a closed circuit loop containing this fire protection equipment10.9.2
Manual shutdownProvided10.9.3.1
Automatic shutdownNot permitted10.9.3.2
LockoutWhere required, a lockout feature in duty-standby use10.9.4.1
Lockout indicationWhere supplied, a visible indicator and provisions for annunciating the condition at a remote location10.9.4.2
Marking“Additive Pump Controller”10.9.5

Starting: why a closed loop?

Per the Handbook (2022) commentary, additive pump controllers are generally started by remote means and conditions other than a drop in water pressure from sprinkler operation. The closed circuit loop ensures the pump starts even if the starting circuit or its components fail.

Stopping: why manual only?

Per the Handbook (2022), manual shutdown is the required method of stopping in additive systems; no automatic detection and signaling means can determine whether the system still needs to operate. Automatic shutdown is not permitted because an automatic shutdown function can malfunction.

Lockout

As a general rule, lockout, remote shutdown or an interlock preventing normal operation is not permitted unless approved by the authority having jurisdiction; 10.9.4 is one of the exceptions (10.3.4.5.3). Where required, the controller contains a lockout feature in duty-standby use (10.9.4.1); where supplied, the lockout is shown by a visible indicator with provisions for remote annunciation (10.9.4.2).

The Handbook (2022) commentary says the lockout allows the pump to be stopped when the additive supply is depleted, and gives the example that trying to suppress a chemical-based fire with water alone could spread or enlarge the fire. The standard gives no other reasoning.

When driven by a variable speed controller

Variable speed controllers for motors driving constant torque loads, such as additive (foam) pumps, are rated for constant torque applications, and their variable frequency drive (VFD) for constant torque motor load (10.10.1.4.1, 10.10.1.4.2). See variable speed fire pump controllers.

Common field mistakes

  • Automatic stop configured: contrary to 10.9.3.2; stopping is manual only.
  • Lockout without indicator or remote annunciation: contrary to 10.9.4.2.
  • Unmarked controller: 10.9.5 requires the “Additive Pump Controller” marking.
  • Drive rated for variable torque: a constant torque additive pump needs a constant torque rating per 10.10.1.4.

Checklist

  1. Controller complies with 10.1–10.5 (and 10.8 where required) (10.9.1).
  2. Automatic start on opening of the closed loop tested (10.9.2).
  3. Manual shutdown provided, no automatic shutdown (10.9.3).
  4. Lockout in duty-standby use where required; indicator and remote annunciation work (10.9.4).
  5. “Additive Pump Controller” marking present (10.9.5).

Frequently Asked Questions

Does an additive pump controller start on a pressure switch?

Per NFPA 20-2025 10.9.2, in lieu of the pressure switch of 10.5.2.1, automatic starting must be possible by the automatic opening of a closed circuit loop containing this fire protection equipment. Per the Handbook (2022), the closed loop ensures the pump starts even if the starting circuit fails.

Can an additive pump be stopped automatically?

No. Manual shutdown is provided and automatic shutdown is not permitted (10.9.3.1, 10.9.3.2). The Handbook (2022) notes that no automatic means can determine whether the system still needs to operate.

When does an additive pump controller have a lockout?

Where required, in duty-standby use (10.9.4.1). Where supplied, it is shown by a visible indicator and can be annunciated at a remote location (10.9.4.2). 10.3.4.5.3 names it as an exception to the general lockout prohibition.

How is an additive pump controller marked?

It is marked “Additive Pump Controller” (10.9.5). Other markings come from the general controller rules of 10.1 through 10.5 (10.9.1).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.