Tank farm dike foam calculator

Enter the dike floor area and tank types (count and size) and pick the liquid; the tool finds the dike height and gives the NFPA 30 dike capacity and diking checks, and the NFPA 11 foam solution for the dike, the outlet or monitor count, supplementary hose streams, concentrate and water, clause by clause.

NFPA 30-2024 22.11NFPA 11-2024 5.7Outlet layoutConcentrate and reserve

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

38 more calculators ↓

How is foam calculated for a tank farm dike?

Aboveground tanks of ignitible liquids are usually surrounded by a dike. The dike does two jobs: it holds a spill (NFPA 30 Section 22.11) and, if a fire starts inside it, it limits the area to be covered with foam (NFPA 11 Section 5.7). This tool combines both in one sheet: first the dike capacity and diking rules, then the foam solution to apply in the dike, the number of outlets or monitors, supplementary hose streams, concentrate and water. Each line shows the clause it relies on.

1. Dike capacity (NFPA 30 22.11.2.2)

The dike must hold the greatest amount of liquid that can be released from the largest tank, assuming a full tank. With more than one tank, the volume of the other tanks below the dike height is deducted (22.11.2.2.1). The tool treats tanks as vertical cylinders with foundations of the tank diameter; only the foundation of the largest tank is deducted. If the net volume is short, it also gives the minimum dike height.

2. Diking rules

The outside base of the dike is at least 10 ft (3 m) from a property line that is or can be built upon (22.11.2.3). Where the average interior height exceeds 6 ft (1.8 m), access and egress are provided and tank shells are at least 5 ft (1.5 m) from the toe of the interior wall (22.11.2.5). A dike with two or more tanks is subdivided by drainage channels or intermediate dikes at least 18 in. (450 mm) high (22.11.2.6). Minimum shell-to-shell spacing of adjacent tanks comes from Table 22.4.2.1.

3. Foam rate and time (NFPA 11 Table 5.7.3.2)

For hydrocarbons: low-level fixed outlets at least 0.10 gpm/ft² (4.1 mm/min), monitors 0.16 gpm/ft² (6.5 mm/min); 30 min for Class I and 20 min for Class II. For compressed air foam and for polar liquids requiring alcohol-resistant foam the rate comes from the manufacturer’s listing; for polar liquids the minimum time is 30 min (5.7.4.3). Solution flow is rate × area.

4. Outlet and monitor layout

Low-level outlets are around the dike wall and, where necessary, inside the dike (5.7.3.5.2). With 60 gpm (230 L/min) or less per outlet, no point in the dike may be more than 30 ft (9 m) from an outlet; above that, outlets are at most 60 ft (18 m) apart (5.7.3.5.3). Monitors are outside the dike and the design allows for wind-carried foam (5.7.3.5.4). The tool finds the outlet count from both the flow and the layout rule and takes the larger; the layout count is an estimate, the actual layout is drawn in the design.

5. Hose streams, concentrate and reserve

In addition to the tank foam installations, supplementary foam hose streams and times are added based on the largest tank diameter (Tables 5.9.2.2 and 5.9.2.4; at least 50 gpm (190 L/min) each). Concentrate is the proportioning percentage times the total solution volume; the reserve meets the worst-case need (4.3.2.5.2).

Good to know

NFPA 11 does not define deducting tank footprints from the dike area; in the tool this deduction is optional and is stated as a design assumption when selected. Large dikes may be subdivided to limit the total solution (5.7.3.3.2); then enter the area of the largest subdivision.

Frequently Asked Questions

How is the dike capacity determined?

Per NFPA 30 22.11.2.2 the dike holds the greatest amount of liquid that can be released from the largest tank, assuming a full tank. The volume of the other tanks below the dike height is deducted (22.11.2.2.1).

At what rate is foam applied in a dike?

NFPA 11 Table 5.7.3.2: for hydrocarbons at least 0.10 gpm/ft² (4.1 mm/min) with low-level fixed outlets and 0.16 gpm/ft² (6.5 mm/min) with monitors; 30 min for Class I and 20 min for Class II. For polar liquids the rate comes from the manufacturer and the time is at least 30 min (5.7.4.3).

How far apart are low-level foam outlets?

With 60 gpm (230 L/min) or less per outlet, no point in the dike may be more than 30 ft (9 m) from an outlet; above that, outlets are at most 60 ft (18 m) apart (NFPA 11 5.7.3.5.3).

Are tank footprints deducted from the foam area?

NFPA 11 does not define this; it requires foam to be applied uniformly over the dike area (5.7.3.3.1). In the tool the deduction is optional and is stated as a design assumption when selected.

Where are foam monitors located?

Outside the dike (NFPA 11 5.7.3.5.4). As primary protection the design allows for wind-carried foam, and a compact high-velocity stream is directed against dike walls or tank surfaces, not into the burning liquid.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →