Enter the system type, density, area, sprinkler spacing, device type and temperature rating; the tool gives the solution flow, number of sprinklers, foam duration, concentrate and water, spare sprinklers and the spacing, device and rating checks to NFPA 11-2024 Chapter 6.

NFPA 11-2024 Chapter 6Deluge and wet pipeTable 6.4.11.3Preliminary sizing

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

38 more calculators ↓

How is a foam-water sprinkler system calculated?

Foam-water sprinkler and spray systems first discharge foam-water solution for a set time, then water until manually shut off (NFPA 11-2024 6.2.3.2). They may be wet pipe, dry pipe, deluge or preaction (6.2.2). The calculation rests on five questions: density, area, duration, spacing, and sprinkler type and rating.

1. Density

The design density follows the applicable occupancy standard but is never less than 0.16 gpm/ft² (6.5 mm/min) (6.5.2.2.1). With SFFF the rate is set from Annex H and the manufacturer’s recommendations (6.5.2.2.1.1). Only alcohol-type foam is used on fires in water-soluble and polar solvents (6.1.3.4).

2. Area and duration

For wet, dry and preaction systems the total design area is 5000 ft² (465 m²), unless the occupancy standard specifies another (6.5.2.2.2.1). The solution discharges for 10 minutes: over the entire system area for deluge and spray systems, over the design area for the others (6.5.2.3.1). Where actual discharge exceeds the minimum, the time may be reduced in proportion, never below 7 minutes (6.5.2.3.2).

3. Spacing

Area per sprinkler may not exceed 100 ft² (9.3 m²), and spacing on and between branch lines may not exceed 12 ft (3.7 m) (6.5.6.1). In buildings with primary structural members 25 ft (7.6 m) apart, line-to-line spacing may be 12 ft 6 in. (3.8 m) at a density of ≥0.25; the standard prints this threshold without a unit, and the tool reads it as 0.25 gpm/ft², the chapter’s density unit, and says so in the result.

4. Device type and temperature rating

Deluge and spray systems may use air-aspirating devices (foam-water sprinklers and spray nozzles) or non-air-aspirating ones (standard sprinklers) (6.4.2.2); wet, dry and preaction systems use automatic, non-air-aspirating devices (6.4.2.3). Sprinklers at the roof or ceiling are rated 250–300 °F (121–149 °C), those at an intermediate level 135–170 °F (57–77 °C), unless ambient conditions require higher (6.5.7). Ratings, classes and color codes for glass-bulb and fusible-link sprinklers are in Tables 6.4.11.3(a) and (b).

5. Concentrate, water and spares

Concentrate is the proportioning percentage × solution flow × time. How a reserve is provided is agreed with the AHJ (6.2.4). The water supply meets the fixed system demand plus 250 gpm (946 L/min) for hose streams for at least 60 minutes (4.2.2.3.1). Keep at least 6 spare sprinklers under 300 sprinklers, 12 for 300–1000 and 24 above (6.4.11.5).

Scope

The tool gives the Chapter 6 criteria; the pipe hydraulic calculation is done separately to NFPA 13 (6.5.10.1.3). For tanks, dikes and spills use the NFPA 11 design criteria wizard. Background: sprinkler types and temperature ratings, design area, spacing and duration.

Frequently Asked Questions

What is the minimum density of a foam-water sprinkler system?

The occupancy standard density applies, but never less than 0.16 gpm/ft² (6.5 mm/min) (NFPA 11-2024 6.5.2.2.1). With SFFF the rate comes from Annex H and the manufacturer.

How long is foam discharged?

10 minutes: over the entire system area for deluge and spray systems, over the 5000 ft² (465 m²) design area for wet, dry and preaction systems (6.5.2.3.1). With a higher actual discharge the time is reduced in proportion, never below 7 minutes (6.5.2.3.2).

Where may air-aspirating foam-water sprinklers be used?

Only on deluge and spray systems (6.4.2.2). Wet, dry and preaction foam-water systems must use automatic, non-air-aspirating devices (6.4.2.3).

Which temperature rating is used for foam-water sprinklers?

250–300 °F (121–149 °C, high) at the roof or ceiling and 135–170 °F (57–77 °C) at an intermediate level, unless ambient conditions require a higher rating (6.5.7.1, 6.5.7.2).

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store