Tank dike (bund) volume

Enter the tanks and the bund dimensions; the tool gives the bund volume required by BYKHY 119/2, the net volume after deducting the other tanks, the minimum wall height and the tank-to-bund distance check.

BYKHY Art. 119/2Guide Figure 119.2Bund sectionClause references

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

34 more calculators ↓

What the tool does

Bunding (the tank dike) that holds liquid spilled from outdoor above-ground tanks is governed by Article 119/2 of Turkey's Regulation on the Fire Protection of Buildings (BYKHY). For your tank arrangement the tool finds the bund volume the regulation requires, works out the net volume your bund dimensions provide, gives the minimum bund wall height and checks the tank-to-bund distance under 119/2-ğ. The result shows a section with the bund walls, tanks and the required liquid level.

Which text? The tool is based on the consolidated text of the regulation up to the 09.07.2015 amendment and on the Ministry's December 2024 BYKHY Guide (Figure 119.2). The regulation has been amended since; confirm against the current text in the Official Gazette and with the fire brigade.

Article 119/2: required bund volume

CaseBund volumeClause
Tanks of the same sizeVolume of one tank119/2-a
Tanks of different sizesVolume of the largest tank119/2-a
Portable tanks75% of the total volume, or at least the volume of the largest portable tank119/2-b
Mixed storageSum of the volumes under (a) and (b)119/2-c
Crude oil, carbon disulphideTotal volume119/2-ç

The portable-tank clause joins its two conditions with "or at least"; the tool takes the larger of the two (safe reading). Example: portable tanks totalling 8 m³ with the largest at 2 m³ give 0.75 × 8 = 6 m³. With three 50 m³ fixed tanks in the same bund, mixed storage needs 50 + 6 = 56 m³.

How the net volume is worked out

Guide Figure 119.2 shows the bund volume as side lengths times height. In a real bund the other tanks and the foundations take up space up to the wall height and liquid cannot fill it. The regulation does not state this deduction; the tool makes it as a calculation assumption:

Vnet(h) = L × W × h − Σ π/4 × Di² × min(h, hfound + Hi) − π/4 × Dlargest² × min(h, hfound) − Vother

The minimum bund height is the height at which the net volume equals the required volume. If the tank footprints fill the bund area no such height exists, and the tool says so.

Bund and tank layout

RuleRequirementClause
Tank to bundAt least 3 m from bund walls lower than 4/5 of the tank height, measured from the tank shell119/2-ğ
Dividing wallsNot lower than 4/5 of the outer wall; channels open on top119/2-ı
ConstructionExcavated or walled; non-combustible except the sealing membrane; liquid-tight in a fire119/2-g
Penetrations and drainageSealed pipes; water can be drained; closable outlet with a liquid separator119/2-h
Inside the bundOnly valves and pipes besides the tanks119/2-i

The 3 m rule in 119/2-ğ is written only for bund walls lower than 4/5 of the tank height; for a higher wall the clause sets no distance. The tool works out 4/5 of each tank group's height and compares the shortest distance you enter.

How many bund zones?

Class I, II and III liquids other than crude oil and carbon disulphide may share one bund zone while the total, expressed as Class IA, does not exceed 12,500 litres (119/2-d). Article 119 gives no conversion ratio; the tool uses the storage-building ratios of 118/2 (IB/2, IC/4, II/12, IIIA/40, IIIB/80) as an assumption and warns if the limit is exceeded. For crude oil or carbon disulphide one bund zone is allowed while the stored volume stays within 15,000 m³ and the bund surface within 700 m² (119/2-e); the tool takes the surface as the bund inside area. Clauses (a) and (b) also apply where Class I, II and III liquids are stored together (119/2-f).

The bund does not replace the protection zone around the tanks: for above-ground tanks the clearance comes from Annex 12/C, for portable containers from Annex 12/D, and at least two-thirds of it lies outside the bund (119/3).

Common mistakes

For tank distances to boundaries and between tanks, use the Annex 12/C part of the flammable liquid class and storage tool.

Frequently Asked Questions

How is the bund volume taken for tanks of different sizes?

Under BYKHY 119/2-a the volume of the largest tank; for tanks of the same size, the volume of one tank. For crude oil and carbon disulphide the total volume is needed (119/2-ç).

What is the 75% rule for portable tanks?

The bund volume is 75% of the total volume of the portable tanks, or at least the volume of the largest portable tank (119/2-b). The tool takes the larger.

Are the other tanks in the bund deducted?

The regulation does not say; Guide Figure 119.2 shows only side lengths × height. As a stated assumption the tool deducts the volume the other tanks and the foundations take up to the bund height.

How far must a tank be from the bund wall?

At least 3 m from walls lower than 4/5 of the tank height, measured from the tank shell (119/2-ğ). For a higher wall the clause sets no distance.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →