How many fire extinguishers are required?

Pick the use from the Annex 1 list and enter the gross area and number of storeys; the checker gives the number of 6 kg units under Article 99/2, a per-storey layout, the distance to the farthest point and whether a wheeled unit is needed. The 3D floor plan shows the units and their 25 m reach circles.

BYKHY Art. 99Annex 1 hazard class25 m reach3D floor plan

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

Area and hazard class set the count

Article 99/2 of the Turkish fire code (BYKHY) ties the number of portable extinguishers directly to the gross construction area: one 6 kg dry-powder or equivalent gas unit per 500 m² in low hazard, and per 250 m² in ordinary and high hazard. The area is the total of all storeys. The checker rounds up: 2400 m² in ordinary hazard gives 2400 / 250 = 9.6 → 10 units.

Hazard class (Annex 1)Area per unitExample: 2400 m²
Low hazard (Annex 1/A)500 m²5 units
Ordinary hazard 1–4 (Annex 1/B)250 m²10 units
High hazard 1–4 (Annex 1/C)250 m²10 units

Hazard class: Annex 1

Annex 1/A defines low hazard: spaces with low fire load and low combustibility, at least 30 minutes fire resistance and no compartment larger than 126 m², such as parts of schools and offices meeting this condition, and prisons. Annex 1/B lists ordinary hazard in four groups, for example hospitals, hotels, dwellings, restaurants, schools and offices in Ordinary Hazard 1; car parks, laundries and museums in Ordinary Hazard 2; shopping centres, printing works, furniture and textile production and plant rooms in Ordinary Hazard 3; cinemas, theatres, exhibition halls and chipboard production in Ordinary Hazard 4. Annex 1/C is high hazard: paint and varnish manufacture, plastic foam and sponge works, cellulose nitrate and fireworks factories and similar. Ordinary Hazard 1 and 2 areas with high fire-load parts such as painting count as Ordinary Hazard 3.

Extinguisher type: by fire class (99/1)

Water or clean-agent extinguishers are preferred in hospitals, care homes, nurseries and similar places.

Wheeled units (99/3)

Car parks, storage areas, plant rooms and similar places need a wheeled extinguisher in addition to the portable ones. The article gives no number or size; choose by fire class and consult the local fire brigade if needed (99/8). Wheeled units are certified to TS EN 1866, the others to TS 862-EN 3 (99/6).

Layout: the 25 m rule

Under Article 99/4 the distance to an extinguisher is at most 25 m. Units sit near passageways, evenly distributed and signed, and may be inside or next to a hose cabinet. Behind doors, in closed cupboards (other than hose cabinets), in deep recesses and above heaters are not allowed. Units heavier than 4 kg and lighter than 12 kg hang no higher than about 90 cm above the floor (99/5).

The checker divides each storey into equal cells and places one unit at the centre of each cell. The number of cells covers both the storey’s share of the area rule (storey area / 250 or 500) and a farthest point within 25 m in a straight line. This is a layout suggestion, not a regulation value: walls and partitions lengthen the walking distance, so check the final layout on the plan. The suggested total can exceed the 99/2 minimum; the excess comes from distribution.

Maintenance (99/7): annual on-site inspection to TS ISO 11602-2; at the end of the fourth year the agent is renewed and a hydrostatic test made. When units are taken for refilling, the service company leaves the same number of ready units of the same type.

What the 3D floor plan shows

One storey is built from your area and plan ratio, with the storeys below shown as ghosts. The units drop into place and each one shows a glowing 25 m reach circle. The amber ring is the farthest point of the storey; the dashed line shows the distance to the nearest unit. With “Reach walk” on, a person walks that route. If a wheeled unit is required, it appears in a corner.

Frequently Asked Questions

How many square metres per fire extinguisher in Turkey?

Under Article 99/2 of the Turkish fire code, one 6 kg dry-powder or equivalent gas extinguisher per 500 m² of gross area in low hazard, and per 250 m² in ordinary and high hazard. The area is the total of all storeys and the result is rounded up.

What is the maximum distance to a fire extinguisher?

Under Article 99/4 the distance to an extinguisher is at most 25 m. Units must be near passageways, evenly distributed and signed, and not behind doors, in closed cupboards (other than hose cabinets) or near heaters.

Where are wheeled extinguishers mandatory?

Under Article 99/3, car parks, storage areas, plant rooms and similar places need a wheeled extinguisher in addition to portable ones. The article gives no number or size; the local fire brigade may be consulted (99/8).

How often are fire extinguishers serviced?

Under Article 99/7, an on-site inspection once a year to TS ISO 11602-2; at the end of the fourth year the agent is renewed and a hydrostatic test made. The service company must hold a filling and service competence certificate.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content