This article in the NFPA 25 series covers Chapter 15: impairment management. Almost every inspection, test and maintenance task in the other articles takes a system, or part of one, out of service at some point; the fire pump, sprinkler and other chapters then send you to Chapter 15. The chapter is short but is the one most often skipped in the field: who authorizes, where the tag goes, who is notified, what happens when the outage passes 10 hours, and how the system is handed back. Below these are set out as a step-by-step procedure and checklist. Every line carries its clause number from NFPA 25-2026; references beginning with “Annex A” are explanatory material, not mandatory requirements.

In short: The property owner or designated representative assigns an impairment coordinator, and is the coordinator if no one is assigned (15.2). A system or part taken out of service is marked with a tag posted at the fire department connection and the system control valve (15.3). The coordinator authorizes each preplanned impairment and first verifies the nine items in 15.5.2: extent and duration, risk review, recommendations, notification of the fire department, insurer, alarm company and area supervisors, tags and materials (15.5). If a system is out of service for more than 10 hours in a 24-hour period, one of evacuation, an approved fire watch, a temporary water supply or an approved ignition-source program is required (15.5.2(4)). Emergency impairments follow the same steps (15.6.2). On restoration, tests are done, everyone is advised and the tag comes off (15.7).

A. Definitions: what counts as an impairment

TermDefinitionClause
ImpairmentA condition where a fire protection system or unit or portion of it is out of order, and the condition can result in it not functioning in a fire event3.3.22
Emergency impairmentA water-based system or portion out of order due to an unplanned occurrence, or an impairment found while performing inspection, testing or maintenance3.3.22.1
Preplanned impairmentA water-based system or portion out of service due to work planned in advance3.3.22.2

The Annex A.3.3.22 explanation clarifies two points. “Unit” refers to a fire pump (NFPA 20), a water storage tank (NFPA 22) or a private fire service main (NFPA 24) with their connections, not to an individual sprinkler, valve or piece of pipe. And temporarily shutting a system down for routine inspection, testing and maintenance, under constant attendance by qualified personnel and where it can be restored quickly, should not be considered an impairment. Similarly, under 4.4 water supplies, including fire pumps, stay in service during inspection, testing and maintenance unless under constant attendance by qualified personnel or unless the Chapter 15 procedures are followed.

B. Scope and general rule

CheckCriterionClause
☐ Impairment programChapter 15 gives the minimum requirements15.1.1.1
☐ During the impairmentMeasures are taken to minimize increased risk and limit the duration15.1.1.2
☐ Impairment occurs or is found during inspection, testing or maintenanceChapter 15 procedures are followed, including tagging the impaired system4.1.12.1
☐ NotificationThe AHJ, the fire department where required, and the alarm-receiving facility are notified when an impairment is identified or before a system or its supply is tested or shut down4.1.4
☐ Preplanned and emergency impairmentsNotification is required for both; the additional information of 15.5.2 is included as applicable4.1.4.1, 4.1.4.1.1
☐ Content of a shutdown or test noticePurpose, system or component involved, estimated time and expected duration4.1.4.2

The owner’s general responsibilities are covered separately in the series article on general requirements.

C. Impairment coordinator

CheckCriterionClause
☐ Coordinator assignmentThe property owner or designated representative assigns an impairment coordinator to meet this chapter15.2.1
☐ No specific designeeThe property owner or designated representative is considered the coordinator15.2.2
☐ Lease, written use agreement or management contract expressly gives ITM authority to the tenant, management firm or managing individualThat party assigns a person as impairment coordinator15.2.3

D. Tag impairment system

CheckCriterionClause
☐ System or part removed from serviceIndicated with a tag15.3.1
☐ Where the tag goesAt each fire department connection, the system control valve and other locations the AHJ requires, stating which system or part is out of service15.3.2

Per the Annex A.15.3.1 explanation, the tag alerts occupants and the fire department that all or part of the system is out of service. It should be weather resistant, plainly visible and of sufficient size (typically 4 in. × 6 in., 100 mm × 150 mm), and should identify the impaired system, the date and time the impairment began, and the person responsible. The sample tag in the standard (Figure A.15.3.1) is a valve card marked “sprinkler valve shut”: it records which buildings the valve controls, who shut it and when; the reverse asks for a 2 in. (50 mm) drain test after the valve is reopened, treats an extreme pressure drop that does not recover as an impairment needing immediate investigation, and records static and flowing pressures, the tester’s signature and the date.

The Annex A.15.3.2 explanation gives the reason for the tag at the fire department connection: a tag on the riser alone could go unnoticed for a long time if firefighters have trouble getting into the building or the sprinkler control room.

E. Impaired equipment

Impaired equipment is the water-based fire protection system, or part of it, that is removed from service (15.4.1). It includes, but is not limited to, the following (15.4.2):

Equipment that can be impairedRelated article in the seriesClause
Sprinkler systemsChapter 5: sprinklers15.4.2(1)
Standpipe systemsChapter 6: standpipe and hose15.4.2(2)
Fire hose systemsChapter 6: standpipe and hose15.4.2(3)
Underground fire service mainsChapter 7: private fire service mains15.4.2(4)
Fire pumpsChapter 8: fire pumps15.4.2(5)
Water storage tanksChapter 9: water storage tanks15.4.2(6)
Water spray fixed systemsChapter 10: water spray15.4.2(7)
Foam-water sprinkler systemsChapter 11: foam-water sprinklers15.4.2(8)
Water mist systemsChapter 12: water mist15.4.2(9)
Fire service control valvesChapter 13: valves and common components15.4.2(10)
Water supply—15.4.2(11)

F. Preplanned impairment: step-by-step procedure

According to the Annex A.15.5 explanation, the need for temporary protection, termination of all hazardous operations and the frequency of checks in the affected areas should be determined, and all possible work done in advance to shorten the impairment. Where possible, temporary feedlines should keep portions of systems in service while work is completed. Systems should not be taken out of service just because the building is not in use; where a system out of service for a long period, as in idle or vacant property, is returned to service, qualified personnel should be retained to inspect and test it.

Before giving authorization the coordinator is responsible for verifying these steps (15.5.2):

StepWhat is doneClause
☐ 1. AuthorizationAll preplanned impairments are authorized by the impairment coordinator15.5.1
☐ 2. Extent and durationThe extent and expected duration of the impairment have been determined15.5.2(1)
☐ 3. Site reviewThe areas or buildings involved have been inspected and the increased risks determined15.5.2(2)
☐ 4. Mitigation recommendationsRecommendations to mitigate the increased risks have been submitted to management or the property owner or designated representative15.5.2(3)
☐ 5. Over 10 hours in 24The coordinator arranges one of the four options below15.5.2(4)
☐ 6. Fire departmentThe fire department has been notified15.5.2(5)
☐ 7. Other partiesThe insurance carrier, alarm company, property owner or designated representative and other authorities having jurisdiction have been notified15.5.2(6)
☐ 8. Area supervisorsThe supervisors in the affected areas have been notified15.5.2(7)
☐ 9. Tag systemA tag impairment system has been implemented (Section 15.3)15.5.2(8)
☐ 10. MaterialsAll necessary tools and materials are assembled at the impairment site15.5.2(9)

More than 10 hours in a 24-hour period: four options

Where a fire protection system will be out of service for more than 10 hours in a 24-hour period, the coordinator arranges one of the following (15.5.2(4)):

OptionRequirement and Annex A explanationClause
(a) EvacuationEvacuation of the building or the portion affected by the system out of service15.5.2(4)(a)
(b) Approved fire watchAnnex A.15.5.2(4)(b): trained personnel continuously patrolling the affected area. Ready access to extinguishers and the ability to notify the fire department promptly matter. The patrol looks not only for fire but also checks that other features such as egress routes and alarm systems are available and working15.5.2(4)(b)
(c) Temporary water supplyAnnex A.15.5.2(4)(c): sources such as a large-diameter hose from a hydrant to a fire department connection, a portable tank and portable pump, or a standby fire department pumper and/or tanker15.5.2(4)(c)
(d) Ignition source and fuel programEstablishing and implementing an approved program to eliminate potential ignition sources and limit the fuel available to the fire. Annex A.15.5.2(4)(d): depending on the occupancy, stopping certain processes or cutting fuel to some machines may be enough; “No Smoking” and “No Hot Work” (cutting, grinding, welding) policies are also helpful while the system is out of service15.5.2(4)(d)

G. Emergency impairments

CheckCriterionClause
☐ Examples of emergency impairmentsInterruption of water supply, frozen or ruptured piping, equipment failure, and impairments found during inspection, testing or maintenance (not limited to these)15.6.1
☐ What the coordinator doesImplements the steps of Section 15.515.6.2
☐ TagThe impaired system is tagged4.1.12.1, 15.3
☐ NotificationNotification is also required for emergency impairments4.1.4.1

The Annex A.15.6 explanation adds system leakage to the list. Per the Annex A.15.6.2 explanation, when one or more impairments are found during inspection, testing and maintenance, the owner or authorized representative should be notified in writing. The sample notice in the standard (Figure A.15.6.2) uses a checklist: control valve shut, low water pressure during a flow test (possible obstruction or partly closed valve), frozen, leaking or obstructed pipes, disconnected piping, missing, damaged or obstructed fire department connection, dry pipe valve that cannot be reset, quick-opening device out of service, painted, corroded, damaged or loaded sprinklers, fire pump out of service, detection/actuation system out of service, and other.

If the inspection turned up findings such as plugged sprinklers or foreign material in drain tests, an obstruction investigation under Chapter 14 may also be needed before the system is handed back.

H. Restoring systems to service

When all impaired equipment is back in normal working order, the coordinator verifies the following (15.7):

StepWhat is doneClause
☐ 1. Inspection and testingThe inspections and tests needed to verify the affected systems are operational have been done; the relevant chapter of the standard gives the type15.7(1)
☐ 2. Area supervisorsAdvised that protection is restored15.7(2)
☐ 3. Fire departmentAdvised that protection is restored15.7(3)
☐ 4. Other partiesProperty owner or designated representative, insurance carrier, alarm company and other authorities having jurisdiction advised that protection is restored15.7(4)
☐ 5. TagThe impairment tag has been removed15.7(5)

Which test is needed is set by the “Summary of Component Replacement [Action] Requirements” table in each system chapter; the system is verified by the appropriate inspection or test from that table (4.1.12.2). The AHJ, fire department and alarm-receiving facility are notified when the system, supply or component returns to service or the test is complete (4.1.4.3).

Systems shut down for a long time

The Annex A.15.7 explanation recommends that systems in idle or vacant buildings that were shut off, drained and left unmaintained for a long time be restored by qualified personnel or a qualified contractor, and gives an example procedure. It is a recommendation; the mandatory steps are those in 15.7. Returning a system to service after more than a year shut down also requires an obstruction investigation under 14.3.1(11).

StepExample procedure in the Annex A.15.7 explanationSource
Trace the pipingTrace all piping from the extremities to the main connections, checking for blank gaskets in flanges, closed valves, corroded or damaged sprinklers, nozzles or piping, insecure or missing hangers and insufficient support. Make repairs, adjustments and needed extensionsAnnex A.15.7(1)
Air test and fillingRun a low-pressure (40 psi) air test before admitting water; once the piping is proven tight, introduce water slowly with precautions against escaping water from undiscovered defects. Once full at normal pressure, make drain valve tests to catch any overlooked closed valve; flush all available pipes and complete an obstruction investigation to make sure the system is clearAnnex A.15.7(2)
Hydrostatic testWhere the system was damaged by freezing or other extensive damage may have occurred, a full hydrostatic test per NFPA 13 can show whether integrity has been maintainedAnnex A.15.7(3)
Valves and alarm connectionsExamine, put in proper condition and test dry pipe valves, quick-opening devices, alarm valves and all alarm connectionsAnnex A.15.7(4)
Water suppliesFire pumps, pressure and gravity tanks, reservoirs and other supply equipment get proper attention before going into service; test each supply separately, then together if designed to work togetherAnnex A.15.7(5)
Control valvesOperate all control valves from closed to fully open and leave them sealed, locked or with a tamper switchAnnex A.15.7(6)

I. One-page checklist

StageWhat is doneClause
Preparation (ongoing)
CoordinatorThe property owner or designated representative assigns an impairment coordinator; without one, they are the coordinator15.2.1, 15.2.2
ProgramMeasures that minimize increased risk and limit the duration of the impairment15.1.1.2
When an impairment starts
PreplannedAuthorization by the coordinator and verification of the nine items in 15.5.215.5.1, 15.5.2
EmergencyThe coordinator implements the same 15.5 steps15.6.2
TagTag at the fire department connection and the system control valve15.3.2
More than 10 hours in 24Evacuation, approved fire watch, temporary water supply, or an approved program limiting ignition sources and fuel15.5.2(4)
Return to service
VerificationRequired inspections and tests, notifications, removal of the tag15.7(1)–(5)

J. Common mistakes in the field

CheckCriterionClause
☐ No one knows who the coordinator isWithout an assignment the owner or representative is responsible; where ITM authority is contracted out, the tenant or management firm assigns a person15.2.2, 15.2.3
☐ Tag hung only on the riserTags also go on every fire department connection and the system control valve15.3.2
☐ System left shut overnight with no extra measuresPast 10 hours in 24, one of the four options in 15.5.2(4) is mandatory15.5.2(4)
☐ A defect found during inspection only goes in the reportIt is an emergency impairment; the 15.5 steps apply15.6.1, 15.6.2
☐ Job done, valve opened, nothing elseInspections and tests, notification of all parties and removal of the tag15.7
☐ System shut down because the building is emptyAnnex A.15.5: systems should not be removed from service because the building is not in useAnnex A.15.5

Frequently Asked Questions

Who is the impairment coordinator?

The person the property owner or designated representative assigns to meet Chapter 15 (15.2.1). Without an assignment, the owner or representative is the coordinator (15.2.2). If a contract gives ITM authority to a tenant or management firm, that party assigns the coordinator (15.2.3).

Where is the impairment tag posted?

At each fire department connection, the system control valve and any other locations the AHJ requires, stating which system or part is out of service (15.3.2). The Annex A.15.3.1 explanation suggests a durable, visible tag, typically 4 in. × 6 in. (100 mm × 150 mm).

What is required if a system is out for more than 10 hours?

If a system is out of service for more than 10 hours in a 24-hour period, the coordinator arranges one of: evacuation of the affected area, an approved fire watch, a temporary water supply, or an approved program to eliminate ignition sources and limit fuel (15.5.2(4)).

Who must be notified of a preplanned impairment?

The fire department; the insurance carrier, alarm company, property owner or designated representative and other authorities having jurisdiction; and the supervisors of the affected areas (15.5.2(5)–(7)). Notification is also required for emergency impairments (4.1.4.1).

What is verified when a system is restored to service?

Inspections and tests showing the affected systems are operational, notice that protection is restored to supervisors, the fire department, the owner, insurer, alarm company and AHJs, and removal of the tag (15.7).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 25-2026, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems: Chapter 15 (15.1–15.7), definitions 3.3.22–3.3.22.2, 4.1.4, 4.1.12 and 4.4, with Annex A explanations A.3.3.22, A.15.3.1–A.15.7 and Figures A.15.3.1 and A.15.6.2 (explanatory, not mandatory). The content of other chapters and of NFPA 13 referenced by Chapter 15 is not reproduced here.